5 List of error messages of LMV5 system
Error
code Diagnostic
code Device Display Meaning for the LMV5 system Troubleshooting
B6 # LMV5 COx alarm error messages
B6 01 LMV5 COx value invalid COx signal is not within the defined range
of values or there is a cable break.
Check connection between the COx sensor and PLL52, check
cable connection on the PLL52 basic unit, correct resistance
dimensioning
B6 02 LMV5 COx monitoring time COx alarm
undefined No valid value has been entered in the
parameter Time COx Alarm Set Time COx Alarm parameter correctly
B6 03 LMV5 COx monitoring time constant Tau
undefined Missing path time constant Perform adaption of O2 trim control, Tau Low-Fire and / or Tau
High-Fire have no valid value
B6 04 LMV5 COx limit exceeded in operation COx indicated by COx sensor Optimize combustion settings
B6 05 LMV5 COx limit exceeded in prepurge COx indicated by COx sensor Optimize combustion settings
B7 # LMV5 PLL52 error during active COx supervision
B7 00..3E LMV5... COx supervision
No valid COx signal from PLL52 Error messages from the PLL52... when
COx supervision is active Check the supply air temperature at the connection (short-
circuit, open-circuit) Check the ambient temperature
B7 01 O2M
No valid COx signal from PLL52 CRC fault during ROM test If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 02 O2M
No valid COx signal from PLL52 CRC fault during RAM test If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 04 O2M
No valid COx signal from PLL52 Fault during key value check If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 05 O2M
No valid COx signal from PLL52 Error code for time block overflow If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 07 O2M
No valid COx signal from PLL52 Sync fault or CRC fault If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 08 O2M
No valid COx signal from PLL52 Error code for main loop counter If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 09 O2M
No valid COx signal from PLL52 Fault during stack test If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 0A O2M
No valid COx signal from PLL52 Feedback values invalid If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 10 O2M
No valid COx signal from PLL52 Nernst voltage outside the valid range Check the connection (correct polarity, short-circuit)
B7 12 O2M
No valid COx signal from PLL52 Thermo couple voltage outside the valid
range Check connections (polarity, short-circuit, open-circuit).
Check power supply to the O2 module.
Check fuse F2 on the O2 module.
Check heating control on the QGO.