Siemens Ltd.
SGR-02IO-813
OrderNo.A5E03830809000A
Productdevelopmentisacontinuousprocess.Consequently
thedataindicatedinthisLeaetissubjecttochangewithout
priornotice.Forlatestissuecontactoursalesofces.
SACHINENTERPRISE
Disposal
Siemensproductareenvironmentfriendly,whichpredominantly
consist of recyclable materials.
For disposals we recommend disassembling and separation into
following materials:
METALS:SegregateintoFerrous&NonFerroustypesforrecycling
through authorised dealer.
PLASTICS:Segregateaspermaterialtypeforrecyclingthrough
authorised dealer. Because of the long lifetime of Siemens
products the disposal guidelines may be replaced by other national
regulations when taking the product out of service.
The local customer care service is available at any time to answer
disposal-related questions
B. Installation
1. Permitted mounting positions are indicated in Fig.2
2. Theunitissuitableforscrewmountingonatvertical
surfacewithtwoM4screws.Alwaysuseplainandspring
washers.
3. Alternativelysnapfor3TS11..to3TS15..ontoa35mm
TophatRailTH35asperDIN:EN60715.
Note:Installtheunitinhousingifitisexposedtodust,dirt,
contamination or aggressive atmosphere.
C. Maintenance
• Removedustbysuction.
• Replacementofcoilavailableasspare.
• Sparecontactkitsavailablefrom3TS12to3TS15.
• ContactSiemensSalesofcefordetails.
• Handletheresistorwirescarefully.
D. Note:
NormallythepowerfactorcontrollerinAPFCpanels,hasthe
provisionforadjustmentundervoltagecutoutwithrespect
to voltage and time. Please ensure that the controllers are
present as per values given in the table on right side.
Coil Voltage Controller settings
Under Voltage setting Actuating time
110V ≥94V <0.1sec
230V ≥196V <0.1sec
415V ≥353V <0.1sec
220-230V ≥187V <0.1sec
400-415V ≥340V <0.1sec
Incase,Powerfactorcontrollerdoesnothavetheprovision
ofabovesettings,itisrecommendedtoprovideaseparate
undervoltagemonitorhavingsettingsaspertable,toensure
satisfactory performance of the contactors. For further details
onsuchanundervoltagemonitor,pleasecontactnearest
Siemensofce.
Permissible Conductor Size: Main Terminals
Termination Data - Contactor Cable 3TS11..-0A..5-8K 3TS1200-0A..5-8K 3TS1300-0A..5-8K 3TS1400-0A..5-8K 3TS1500-0A..5-8K
Solid
mm21 x (1 to 2.5) 1x(2.5to6) 1to16 1to16 1to16
Flexible without end sleeve
mm2– – 1.5to16 1.5to16 1.5to16
Flexible with end sleeve
mm21x(0.75to2.5) 1 x (1.5 to 4) 1.5to16 1.5to16 1.5to16
Screw Size M3.5 M4
Tightening Torque N-m 0.8to1.4 1.0to1.5 2.5 to 3
Fig. 2 Mounting Positions for 3TS11… to 3T15…
E. Overall Dimensions
Dimensional drawing: 7/12.5,16, 20, 25 kVAr (3TS11/12/13/14/15..-0A .. 5-8K)
Type A B C D F G H J K Ø E M Term
Screw
3TS11 125 74 60 10 115 78 45 60 35 4.8 48 M3.5
3TS12 136 85 70 14.5 115 85 45 75 35 4.8 51 M4
3TS13..15 148 85 63 18 120 103 55 75 45 5 62.5 M4