manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Relay
  8. •
  9. Siemens FS-RU2 Wiring diagram

Siemens FS-RU2 Wiring diagram

This manual suits for next models

1

Other Siemens Relay manuals

Siemens SIRIUS 3TK2840 User manual

Siemens

Siemens SIRIUS 3TK2840 User manual

Siemens 3UA60 User manual

Siemens

Siemens 3UA60 User manual

Siemens 7SR210 Argus User manual

Siemens

Siemens 7SR210 Argus User manual

Siemens SIPROTEC 7SJ61 User manual

Siemens

Siemens SIPROTEC 7SJ61 User manual

Siemens 3TK2810-0 User manual

Siemens

Siemens 3TK2810-0 User manual

Siemens 3VT9115-5GY31 User manual

Siemens

Siemens 3VT9115-5GY31 User manual

Siemens siprotec 7SD5 User manual

Siemens

Siemens siprotec 7SD5 User manual

Siemens 3RV1976-3AP3 User manual

Siemens

Siemens 3RV1976-3AP3 User manual

Siemens 48-HASA3M User manual

Siemens

Siemens 48-HASA3M User manual

Siemens 3UA66 User manual

Siemens

Siemens 3UA66 User manual

Siemens SIRIUS 3RQ1 User manual

Siemens

Siemens SIRIUS 3RQ1 User manual

Siemens SIPROTEC 4 7SJ61 User manual

Siemens

Siemens SIPROTEC 4 7SJ61 User manual

Siemens Argus 7SR11 User manual

Siemens

Siemens Argus 7SR11 User manual

Siemens Argus 8 7SG11 User manual

Siemens

Siemens Argus 8 7SG11 User manual

Siemens Ohmega 406 7SG16 User manual

Siemens

Siemens Ohmega 406 7SG16 User manual

Siemens 7UT51 User manual

Siemens

Siemens 7UT51 User manual

Siemens 3TK2810-0 Technical Document

Siemens

Siemens 3TK2810-0 Technical Document

Siemens SIMPRO-100 User manual

Siemens

Siemens SIMPRO-100 User manual

Siemens 3RP25 User manual

Siemens

Siemens 3RP25 User manual

Siemens 3US50 User manual

Siemens

Siemens 3US50 User manual

Siemens SIRIUS 3RP15 User manual

Siemens

Siemens SIRIUS 3RP15 User manual

Siemens ISGS User manual

Siemens

Siemens ISGS User manual

Siemens 3RT2840.-2 User manual

Siemens

Siemens 3RT2840.-2 User manual

Siemens SIRIUS 3TK2826- 1/2/4 Series User manual

Siemens

Siemens SIRIUS 3TK2826- 1/2/4 Series User manual

Popular Relay manuals by other brands

Woodward BU1-DC2 manual

Woodward

Woodward BU1-DC2 manual

ABB SSR32 product manual

ABB

ABB SSR32 product manual

Shelly Pro Series user manual

Shelly

Shelly Pro Series user manual

GE MVAX 11 Technical manual

GE

GE MVAX 11 Technical manual

ABB RELION REF615R manual

ABB

ABB RELION REF615R manual

Kemo Electronic B197 quick guide

Kemo Electronic

Kemo Electronic B197 quick guide

Seg MRM3 manual

Seg

Seg MRM3 manual

Basler BE1-700C manual

Basler

Basler BE1-700C manual

CD Automation REVEX 2PH 280A user manual

CD Automation

CD Automation REVEX 2PH 280A user manual

ABB SPAJ 142 C User manual and technical description

ABB

ABB SPAJ 142 C User manual and technical description

Ruelco 1S04 Operation manual

Ruelco

Ruelco 1S04 Operation manual

Basler V3E Z1P B2C1F instruction manual

Basler

Basler V3E Z1P B2C1F instruction manual

GE DGP instruction manual

GE

GE DGP instruction manual

Kyongbo Electronics GDR-D01 user manual

Kyongbo Electronics

Kyongbo Electronics GDR-D01 user manual

Eaton easyE4 series Application note

Eaton

Eaton easyE4 series Application note

Leuze MSI-SR5B Original operating instructions

Leuze

Leuze MSI-SR5B Original operating instructions

Littelfuse SE-330AU manual

Littelfuse

Littelfuse SE-330AU manual

EVA Logik ZW12 user manual

EVA Logik

EVA Logik ZW12 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Siemens Industry, Inc. Siemens Building Technologies, Ltd.
Building Technologies Division Fire Safety & Security Products
Florham Park, NJ 2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
P/N 315-049308-6 (v12-14-09)
INSTALLATION INSTRUCTIONS
Model FS-RU2 Serial Relay Unit
Model FS-RE8 Serial Relay Extender
The FS-RU2 Serial Relay Unit is an optional accessory for the FS-250 and FS-250C Fire Alarm System
Control Panels. The FS-RU2 includes a processor board and a relay board. The processor board receives
commands from the control unit for activating the relays and transmits supervision and control functions to
the control unit. The processor board can control up to 3 relay boards. Each relay board provides 8 relays
with Form C contacts. The control unit can address up to 8 Serial Relay Units and/or Serial Annunciator
Units. Auxiliary power supplies will be required to power units beyond the control unit capability.
FS-RU2 PARTS SUPPLIED
1 Processor Board Assembly
1 Relay Board Assembly
1 34 pin Cable Assembly, 3 1/2”
1 PCB Track, 14 1/2”
1 10 pin Cable Assembly, 6”
1 Screwdriver
3 Keps Nut, #6-32
1 Instruction Sheet
FS-RE8 PARTS SUPPLIED
1 Relay Board Assembly
1 34 pin Cable Assembly, 15”
1 34 pin Cable Assembly, 3 1/2”
1 PCB Track, 14 1/2”
3 Keps Nut, #6-32
1 Instruction Sheet
P6 SW-1 S1
FS-RU2 DIMENSIONS
S1
FS-RE8 DIMENSIONS
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect BATTERY and AC prior to working on
equipment.
Step 3.) Mount enclosure that is UL Listed for Fire
Protective Signaling Use as required in a dry
protected environment.
Step 4.) Attach conduit and run wires as required in a dry
protected environment.
Step 5.) Set processor board dip switch (SW1) for proper
remote address (See FS-RU Address Setting).
Step 6.) Set each relay board dip switch (S1) for proper
relay set number on the relay board (FS-RE8).
NOTE: Relays are numbered from left to right:
Relay Set TB1 TB2 TB3 TB4
(1-8) 1 2 3 4 5 6 7 8
(9-16) 9 10 11 12 13 14 15 16
(17-24) 17 18 19 20 21 22 23 24
Step 7.) Set jumper P6 for desired buzzer operation.
P6 – BUZZER ACTIVATION
•REMOTE
•
•LOCAL (Processor Board Buzzer)
NOTE: When “Local” is selected, the buzzer follows the sounder
on the panel. When “Remote” is selected, the local
buzzer does not activate, but the “Remote Buzzer Output”
pin of P2 follows the sounder on the panel.
Step 8.) Mount PCB Track(s) using #6-32 keps nuts and
snap in PCB assemblies.
Step 9. Plug in the cable assembly(s) to the PCB
assemblies as required.
Step 10. Connect ground wire(s) to chassis ground using
#6-32 keps nut(s).
Step 11.) Connect IN wires from fire alarm system control
unit or previous remote as required.
Step 12.) Connect OUT wires to next remote or 120 ohm
E.O.L. Resistor Assembly (P/N 140-050008-1), if
last remote.
P/N 315-049308-6 2
Step 13.) Connect relay contacts, as required.
Step 14.) Apply power to system.
Step 15.) Program control unit for required relay operation.
Step 16.) Check for proper operation of functions.
FS-RU2 / FS-RE8 WIRING
Notes:
1.) Units to be installed in accordance with all local codes.
2.) T-Tapping is not allowed! Communication wiring must be daisy chained from unit to unit.
3.) Terminal block will accept 12 AWG to 18 AWG wiring.
4.) Use twisted pair cable with a characteristic impedance of approximately 120 ohms. 4000 feet maximum distance from
end to end.
5.) Power Limited wiring must be kept separate from non-power limited wiring, ¼ “ minimum.
6.) All wiring to P2 on the remote processor board must be in the same enclosure.
7.) The following table gives the currents necessary for power supply and battery calculations.
Model Standby Current Alarm Current Voltage
FS-RU2 0.032 A 0.192 A (All relays activated) 24VDC nominal, filtered
FS-RE8 0.000 A 0.170 A (All relays activated) 24VDC nominal, filtered
FS-RU2 ADDRESS SETTING
Address Switch 1 Switch 2 Switch 3 Switch 4
1 On On On Off
2 Off On On Off
3 On Off On Off
4 Off Off On Off
5 On On Off Off
6 Off On Off Off
7 On Off Off Off
8 Off Off Off Off
PROCESSOR BOARD HEADER CONNECTIONS
Pin P2 - Processor Board
1 24V Output (+)
2 Not Used
3 Lamp Test Switch
4 Alarm Silence Switch
5 Trouble Acknowledge/Silence Switch
6 System Reset Switch
7 Remote Buzzer Output (open collector)
8 Alarm Silence Output (open collector)
9 Trouble Output (open collector)
10 24V Output (-) or GND
SW-1
OFF ON
1
2
3
4
Programmable Relay Contacts
(Shown in normal standby condition)
1A@28VDC max., Resistive
For Power Limited Source, Unsupervised
Power Limited, Supervised
Cable for power (+ & -) and Twisted
pair Cable for data (X+ & X-) from
panel or previous remote.
Cable for power (+ & -) and twisted
pair Cable for data (X+ & X-) to next
remote or 120 ohm E.O.L. Resistor
A
ssembly (P/N 140-050008-1) on the
last remote.
TB3 allows for connection to an
external regulated and power limited
24VDC power supply, listed for fire
protective signaling use.
A
= Common (Armature)
C = Normally Closed
O = Normally Open
P/N 315-049308-6 3
The P2 connector on the processor board assembly of the FS-RU2 allows the unit to be connected to an annuniator
to display system status and ancillary control of the panel.
NOTE: If used for ancillary control of the panel, it must be located in a locked enclosure.
POWER OUTPUTS:
P2-1: 24VDC (+)
P2-10: GND
Rating:
24VDC nominal, filtered
0.200A max.
SWITCH INPUTS:
These inputs are momentarily connected to GND using a toggle switch to activate. These inputs are not supervised.
All switch input wiring must be in the same room as the FS-RU2.
Typical wiring connection:
P2-3: Lamp Test Switch – when activated, all local LEDs activate for 4 seconds, then LEDs revert back to
previous state.
P2-4: Alarm Silence Switch – when activated during an alarm condition, silences the NACs. Once the NACs are
silenced, pressing this switch again does not unsilence the NACs.
P2-5: Acknowledge Switch – if events are present when activated, acknowledges the event and silences the
local buzzer.
P2-6: System Reset Switch – when activated, initiates a panel system reset.
OPEN COLLECTOR OUTPUTS:
If LEDs are connected to these outputs, use the proper resistor value (typically 2.4K ohms) to limit the current flowing
through the LEDs.
Rating:
24VDC nominal, filtered
0.070A max. per circuit
Typical wiring connection:
P2-7: Remote Buzzer Output – when “Remote” is selected in P6, this output follows the buzzer activation on the
panel.
P2-8: Alarm Silence Output – this output activates to indicate that the NACs are silenced.
P2-9: Trouble Output – this output activates when a trouble event is detected by the system.
P/N 315-049308-6 4