manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Switch
  8. •
  9. Siemens N 523/02 User manual

Siemens N 523/02 User manual

instabus EIB
Technical product information
August 2010
Venetian blind switch N 523/02 5WG1 523-1AB02
4 x 230 V AC / 6 A
Siemens AG N 523/02, 4 pages Technical manual
Industry Sector, Building Technologies
Electrical Installation Technology © Siemens AG 2010 Update: http://www.siemens.com/gamma
P.O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.10.1.13/1
Product and functional description
The Venetian blind switch N 523/02 is a DIN rail mounted
device in N-system dimensions with a width of 4 module
units. Only one AC 230V drive (motor) with electro-
mechanical limit switches or with integrated electronics
for disconnection at the limit positions can be connected
to a channel of the 4-fold Venetian blind switch
N 523/02. The parallel operation of several drives on one
channel requires the intermediate switching of a special
relay. Apart from moving the sun/anti-glare protection
into one of the two limit positions, the Venetian blind
can also be stopped and the slats can be adjusted step-
wise.
The power supply of the Venetian blind switch elec-
tronics is carried out via an integrated power supply unit,
which is fed via the mains connection L1 for channels A
and B. The mains connection of channels C and D is car-
ried out via the connection L2. This enables two channels
to be connected to different external conductors. If this is
not required, one of the terminals L1 must be linked to
one of the terminals L2 via a wiring jumper.
For direct operation (also in the event of communi-
cations failure or if EIB communication has not yet been
put into operation), four pairs of push buttons are avail-
able on the top of the device. For direct operation, both
AC 230 V and bus voltage must be applied at the actua-
tor. Moreover, the actuator must be switched to direct
operation via the appropriate push button with an LED.
In direct operation mode, an output remains switched on
while the associated push button is pressed. As the direct
operation is completely isolated from the bus communi-
cation, any active safety alarm or protection mode (for
blocking the raising or lowering of the sun/anti-glare pro-
tection) is not taken into account.
Application program
The sunblind switch N 523/02 only works together with
the application program 25 A4 Sunblind switch 980103.
Due to its two 1 bit command objects which are always
available per channel, the program enables the move-
ment of a Venetian blind into the upper or lower limit
position, stopping the movement of the Venetian blind
as well as the stepwise adjustment of the slats. The ad-
justable period for gradually opening the slats or gradu-
ally raising the sunblind again once it has reached the
lower limit position only becomes into effect if the sun-
blind has been lowered from the upper limit position
without any interruptions.
When commissioning the sunblind switch the following
objects can be added to all the channels :
-one object “Move-up blockade On/Off“
(required e.g. for cleaning)
-one object “Move-down blockade On/Off”
(required e.g. for interior sun protection and when
the window is open)
-two 1 bit objects for saving/restoring two Venetian
blind/slat positions
-two 8 bit status objects (Venetian blind and slat posi-
tion as percentage values).
In connection with a weather station, in the event of a
wind or rain alarm it is ensured via an alarm object that
the sun/anti-glare protection is for example raised auto-
matically and that the lowering of it via the EIB is pre-
vented when there is an alarm.
It can further be selected whether the parameterisation
is adopted for all the channels or whether each channel
should be configured individually.
Connection example
Venetian blind switch N 523/02
instabusEIB
Bus coupling unit
venetian blind drives
venetian
blind
channel
D
venetian
blind
channel
C
venetian
blind
channel
B
venetian
blind
channel
A
K1
up
K2
down
K3
up
K4
down
K5
up
K6
down
K7
up
K8
down
L2
L1 N
power supply
instabus EIB
Technical product information
August 2010
Venetian blind switch N 523/02 5WG1 523-1AB02
4 x 230 V AC / 6 A
Technical manual N 523/02, 4 pages Siemens AG
Industry Sector, Building Technologies
Update: http://www.siemens.com/gamma © Siemens AG 2010 Electrical Installation Technology
Subject to change without further notice P.O. Box 10 09 53, D-93009 Regensburg
2.10.1.13/2
Notes for installation
The device may be used for permanent interior installa-
tions in dry locations within distribution boards or small
casings with DIN rail EN 60715-TH35-7,5.
VDANGER
•The device must be mounted and commissioned by an
authorised electrician.
•When connecting the device, it should be ensured that
the device can be isolated.
•The device must not be opened.
•For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
•In the case of motors with electronic limit switches, the
switching points must be adapted on site.
Technical data
Power supply
•Bus voltage: carried out via the bus line
•N 523 electronics: integrated power supply unit
230V AC, +10% / -15%, 50Hz
•Supply voltage for bus: 21V DC to 30V DC
Operating elements
•1 push button:
for toggling between normal mode / addressing mode
•1 push button:
for toggling between bus / direct operation
•4 x 2 push buttons:
for direct operation of the Venetian blind drives,
independent of the EIB
Display elements
•1 red LED: for displaying
normal mode / addressing mode (off / on)
•1 yellow LED: for displaying
bus / direct operation (off / on)
Inputs/outputs
•Mains connection:
- 2 x 2-pole (N, L1) (L1 is also the power supply for
outputs A and B)
- 2-pole L2 (power supply for channels C and D)
•4 load outputs for 4 Venetian blinds:
- each 2-pole (UP, DOWN)
-rated voltage: AC 230 V, 50Hz
-rated current per relay contact:
6 A (resistive load)
-Switching cycles: >20,000 at cos ϕ= 1
Connections
•Mains and load circuits
plug-in terminals for mains connections and outputs
Insulation strip length 9... 10 mm
The following conductor cross-sections are permitted:
- 0.5... 2.5 mm² single-core
- 0.5... 2.5 mm² finely stranded with connector sleeve
- 1.5 mm² finely stranded, untreated (max. ampacity
6A).
•Bus line: Pressure contacts on data rail and
bus terminal
VDANGER
When looping through the L and N conductors, it should
be noted that the maximum terminal current of 10 A,
which is limited by the permitted printed conductor load,
may not be exceeded.
Mechanical data
•Housing: plastic
•Dimensions: DIN rail mounted device in N-system di-
mensions, width: 4 modules (1 module = 18 mm)
•Weight: approx. 260 g
•Fire load: approx. 3600 KJ ± 10%
•Installation: snap-on fixing onto DIN rail
DIN EN 50022-35 x 7.5
Electrical safety
•Degree of pollution (in accordance with IEC 60664-1): 2
•Protection type (in accordance with EN 60529): IP 20
•Bus: safety extra-low voltage SELV DC 24 V
•Device complies with
EN 50090-2-2 and EN 60669-2-1
EMC requirements
complies with EN 61000-6-1, EN 61000-6-3 and
EN 50090-2-2
Environmental conditions
•Ambient operating temperature: - 5 ... + 45 °C
•Storage temperature: - 25 ... + 70 °C
Markings
KNX / EIB
CE mark
In accordance with the EMC guideline (residential and
functional buildings) and the low voltage guideline
instabus EIB
Technical product information
August 2010
Venetian blind switch N 523/02 5WG1 523-1AB02
4 x 230 V AC / 6 A
Siemens AG N 523/02, 4 pages Technical manual
Industry Sector, Building Technologies
Electrical Installation Technology © Siemens AG 2010 Update: http://www.siemens.com/gamma
P.O. Box 10 09 53, D-93009 Regensburg Subject to change without further notice
2.10.1.13/3
Location and function of the display and
operating elements
Figure 1: Location of the display and operating elements
A1 Commissioning button
A2 Commissioning LED
A3 Bus terminal
A4 Buttons for direct operation UP/DOWN of a sun-
blind
A5 Terminals for sunblind UP/DOWN (Channel C + D)
A6 Terminals for sunblind UP/DOWN (Channel A + B)
A7 Terminals N
A8 Terminals L1
A9 Terminals L2
A10 LED direct operation
A11 Button for toggling between bus / direct operation
Mounting and wiring
General description
The DIN rail mounted device with N-system dimensions (4
module units) can be inserted in N-system distribution
boards, either surface- or flush-mounted, and wherever
EN 50022-35 x 7.5 DIN rails are available. The contact
with the bus line is carried out via the bus terminals or
via the contact system to the data rail.
Assembling the DIN rail mounted device (Figure 2)
-Place the device (B1) on the DIN rail (B2) and
-rotate the device downwards until the slide switch au-
dibly clicks into position.
Dismantling the DIN rail mounted device (Figure 2)
-Remove all the connected cables,
-press the slide switch (C3) down with a screwdriver
and
-remove the device (C1) from the DIN rail (C2) with a
swivel action.
B1 C1
C2
C3
B2
Figure 2: Assembling and dismantling the DIN rail
mounted device
Removing the bus terminal (Figure 3)
-The bus terminal is located on the top of the Venetian
blind switch N 523/02 (D1)
-The bus terminal (D2) consists of two sections (D2.1,
D2.2), each with four terminal contacts. Care should
be taken not to damage the two test sockets (D2.3) ei-
ther by accidentally connecting them to the bus con-
ductor or with the screwdriver when attempting to
remove the bus terminal.
-Carefully insert the screwdriver in the wire entry slot
underneath the bus terminal (D2) and pull the bus ter-
minal forwards out of the Venetian blind switch
N 523/02 (D1).
Note
When removing the bus terminal, there is a danger of
short circuits.
Plugging in the bus terminal (Figure 3)
-Place the bus terminal (D2) in the guide slot and
-press downwards until it reaches the stop.
Connecting the bus cable (Figure 3)
-The bus terminal (D2) is suitable for single-core con-
ductors with 0.6 ... 0.8 mm Ø.
-Strip approx. 5 mm of insulation from the conductor
(D2.4) and then plug in the terminal (D2) (red = +,
black = -).
Disconnecting the bus cable (Figure 3)
-Remove the bus terminal (D2) and the conductor
(D2.4) from the bus cable by rotating them simultane-
ously backwards and forwards.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
instabus EIB
Technical product information
August 2010
Venetian blind switch N 523/02 5WG1 523-1AB02
4 x 230 V AC / 6 A
Technical manual N 523/02, 4 pages Siemens AG
Industry Sector, Building Technologies
Update: http://www.siemens.com/gamma © Siemens AG 2010 Electrical Installation Technology
Subject to change without further notice P.O. Box 10 09 53, D-93009 Regensburg
2.10.1.13/4
C1
C2
C2
C2.4
C2 C2.4
5 mm
C2.1 C2.2
2
C2.3
C
Figure 3: Connecting and removing the cable
Connecting the mains voltage and Venetian blind drives
-The connections are carried out with plug-in terminals.
-Strip approx. 9-10 mm of insulation from the conduc-
tor and slide into the respective terminal.
-Outputs A and B are supplied via terminal L1 while
outputs C and D are supplied via terminal L2. This en-
ables two outputs to be connected to different exter-
nal conductors. If all the actuator outputs should be
connected to the same external conductor, a terminal
L1 must be linked to a terminal L2 via a wiring jumper.
Cross-sections:
•The following conductor cross-sections are permitted:
-2 x 0.5... 2.5mm² single-core or 2 x 0.5... 1.5mm²
finely stranded with connector sleeve
•Each of the mains connections L1 and L2 must be
fused with a miniature circuit breaker of characteristic
B or C with a max. nominal current of 10 A.
Mounting the insulating cap
If the device should be mounted on a DIN rail without an
data rail, the contact system must be covered with the
supplied insulating cap.
Removing the locating clamp: (Figure 4)
-The locating clamp (D3) encloses the contact system
(D2) on the rear of the Venetian blind switch (D1).
-Insert the screwdriver between the DIN rail mounted
device (D1) and the locating clamp (D3) and remove
the clamp.
Clipping on the insulation cap: (Figure 4)
Place the insulating cap (D4) on the contact system and
press so that it snaps in place.
Figure 4: Covering the contact system
Dimension drawing
Dimensions in mm
b
90
44
55
45
b = 4 module units
1 module unit = 18 mm
General notes
•Any faulty devices should be returned to the local Sie-
mens office.
•Should you have any additional queries, please contact
our Technical Support department:
℡+49 (911) 895 - 7222
+49 (911) 895 - 7223
E-mail: support.automation@siemens.com
Web: http://support.automation.siemens.com
D3 D1 D2 D2 D4 D1

This manual suits for next models

1

Other Siemens Switch manuals

Siemens 3VA1225-1AA 2 Series User manual

Siemens

Siemens 3VA1225-1AA 2 Series User manual

Siemens Scalance X204-2 Multimode Service manual

Siemens

Siemens Scalance X204-2 Multimode Service manual

Siemens RUGGEDCOM RS900GF User manual

Siemens

Siemens RUGGEDCOM RS900GF User manual

Siemens 5SG7234-1 User manual

Siemens

Siemens 5SG7234-1 User manual

Siemens BT300 LonWorks User manual

Siemens

Siemens BT300 LonWorks User manual

Siemens 3WN6 User manual

Siemens

Siemens 3WN6 User manual

Siemens 3KA User manual

Siemens

Siemens 3KA User manual

Siemens SCALANCE XR-300M PoE Series Administrator guide

Siemens

Siemens SCALANCE XR-300M PoE Series Administrator guide

Siemens SIMATIC NET RUGGEDCOM M969F User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM M969F User manual

Siemens SIMATIC NET RUGGEDCOM RS900 User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RS900 User manual

Siemens Type Vector User manual

Siemens

Siemens Type Vector User manual

Siemens RUGGEDCOM RSG2300F User manual

Siemens

Siemens RUGGEDCOM RSG2300F User manual

Siemens SIMATIC NETRUGGEDCOM RS900W User manual

Siemens

Siemens SIMATIC NETRUGGEDCOM RS900W User manual

Siemens SIMATIC NET SCALANCE SC-600 Instruction sheet

Siemens

Siemens SIMATIC NET SCALANCE SC-600 Instruction sheet

Siemens siprotec 7SA522 User manual

Siemens

Siemens siprotec 7SA522 User manual

Siemens SIMATIC NET RUGGEDCOM RS920L User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RS920L User manual

Siemens SIMATIC NET RUGGEDCOM RS930W User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RS930W User manual

Siemens 3KD Series User manual

Siemens

Siemens 3KD Series User manual

Siemens SIMATIC NET RUGGEDCOM RS900F User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RS900F User manual

Siemens SIMATIC NET RUGGEDCOM RST2228 User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RST2228 User manual

Siemens SIRIUS Instruction sheet

Siemens

Siemens SIRIUS Instruction sheet

Siemens 3NJ4183-3 User manual

Siemens

Siemens 3NJ4183-3 User manual

Siemens SCALANCE MM900 Administrator guide

Siemens

Siemens SCALANCE MM900 Administrator guide

Siemens 3VT9300-4WA30 User manual

Siemens

Siemens 3VT9300-4WA30 User manual

Popular Switch manuals by other brands

Hama 00079091 Operating	 instruction

Hama

Hama 00079091 Operating instruction

LEGRAND Wattstopper LMPS-104-W quick start guide

LEGRAND

LEGRAND Wattstopper LMPS-104-W quick start guide

AAS POE-0401-60 user manual

AAS

AAS POE-0401-60 user manual

VigilLink VLML-16X1H13 user manual

VigilLink

VigilLink VLML-16X1H13 user manual

Agema Delta AGV424 installation guide

Agema

Agema Delta AGV424 installation guide

Converters.TV 15429 Operation manual

Converters.TV

Converters.TV 15429 Operation manual

AlzaPower APW-HCC7B user manual

AlzaPower

AlzaPower APW-HCC7B user manual

Honeywell NR Series General information

Honeywell

Honeywell NR Series General information

Eaton ATR Instruction leaflet

Eaton

Eaton ATR Instruction leaflet

Gefen EXT-DVIKVM-441DL user manual

Gefen

Gefen EXT-DVIKVM-441DL user manual

Moxa Technologies EDS-600 Series Quick installation guide

Moxa Technologies

Moxa Technologies EDS-600 Series Quick installation guide

TRENDnet TK-210K user guide

TRENDnet

TRENDnet TK-210K user guide

Moxa Technologies EtherDevice EDS-510A Series user manual

Moxa Technologies

Moxa Technologies EtherDevice EDS-510A Series user manual

PulseWorx WS1D quick start guide

PulseWorx

PulseWorx WS1D quick start guide

Endress+Hauser Liquiphant S FTL70 7 Series operating instructions

Endress+Hauser

Endress+Hauser Liquiphant S FTL70 7 Series operating instructions

IOGear GCS1932 user manual

IOGear

IOGear GCS1932 user manual

TRENDnet TPE-224WS - Web Smart PoE Switch Specifications

TRENDnet

TRENDnet TPE-224WS - Web Smart PoE Switch Specifications

Roland V-44SW Midi implementation

Roland

Roland V-44SW Midi implementation

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.