Insert CU Remove CU
Fitting CU to PM
Tightening torques:
SINAMICS G120
Power Module PM240-2, FSA, FSB, FSC
Mains, Motor and Brake terminals
The Power Modules are fitted with detachable terminals. It can
be removed from the Power Module by pressing the release
catch. The connectors are not interchangeable.
FSA: 0.5 Nm ( 4.5 lbf.in)
FSB: 0.6 Nm ( 5.5 lbf.in)
FSC: 1.3 Nm (12 lbf.in)
① Mains connector
② Motor connector
③ DC Link connector
④ Release catch
Cable cross sections
FSA: 1.5 … 2.5 mm216 … 14 AWG
FSB: 1.5 … 6 mm216 … 10 AWG
FSC: 6 … 16 mm210 … 6 AWG
150 % for 3 s
110 % for 57 s
200 % for 3 s
150%for 57 s
100 % for 240 s 100 % for 240 s
Permissible overload for operation
Screened cables, filtered units (class A) Second Environment, C2
EMI Standard not fulfilled
EMI Standard not fulfilled
Screened cables, unfiltered units
Unscreend cables, filtered or unfiltered units
according to “Low Overload“ (LO)
Overloads
Permissible overload for operation
according to “High Overload“ (HO)
HO base load: 100 % HO power
100 % HO current
LO base load: 100 % LO power
100 % LO current
%
300240
1801200
100
200
60t[s]
%
300240
1801200
100
150
60t[s]
For United States / Canadian installations (UL/cUL): In order that the system is UL/cUL-compliant, use
UL/cUL-certified J-type fuses. Use 75° C copper wire only.
Additional requirements for Canadian compliance:
400 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 480 V
(phase to ground), 480 V (phase to phase), suitable for overvoltage category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
200 V supply:
Transient surge suppression must be installed on the line side of this equipment and shall be rated 240 V
(phase to ground), 240 V (phase to phase), suitable for Overvoltage Category III and shall provide protection
for a VPR maximum of 2 kV, type 1 or type 2 SPD application.
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the power cables.
Siemens AG,
Digital Industries
Motion Control
Postfach 3180
91050 ERLANGEN
Germany
Edition: 04/2021
3 AC 380V… 480V± 10%up to 2000m installation
altitude. 1 AC / 3 AC 200 V... 240 V± 10%up to 2000 m installation altitude.
3 AC 0V… input voltage * 0.95
<
Feature Specification
PM240-2, Push-through units, 3 AC 380 V ... 480 V
PM240-2, Built-in units, 3 AC 380 V ... 480 V
PM240-2, Built-in units, 1 AC/3 AC 200 V ... 240 V
PM240-2, Push-through units, 3 AC 200 V ... 240 V
PM240-2, Push-through units, 1 AC/3 AC 200 V ... 240 V
PM240-2, Built-in units, 3 AC 200 V ... 240 V
Low values
Power
Cable lengths, using EMI level (Emission)
High values
Power
Rated
(LO)
input
current
Output
current
Output
current
Frame
Size
Order No. *)
Siemens
3NA3804
3NA3801
3NA3803
3NA3803
3NA3803
3NA3805
3NE1814-0
3NE1814-0
3NE1815-0
3NE1815-0
3NE1803-0
3NE1803-0
3NE1803-0
3NE1802-0
3NE1802-0
3NE1803-0
3NE1817-0
3NE1817-0
3NE1817-0
3NE1817-0
3NE1817-0
3NE1818-0
3NE1818-0
3NE1817-0
3NA3805
Storage temperature
Shock
< LO base load input current
Short Circuit Current Rating
(SCCR)
3NA3805
3NA3805
3NA3804
6SL3210-1PE11-8_L1
6SL3210-1PE12-3_L1
6SL3210-1PE13-2_L1
6SL3210-1PE13-0_L0
6SL3210-1PE13-8_L0
6SL3210-1PE15-5_L0
6SL3210-1PE17-4_L0
6SL3210-1PE21-0_L0
6SL3210-1PE21-4_L0
6SL3210-1PE21-8_L0
6SL3210-1PE14-3_L1
6SL3210-1PE16-1_L1
6SL3210-1PE21-1_L0
6SL3210-1PE21-4_L0
6SL3210-1PE21-8_L0
6SL3211-1PE21-8_L0
6SL3210-1PE22-7_L0
6SL3210-1PC22-2_L0
6SL3211-1PC22-2_L0
6SL3210-1PC22-8_L0
6SL3211-1PC22-8_L0
6SL3211-1PB13-8_L0
6SL3211-1PB21-0_L0
6SL3211-1PB21-8_L0
6SL3210-1PE23-3_L0
6SL3211-1PE23-3_L0
6SL3210-1PE18-0_L1
6SL3211-1PE18-0_L1
UL, J-type
Line fuses
Compact Operating Instructions
Data regarding the power loss in accordance with Ecodesign Regulation
(EU) 2019/1781 and IEC 61800-9-2
You can find data regading power loss of our products on the Internet:
*) _: A = filtered unit, U = unfiltered unit
Screening methods
Line
cable
Motor cable
Control cable
Wire
straps
Braking resistor cable
Shielding brackets
https://support.industry.siemens.com/cs/ww/en/view/94059311
Bulit-in units (open type equipment): IP20
Push-through units: IP54/UL Type 12 when mounted on a flat surface of an enclosure
Interference emission: The devices are suitable for second environment category C2 in accordance with IEC 61800-3 if the following
conditions are fulfilled: The motor cable is a shielded cable with low capacitance and is not longer than 50 m. The pulse frequency does
not exceed 4 kHz, the current does not exceed the LO input value. For details, refer to the Hardware Installation Manual.
Interference immunity: The devices are suitable for second environment category C3
4 kHz. Can be increased in 2 kHz steps up to 16 kHz. Increasing the pulse frequencies leads to an output current reduction.
DC braking, Compound braking, Dynamic braking with integrated chopper plus external braking resistor
This equipment is capable of providing internal motor overload protection according to UL61800-5-1. The protection level is 115%, 230%
and 400% full load current of the equipment. This is adjusted via parameter P640 and assumes the equipment has had basic motor
commissioning for the motor used as described in the documentation.
Motor overload protection
LO operating temperature 1)
HO operating temperature 1)
Environmental rating
Electromagnetic compatibility
Braking methods
Suitable for use on a circuit capable of delivering not more than 100 kA rms symetrical amperes; 240/480 V AC maximum when protected
by Class J fuses.
Further suitable protective devices including the associated SCCR can be found in:
Power factor
Pollution For open type equipment according to pollution degree level 2. Protection against conductive pollutions required e.g. using an IP54
cabinet.
For enclosed type/push-through equipment according to pollution degree level 3.
200 V units: Uk 2 %, for lower values, a line reactor must be used.
400 V units: Uk 1 %, for lower values, a line reactor must be used.
Long-term storage in the transport packaging according to Class 1M2 of IEC 60721-3-1: Transport in the transport packaging according
to Class 2M3 of IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
Long-term storage in the transport packaging according to Class 1M2 of IEC 60721-3-1: Transport in the transport packaging according
to Class 2M3 of IEC 60721-3-2. See Hardware Installation Manual for detailed specifications.
Suitable for environmental class 3C2 according to IEC 60721-3-3 against damaging chemical substances
Up to 1000 m (3300 ft) without derating/ Up to 4000 m (13000 ft) with derating
95 % RH - non-condensing
0 °C ... 40 °C (32 °F ... 104 °F) without current derating / up to 60 °C (140 °F) with current derating
0 °C ... 50 °C (32 °F ... 122 °F) without current derating / up to 60 °C (140 °F) with current derating
- 40 °C ... + 70 °C (- 40 °F ... + 158 °F)
0.7 without line reactor; 0.85 with line reactor
0 Hz ... 550 Hz, depending on the control mode
https://support.industry.siemens.com/cs/ww/en/view/109782705
Vibration
Line impedance
Environmental conditions
Installation altitude above sea level
Line voltage
Output voltage
Input frequency
Output frequency
Irrush current
Pulse frequency (factory setting)
Humidity
1) according to UL, operation with temperatures > 50 °C (122 °F) is not permitted at all