
2/13
Building Technologies Division CC1N7786en
Infrastructure & Cities Sector 07.08.2013
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
Do not open, interfere with or modify the unit!
•All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
•Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
inadvertently switched on again and that it is indeed dead. If not disconnected,
there is a risk of electric shock hazard
•Ensure protection against electric shock hazard by providing adequate protection
for the burner control’s terminals
•Each time work has been carried out (mounting, installation and service work, etc.),
heck to ensure that wiring is in an orderly state and make the safety checks as
described in «Commissioning notes».
•Press the lockout reset button / operation button only manually (applying a force of
no more than 10 N), without using any tools or pointed objects
•Do not press the lockout reset button on the unit or the remote reset button
(input 21) for more than 10 seconds, since this would damage the lockout
relay inside the unit
•Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage
Mounting notes
•Ensure that the relevant national safety regulations are complied with
Installation notes
•Always run the high-voltage ignition cables separately while observing the greatest
possible distances to the unit and to other cables
•Do not mix up live and neutral conductors
•Install switches, fuses and earthing, in compliance with local regulations
•Make certain that the maximum permissible current rating of the connection
terminals will not be exceeded
Caution!
•Observe the polarity
Burner controls LGI16... are not able to detect wrong polarity of live and
•When used in connection with UV detector QRA53... / QRA55..., terminal 22 must
be earthed
•For repetitive operation, remove wire link «J» between terminals 8 and 11 in base
AGM15
Warning!
•Danger - high voltage
In single-electrode operation, measurement of the ionization current is not
possible. During the ignition times, the ionization current path carries high