Siemens 3TS11 Series User manual

s
Operating Instructions
Contactor for capacitor switching:
Type: 3TS11 .. to 3TS15..
IS/IEC:60947
A. Technical Data
i) Main circuit:
The capacitors are precharged during pick-up via early-make
contacts and integrated pre-charge resistors before the main
contacts close.
This combination may be used for switching of Individual
capacitor for power factor correction of single loads or for
switching capacitor banks in parallel in centralized group
power factor correction system.
• InsulationVoltageUi=690VAC,
Temperature:Storage-25to+55ºC
 Service(withoutderating)-25to+40ºC
Usethedeviceswiththedeclaredcapacitorbankratingsonly.
Contactor Type Load of contactor when switching
3ph-AC capacitor kVAr at 415/440V, 50Hz
3TS11..-0A..5-8K 7
3TS1200-0A..5-8K 12.5
3TS1300-0A..5-8K 16
3TS1400-0A..5-8K 20
3TS1500-0A..5-8K 25
• Switching frequency in Make/Break operations:
180Operatingcycles/hourforallratings
• Maximum back-up fuse rating:ForType-1Coordination
Type-3NA7asperIEC60269
:1.6…1.8Ie
ii) Aux Circuit:
Inbuilt: Auxiliary Contacts
1NOincaseof3TS11…
No built-in auxiliary contacts for 3TS12.. To 3TS15..
Additional Aux:
Facilitytoadd-on1NOor1NCauxiliarycontactblocktype
3TX40..isavailablefrom3TS11..To3TS15..
3TX 40.. Block tment
Aux Contact Rating:
3TX40
IeAC-15=3.6Aat415V
IeDC-13=0.48Aat220V
Note: Do not remove precharging resistors. If contactor is
switchedonloadwithoutresistor,itmaycausedamageto
the contactor.
iii) Control circuit:
• Controlvoltageismarkedonthecolouredidentication
tag on the coil.
Note:
• Thevoltageistobemaintainedwithinallowablelimits.
• Operationonundervoltageconditionstothecoilmay
causedamagetothecoil/contactor.
• Maximumback-upfuseratingforcontrolcircuit=16A
=6Aifrelaycontactisinthecontrolcircuit.
iv) Internal connection diagram
ConnectionDetailsfor3TS11…to3TS15..isshowningure1
Hazardous Voltage can cause
Electric Shock and burns.
Disconnect Power before proceeding with
any work on this equipment
Avoidoperationduringundervoltage
conditions. Switch only onto discharged
capacitors.Manualoperationnot
permitted for function testing
Warning:
!
3TS11..-0A..5-8K 3TS13..-0A .. 5-8K
 InbuiltNOincaseof7kVAronly.
Fig. 1
Siemens Ltd.
SGR-02IO-813
OrderNo.A5E03830809000A
Productdevelopmentisacontinuousprocess.Consequently
thedataindicatedinthisLeaetissubjecttochangewithout
priornotice.Forlatestissuecontactoursalesofces.
SACHINENTERPRISE
Disposal
Siemensproductareenvironmentfriendly,whichpredominantly
consist of recyclable materials.
For disposals we recommend disassembling and separation into
following materials:
METALS:SegregateintoFerrous&NonFerroustypesforrecycling
through authorised dealer.
PLASTICS:Segregateaspermaterialtypeforrecyclingthrough
authorised dealer. Because of the long lifetime of Siemens
products the disposal guidelines may be replaced by other national
regulations when taking the product out of service.
The local customer care service is available at any time to answer
disposal-related questions
CustomerCareTollfreeno.1800220987 Email:[email protected]
B. Installation
1. Permitted mounting positions are indicated in Fig.2
2. Theunitissuitableforscrewmountingonatvertical
surfacewithtwoM4screws.Alwaysuseplainandspring
washers.
3. Alternativelysnapfor3TS11..to3TS15..ontoa35mm
TophatRailTH35asperDIN:EN60715.
Note:Installtheunitinhousingifitisexposedtodust,dirt,
contamination or aggressive atmosphere.
C. Maintenance
• Removedustbysuction.
• Replacementofcoilavailableasspare.
• Sparecontactkitsavailablefrom3TS12to3TS15.
• ContactSiemensSalesofcefordetails.
• Handletheresistorwirescarefully.
D. Note:
NormallythepowerfactorcontrollerinAPFCpanels,hasthe
provisionforadjustmentundervoltagecutoutwithrespect
to voltage and time. Please ensure that the controllers are
present as per values given in the table on right side.
Coil Voltage Controller settings
Under Voltage setting Actuating time
110V ≥94V <0.1sec
230V ≥196V <0.1sec
415V ≥353V <0.1sec
220-230V ≥187V <0.1sec
400-415V ≥340V <0.1sec
Incase,Powerfactorcontrollerdoesnothavetheprovision
ofabovesettings,itisrecommendedtoprovideaseparate
undervoltagemonitorhavingsettingsaspertable,toensure
satisfactory performance of the contactors. For further details
onsuchanundervoltagemonitor,pleasecontactnearest
Siemensofce.
Permissible Conductor Size: Main Terminals
Termination Data - Contactor Cable 3TS11..-0A..5-8K 3TS1200-0A..5-8K 3TS1300-0A..5-8K 3TS1400-0A..5-8K 3TS1500-0A..5-8K
Solid
mm21 x (1 to 2.5) 1x(2.5to6) 1to16 1to16 1to16
Flexible without end sleeve
mm2– – 1.5to16 1.5to16 1.5to16
Flexible with end sleeve
mm21x(0.75to2.5) 1 x (1.5 to 4) 1.5to16 1.5to16 1.5to16
Screw Size M3.5 M4
Tightening Torque N-m 0.8to1.4 1.0to1.5 2.5 to 3
Fig. 2 Mounting Positions for 3TS11… to 3T15…
E. Overall Dimensions
Dimensional drawing: 7/12.5,16, 20, 25 kVAr (3TS11/12/13/14/15..-0A .. 5-8K)
Type A B C D F G H J K Ø E M Term
Screw
3TS11 125 74 60 10 115 78 45 60 35 4.8 48 M3.5
3TS12 136 85 70 14.5 115 85 45 75 35 4.8 51 M4
3TS13..15 148 85 63 18 120 103 55 75 45 5 62.5 M4

This manual suits for next models

1

Other Siemens Switch manuals

Siemens SIMATIC RUGGEDCOM RSG2100P User manual

Siemens

Siemens SIMATIC RUGGEDCOM RSG2100P User manual

Siemens CNFS Series User manual

Siemens

Siemens CNFS Series User manual

Siemens SIMATIC NET RUGGEDCOM M969 User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM M969 User manual

Siemens SIMATIC NET CP 343-1 User manual

Siemens

Siemens SIMATIC NET CP 343-1 User manual

Siemens 3KA User manual

Siemens

Siemens 3KA User manual

Siemens SIMATIC NET RUGGEDCOM RST916P Technical Document

Siemens

Siemens SIMATIC NET RUGGEDCOM RST916P Technical Document

Siemens 3KD36-0P Series User manual

Siemens

Siemens 3KD36-0P Series User manual

Siemens RUGGEDCOM i803 User manual

Siemens

Siemens RUGGEDCOM i803 User manual

Siemens S3VA41TDHD User manual

Siemens

Siemens S3VA41TDHD User manual

Siemens SCALANCE XB-200 Instruction sheet

Siemens

Siemens SCALANCE XB-200 Instruction sheet

Siemens GAMMA instabus AP 422/3 Service manual

Siemens

Siemens GAMMA instabus AP 422/3 Service manual

Siemens NCM S7 User manual

Siemens

Siemens NCM S7 User manual

Siemens 3VM11 1AA Series User manual

Siemens

Siemens 3VM11 1AA Series User manual

Siemens SCALANCE X-400 User manual

Siemens

Siemens SCALANCE X-400 User manual

Siemens ASC77.1E User manual

Siemens

Siemens ASC77.1E User manual

Siemens SITRANS LVL200E User manual

Siemens

Siemens SITRANS LVL200E User manual

Siemens 8DJH User manual

Siemens

Siemens 8DJH User manual

Siemens 5-FSV-350 Owner's manual

Siemens

Siemens 5-FSV-350 Owner's manual

Siemens 5WG1 233-2AB01 User manual

Siemens

Siemens 5WG1 233-2AB01 User manual

Siemens SITRANS LVL200E User manual

Siemens

Siemens SITRANS LVL200E User manual

Siemens RUGGEDCOM RS910W User manual

Siemens

Siemens RUGGEDCOM RS910W User manual

Siemens SIRIUS 3SE53 2-0SH 1 Series User manual

Siemens

Siemens SIRIUS 3SE53 2-0SH 1 Series User manual

Siemens SIMATIC NET SCALANCE XCM-300 User manual

Siemens

Siemens SIMATIC NET SCALANCE XCM-300 User manual

Siemens SIMATIC NET RUGGEDCOM RSG2288 User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RSG2288 User manual

Popular Switch manuals by other brands

Philips SWS4686W Specifications

Philips

Philips SWS4686W Specifications

Eaton XN300 instruction manual

Eaton

Eaton XN300 instruction manual

Moxa Technologies EtherDevice EDS-4008 Series Quick installation guide

Moxa Technologies

Moxa Technologies EtherDevice EDS-4008 Series Quick installation guide

ZyXEL Communications ES-108 - user guide

ZyXEL Communications

ZyXEL Communications ES-108 - user guide

EnGenius EGS5110P user manual

EnGenius

EnGenius EGS5110P user manual

IPGARD SDPN-2D quick start guide

IPGARD

IPGARD SDPN-2D quick start guide

Edimax EK-08RE Technical specifications

Edimax

Edimax EK-08RE Technical specifications

TP-Link 24+2/24+2G user guide

TP-Link

TP-Link 24+2/24+2G user guide

MCDonald 6619-029 Replacement instructions

MCDonald

MCDonald 6619-029 Replacement instructions

EUCHNER CTM-CBI-BP operating instructions

EUCHNER

EUCHNER CTM-CBI-BP operating instructions

Eaton EGS Series Instruction booklet

Eaton

Eaton EGS Series Instruction booklet

ICP DAS USA NS-205A quick start guide

ICP DAS USA

ICP DAS USA NS-205A quick start guide

Freedom9 freeView IP 800 user manual

Freedom9

Freedom9 freeView IP 800 user manual

Intelix AS-1H1V Installation and operation guide

Intelix

Intelix AS-1H1V Installation and operation guide

Supermicro SSE-G3648B installation guide

Supermicro

Supermicro SSE-G3648B installation guide

Cisco Catalyst 3560 Getting started guide

Cisco

Cisco Catalyst 3560 Getting started guide

HP ProCurve 8108fl datasheet

HP

HP ProCurve 8108fl datasheet

Lenovo ThinkSystem NE0152T installation guide

Lenovo

Lenovo ThinkSystem NE0152T installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.