manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens N 526E02 Service manual

Siemens N 526E02 Service manual

This manual suits for next models

1

Other Siemens Controllers manuals

Siemens SIMATIC NET MOBIC T8 User manual

Siemens

Siemens SIMATIC NET MOBIC T8 User manual

Siemens RVP201 Operator's manual

Siemens

Siemens RVP201 Operator's manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens i-3 User manual

Siemens

Siemens i-3 User manual

Siemens IQHeat User manual

Siemens

Siemens IQHeat User manual

Siemens Simatic S7-300 User manual

Siemens

Siemens Simatic S7-300 User manual

Siemens OpenAir GEB 131.1E User manual

Siemens

Siemens OpenAir GEB 131.1E User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens CFG3.F200 User manual

Siemens

Siemens CFG3.F200 User manual

Siemens SIMATIC S7-1200 CP 1243-8 IRC User manual

Siemens

Siemens SIMATIC S7-1200 CP 1243-8 IRC User manual

Siemens SIRIUS 3RF29-0KA Series User manual

Siemens

Siemens SIRIUS 3RF29-0KA Series User manual

Siemens GGA 1E Series User manual

Siemens

Siemens GGA 1E Series User manual

Siemens LMV37.4 Series Operator's manual

Siemens

Siemens LMV37.4 Series Operator's manual

Siemens LCM-OAVS 570-804PA User manual

Siemens

Siemens LCM-OAVS 570-804PA User manual

Siemens SIRIUS S00 User manual

Siemens

Siemens SIRIUS S00 User manual

Siemens RUGGEDCOM WIN5123 User manual

Siemens

Siemens RUGGEDCOM WIN5123 User manual

Siemens SEZ50MB User manual

Siemens

Siemens SEZ50MB User manual

Siemens LME SERIES Operating and maintenance instructions

Siemens

Siemens LME SERIES Operating and maintenance instructions

Siemens RVP36 User manual

Siemens

Siemens RVP36 User manual

Siemens Delta Series User manual

Siemens

Siemens Delta Series User manual

Siemens instabus JB520C23 User manual

Siemens

Siemens instabus JB520C23 User manual

Siemens SINUMERIK 808D User manual

Siemens

Siemens SINUMERIK 808D User manual

Siemens WS 720 A User manual

Siemens

Siemens WS 720 A User manual

Siemens SITOP PSU8600 User manual

Siemens

Siemens SITOP PSU8600 User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Gamma instabus
Schalt-/Dimmaktor N 526E02
Switching/Dimming Actuator N 526E02
8x AC 230 V / 16 A
5WG1 526-1EB02
Bedien- und Montageanleitung
Operating and Mounting Instructions
Stand: Februar 2007
As at: February 2007
Bild / Figure 1
D
Produkt- und Funktionsbeschreibung
Der Schalt-/Dimmaktor N 526E02 ist ein Reiheneinbaugerät im
N-Maß. Er steuert acht voneinander unabhängige Gruppen (Ka-
näle) von Leuchtstofflampen über den 1...10V DC- Steueran-
schluss dimmbarer elektronischer Vorschaltgeräte (z.B. EVG
Dynamic).
Zusätzlich ist pro Kanal ein Schaltkontakt zum direkten Ein- und
Ausschalten der Leuchtstofflampengruppen vorhanden. Dieser
Schaltkontakt kann auch über einen Schiebeschalter von Hand
betätigt werden, der gleichzeitig als Schaltstellungsanzeige
dient (beim Schalten von Hand und über den Bus). Ein Kanal ist
eingeschaltet, wenn die Schaltstellungsanzeige in der unteren
Endlage steht.
Verschiedene Funktionen sind pro Kanal parametrierbar wie z.B.
Leuchtstofflampen ein- und ausschalten, auf- und abdimmen
oder auf einen bestimmten Helligkeitswert setzen.
Mit Hilfe der ETS (Engineering Tool Software) können das Ap-
plikationsprogramm ausgewählt, die spezifischen Parameter
und Adressen vergeben und in den Schalt-/Dimmaktor übertra-
gen werden.
Mit einem Kanal des Schalt-/Dimmaktors N 526E02 können
mehrere dimmbare elektronische Vorschaltgeräte gesteuert
werden. Die Anzahl der dimmbaren EVGs pro Kanal ist sowohl
durch die Schalt- als auch durch die Steuerleistung des Schalt-/
Dimmaktors N 526E02 begrenzt. Wird die Ein- und Ausschalt-
funktion über den Schaltkontakt des Schalt-/Dimmaktors
N 526E02 nicht verwendet, so hängt die Anzahl der ansteuerba-
ren EVGs nur von der Belastung der 1...10 V DC- Steuerspan-
nung ab. Dann kann eine größere Anzahl dimmbarer EVGs an-
gesteuert werden (siehe Technische Daten).
Der N526E02 wird über den Bus gespeist, d.h. er benötigt kei-
ne zusätzliche Spannungsversorgung. Bei der Projektierung ist
zu berücksichtigen, dass er einer doppelten bis dreifachen Bus-
last entspricht und dem Bus max. 30 mA Strom entnimmt.
Weitere Informationen
http://www.siemens.de/gamma
Anschlussbeispiel
Siehe Bild 1
Die Kanäle B bis H sind entsprechend anzuschließen.
Technische Daten
Spannungsversorgung
•erfolgt über die Buslinie
Achtung: Gerät entspricht einer doppelten Buslast und ent-
nimmt dem Bus max. 30 mA Strom.
Ausgänge
•Anzahl: 8 (bistabile Relais, potentialfreie Kontakte)
•Bemessungsspannung: AC 230 V, 50 ... 60 Hz
•Bemessungsstrom: 16 A, cos phi = 1
•Schaltstrom bei AC 230 V:
0,1 ... 16 A, cos phi = 1
•Schaltstrom bei DC:
•DC 10 ... 30 V: max. 16 A, ohmsche Last
•DC 230 V: max. 0,18 A, ohmsche Last
•Schaltverhalten: parametrierbar
(siehe Applikationsprogramm)
Steuerspannung
•1 ... 10 V (vom dimmbaren EVG)
•bei Busspannungsausfall: 10 V
Steuerleistung
•Dimmbare EVGs: max. 60 Stk.
•Signalverstärker: max. 12 Stk.
VORSICHT
JJJJJJJJJJJJJJJJJJJ
Die Steuerstromkreise sind nicht gegen Zerstörung
durch fehlerhaftes Anschließen von 230V geschützt.
Anschlüsse
•Last- und Steuerstromkreis, mechanisch:
Abisolierlänge 8 ... 9 mm;
es sind folgende Leiter/-querschnitte zulässig:
0,5 ... 4 mm² eindrähtig
0,5 ... 2,5 mm² feindrähtig
•Laststromkreis, elektrisch:
Leiter feindrähtig, unbehandelt, ab 1 mm²:
Stromtragfähigkeit von max. 6 A
Leiter feindrähtig, mit Stiftkabelschuh,
gasdicht aufgecrimpt, ab 1,5 mm²:
Stromtragfähigkeit von max. 10 A
Alle anderen Leiter ab 1,5 mm²:
Stromtragfähigkeit von max. 16 A
VORSICHT
JJJJJJJJJJJJJJJJJJJ
Beim Durchschleifen des L-Leiters (Klemmen 1 und
2, 4 und 5, 7 und 8, 10 und 11, 13 und 14, 16 und
17, 19 und 20, 22 und 23) ist zu beachten, dass,
bedingt durch die zulässige Leiterbahnbelastung,
der maximale Klemmenstrom von 16 A nicht über-
schritten werden darf!
•Buslinie:
−Druckkontakte auf Datenschiene
−Busklemme schraubenlos
−0,6 ... 0,8 mm Ø, eindrähtig,
Abisolierlänge 5 mm
Seite 1 von 2
GB
Product and Applications Description
The switching/dimming actuator N 526E02 is a N-system DIN-
rail mounted device for controlling up to eight groups (channels)
of fluorescent lamps via the DC 1-10 V control terminal of dim-
mable electronic ballasts (ECG-Dynamic type).
In addition there is per channel a switching contact for direct
switching on/off of the connected fluorescent lamps. This con-
tact can be operated manually via a slide switch which also in-
dicates the actual switching state of the channel (when swit-
ching manually as well as when switching via the bus). A chan-
nel is switched on when the slide is in the lower position.
Different functions can be parameterised per channel such as
for switching on/off fluorescent lamps, increasing / decreasing
brightness or setting a particular level of brightness.
With the ETS (Engineering Tool Software) the application pro-
gram is selected, its parameters and addresses are assigned
appropriately and downloaded to the switching/dimming actua-
tor.
One channel of the N 526E02 switching/dimming actuator can
control several dimmable electronic ballasts. Their number is
limited as well by the switching capacity as by the control
power of the switching/dimming actuator N 526E02. If the
on/off function is not used via the relay contact of the switch-
ing/dimming actuator N 526E02, the number of controllable
ECGs is only dependent on the load of the DC 1-10 V control
voltage. This might allow to control a larger number of ECGs
(see Technical Specifications below).
The power supply of the N 526E02 is provided by the bus (i.e. it
requires no additional power supply). When projecting an instal-
lation it has to be considered that a N 526E02 represents a
double bus load and takes up to 30 mA from the bus.
Additional Information
http://www.siemens.com/gamma
Example of Operation
See figure 1
The channels B to H have to be connected correspondingly.
Technical Specifications
Power supply
•via bus line
Notice: the device represents a double bus load and takes up to
30 mA from the bus.
Outputs
•number: 8 outputs (latch relays, potential free contacts)
•rated voltage: AC 230 V, 50 ... 60 Hz
•rated current: 16 A, cos phi = 1
•switching current at AC 230 V:
0,1 ... 16 A, cos phi = 1
•DC switching current:
DC 10 ... 30 V: max. 16 A, resistive load
DC 230 V: max. 0,18 A, resistive load
•switching characteristic:
set in parameter list according to application program
Control voltage
•1 ... 10 V (provided by ECG Dynamic)
•in case of bus voltage failure: 10 V
Control power
•dimmable electronic ballast: max 60 units
•signal amplifier: max 12 units
CAUTION
JJJJJJJJJJJJJJJJJJ
There is no protection of the control circuits against
destruction by accidental connection to AC 230 V.
Connections
•load and control circuit, physical:
insulation strip length 8 ... 9 mm
permissible conductor types/cross sections:
0,5 ... 4 mm² single core
0,5 ... 2,5 mm² flexible conductor
•load circuit, electrical:
plain flexible conductor, min. 1 mm²:
current carrying capacity max. 6 A
flexible conductor with terminal pin,
crimped on gas tight, min. 1,5 mm²:
current carrying capacity max. 10 A
all other conductors, min. 1,5 mm²:
current carrying capacity max. 16 A
CAUTION
JJJJJJJJJJJJJJJJJJ
When looping through the L-conductor (connection
blocks 1 and 2, 4 and 5, 7 and 8, 10 and 11, 13 and
14, 16 and 17, 19 and 20, 22 and 23), take care that
the maximum connection current of 16 A (as gov-
erned by the maximum permissible printed conductor
load) is not exceeded!
•bus line:
−pressure contacts on data rail
−screwless bus connection block
−0,6 ... 0,8 mm Ø, single core,
insulation strip length 5 mm
page 1 of 2
2515434132 DS03
N
PE
L
+
-
26
25
Leuchtstofflampe
3
+
-
Kanal A
N
PE
L
+
-
26
25
Leuchtstofflampe
+
-
Kanal A
N
PE
L
+
-
26
25
Leuchtstofflampe
1
+
-
Kanal A
Channel A
Schalt-/Dimmaktor N 526E
Switching/Dimming Actuator N 526E
N
PE
L
Laststromkreis AC 230V
Load circuit AC 230V
L1 PE N
EVG Dynamic
ECG Dynamic
+
-
26
25
Leuchtstofflampe
fluorescent lamp
+
-
Busankoppler
buscouplingunit
Dimmen
Dimming
DC1...10V
Schalten
Switching
AC230V
Steuerung
Control
DC1...10V
Versorgung
Supply
AC230V
2
L
L
instabusEIB
0
A4 A3 A2 A1
A5
A6
Bild 2 / Figure 2
D4D1 D1D3 D2 D2
Bild 3 / Figure 3
D
Mechanische Daten
•Abmessungen: Reiheneinbaugerät im N-Maß,
Breite 8 TE (1 TE = 18 mm)
•Gewicht: ca. 470 g
Elektrische Sicherheit
•Schutzart (nach EN 60529): IP 20
Umweltbedingungen
•Umgebungstemperatur im Betrieb: - 5 ... + 45 °C
•Lagertemperatur: - 20 ... + 70 °C
•rel. Feuchte (nicht kondensierend): 5 % bis 93 %
Lage und Funktion der Anzeige- und Bedienelemente
Siehe Bild 2
A1 LED zur Anzeige Normalmodus (LED aus) oder Adres-
siermodus (LED ein); sie erlischt automatisch nach
Übernahme der physikalischen Adresse.
A2 Lerntaste zum Umschalten zwischen Normalmodus und
Adressiermodus zur Übernahme der physikalischen Ad-
resse.
A3 Busklemme, schraubenlos
A4 Schraubklemmen zum Anschluss der Steuerstromkrei-
se.
A5 Schiebeschalter zur Handbetätigung und zur Schaltstel-
lungsanzeige: Schaltstellung oben = AUS, unten = EIN
A6 Schraubklemmen zum Anschluss der Laststromkreise
Wichtiger Hinweis:
Die Handbetätigung der Schiebeschalter ist lediglich als Notbe-
triebsart vorgesehen. Es wird kein Telegramm auf den Bus ge-
sendet, und die geänderte Schaltstellung wird vom Bus-
Controller nicht registriert.
Bei Busspannungsausfall /-wiederkehr wird ein vorher manuell
geschaltetes Relais in den parametrierten Schaltzustand ge-
steuert.
Montage und Verdrahtung
Das Gerät kann, für feste Installation in Innenräumen, für trock-
ene Räume, zum Einbau in Starkstromverteiler oder Kleinge-
häuse auf Hutschienen TH35-7,5 nach EN 60715 verwendet
werden.
VGEFAHR
•Das Gerät darf nur von einer zugelassenen Elektrofachkraft
installiert und in Betrieb genommen werden.
•Bei Anschluss des Gerätes ist darauf zu achten, dass das
Gerät freigeschaltet werden kann, vor allem bei Anschluss
mehrerer Strompfade.
•Freie Tragschienenbereiche mit eingelegter Datenschiene
sind mit der Abdeckung 5WG1 192-8AA01 abzudecken.
•Das Gerät darf nicht geöffnet werden.
•Bei Planung und Errichtung von elektrischen Anlagen sind
die einschlägigen Richtlinien, Vorschriften und Bestimmun-
gen des jeweiligen Landes zu beachten.
Busanschluss
Bei Kontaktierung über Busklemme (Datenschiene nicht einge-
legt) ist das Kontaktsystem zur Datenschiene durch Abnehmen
der Fixierung z.B. mittels Schraubendreher und anschließen-
dem Aufschnappen der beiliegenden Isolierkappe abzudecken
(Bild 2), um ausreichende Isolation zur Tragschiene zu gewähr-
leisten.
Bei Montage des Schalt-/Dimmaktors N 526E02 auf einer Hut-
schiene mit eingelegter Datenschiene kann (auch für weitere
Geräte auf der Hutschiene) der sonst übliche Verbinder entfal-
len. Die Buslinie wird im Gerät von der Busklemme zur Daten-
schiene weitergeleitet.
Abnehmen der Fixierung (Bild 3)
Die Fixierung (D3) umschließt das Kontaktsystem (D2) auf der
Hinterseite des Schalt-/Dimmaktors N 526E02 (D1).
Den Schraubendreher zwischen dem Reiheneinbaugerät (D1)
und der Fixierung (D3) einführen und die Fixierung
herausziehen.
Aufschnappen der Isolierkappe (Bild 3)
Die Isolierkappe (D4) auf das Kontaktsystem stecken und durch
Drücken aufschnappen.
Allgemeine Hinweise
•Die Bedienungsanleitung ist dem Kunden auszuhändigen.
•Ein defektes Gerät ist an die zuständige Geschäftsstelle der
Siemens AG zu senden.
•Bei zusätzlichen Fragen zum Produkt wenden Sie sich bitte
an unseren Technical Support:
℡+49 (0) 180 50 50-222
"+49 (0) 180 50 50-223
!www.siemens.de/automation/support-request
Seite 2 von 2
GB
Physical specifications
•N-system DIN-rail mounted device, width: 8 SUs
(1 SU = 18 mm)
•weight: approx. 470 g
Electrical safety
•protection (according to EN 60529): IP 20
Environmental specifications
•ambient temperature operating: - 5 ... + 45 °C
•storage temperature: - 25 ... + 70 °C
•relative humidity (non-condensing): 5 % to 93 %
Location and Function of the Display and Operating Elements
See figure 2
A1 LED for indicating normal operating mode (LED off) or
addressing mode (LED on); upon receiving the physical
address the device returns to normal operating mode.
A2 Learning button for switching between normal operating
mode and addressing mode
A3 bus connection block, screwless
A4 screw terminals for connecting the control circuits
A5 Slide switches for manual operation and for displaying
the switching position per channel
Slide in upper position: relay contact open (OFF)
Slide in lower position: relay contact closed (ON)
A6 screw terminals for connecting the load circuits
Important note:
Manual operation is for emergency operation only and is not af-
fecting the application program. No telegram is sent on the bus,
and the new switching status is unknown to the software.
At bus voltage failure/recovery a previously manually operated
relay will also be set automatically to the configured position.
Mounting and wiring
The device may be used for permanent interior installations in
dry locations within distribution boards or small casings with
DIN rail TH35-7,5 according to EN 60715.
VDANGER
•The device must be mounted and commissioned by an
authorised electrician.
•A safety disconnection of the device must be possible.
•Free DIN rail areas with stuck-in data rail must be covered
with covers (order no. 5WG1 192-8AA01).
•The device must not be opened.
•For planning and construction of electric installations, the
relevant guidelines, regulations and standards of the respec-
tive country are to be considered.
Bus connection
If the connection is established via the bus connection block
(data-rail not installed) the contacting system towards the
data-rail has to be covered by removing the locating clamp e.g.
with a screw-driver and afterwards snapping on the insulation
cap to ensure a sufficient insulation towards the DIN-rail (see
figure 2).
When mounting the switching/dimming actuator N 526E02 onto
a DIN rail with stuck-in data-rail (even in combination with other
DIN rail devices) the usually employed bus line connector is not
necessary. The bus voltage is forwarded within the device from
the bus connection block to the data rail pressure contacts of
the N 526E02.
Removing the locating clamp (figure 3)
The locating clamp (D3) encloses the contacting system (D2) on
the back side of the N 526E02 (D1)
Insert the screw-driver between the N 526E02 (D1) and the lo-
cating clamp (D3) and pull out the locating clamp.
Snapping on the insulation cap (figure 3)
Stick the insulation cap (D4) onto the contacting system (D2)
and snap it on by pressing.
General Notes
•The operating instructions must be handed over to the client.
•Any faulty devices should be returned to the local Siemens
office.
•If you have further questions concerning the product please
contact our technical support:
℡+49 (0) 180 50 50-222
"+49 (0) 180 50 50-223
!www.siemens.com/automation/support-request
page 2 of 2
2515434132 DS03