5
SMART 7KT0307 Manual
Technical
specification
7KT0307 (Single Line LED Class 1)
PowerMonitoringDevicePanelinstrumentforstdelectricalvalues
Protocol:ModbusRTU,SinglelineLEDDisplayVaux:95Vto240VAC
x/1or5A,Class1
Measurements
measuring procedure
•forvoltagemeasurement True RMS
•forcurrentmeasurement True RMS
typeofmeasuredvaluedetection complete
voltagecurve Sinusoidal or distorted
measurablelinefrequency
•initialvalue 45Hz
•full-scalevalue 65Hz
operatingmodeformeasuredvaluedetectionautomaticline
frequencydetection
Yes
Supply voltage
design of the power supply SMPSpowersupply
typeofvoltageofthesupplyvoltage AC
Degree of protection class
protectionclassIPonthefront IP54
protectionclassIPoftheterminal IP20
Suitability
suitability for operation Installation in stationary panels in closed rooms
Product Functions
product function
•voltagemeasurement Yes
•currentmeasurement Yes
•activepowermeasurement Yes
•reactivepowermeasurement Yes
•apparentpowermeasurement Yes
•powerfactormeasurement Yes
•frequencymeasurement Yes
•apparentenergy/activeenergy/reactiveenergy Yes
Display and operation
design of the display LED
height of the display 22 mm
width of the display 69mm
color of the background of the display Black
national language on the display screen is supported EN
number of keys 2
Fault limits
reference condition for metering accuracy InaccordancewithIEC61557-12,IEC62053-21,IEC62053-23
formulaforrelativetotalmeasurementinaccuracy
•formeasuredvariablevoltage Class0.5asperIEC61557-12
•formeasuredvariablecurrent Class0.5asperIEC61557-12
•formeasuredvariableapparentpower Class1asperIEC61557-12
•formeasuredvariableactivepower Class1asperIEC61557-12
•formeasuredvariablereactivepower Class2asperIEC61557-12
•formeasuredvariablepowerfactor Class1asperIEC61557-12
•formeasuredvariableactiveenergy Class1asperIEC62053-21andIEC61557-12
•formeasuredvariablereactiveenergy Class2asperIEC61557-12andIEC62053-23