
18 / 24
Siemens RDF880KN… A6V11282546_en--_a
Building Technologies Touch Screen Flush-mount Room Thermostats with KNX Communications 2018-04-19
Obj. Object Name Function Type Length CRWTU Descriptions / Selections:
visibility depends on DIP switch setting
35 Fan speed:
preselection
percentage
(0..100%) 5.001 1 byte CRWTU
CONTROL/STATUS: use for DIP switch Setting à2: VRF
It is a command to set the fan speed (ECM) – depends on value of P53.
e.g. if P53 = 3, indicates the current fan speed as a value 0...100%
Speed Fan output (physical KNX value)
OFF 0% (0)
1 33% (84 )
2 66% (186)
3 100% (255)
36 Fan speed counter pulses
(0..255) 5.010 1 byte CRT
CONTROL: use for DIP switch Setting à2: VRF
It is a command to set the fan speed – depends on value of P53.
0 – Auto; 1 - Speed 1; 2 - Speed 2; 3 - Speed 3;4 - Speed 4; 5 - Speed 5; 6 - Speed
6; 7 - Speed 7
37 Fan speed status counter pulses
(0..255) 5.010 1 byte CWU
STATUS: use for DIP switch Setting à2: VRF
The value of fan speed received will be set and displayed on HMI.
Speed depends on value of P53:
0 – Auto; 1 - Speed 1; 2 - Speed 2; 3 - Speed 3;4 - Speed 4; 5 - Speed 5;
6 - Speed 6; 7 - Speed 7
38 VRF Operating Mode HVAC
control mode 20.105 1 byte CRT
CONTROL: use for DIP switch Setting à2: VRF
It is a command to set the VRF operating mode for VRF equipment.
0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
39 X1: Temperature temperature
value (°C) 9.001 2 bytes CRT CONTROL: all DIP switch Settings
Indicate the values of the temperature sensors connected to the local inputs
X1/X2 (P38/P40).
41 X2: Temperature temperature
value (°C) 9.001 2 bytes CRT
40 X1: Digital switch 1.001 1 bit CRT CONTROL: all DIP switch Settings
Indicates the logic state of the digital inputs (P39 for X1, P41 for X2).
42 X2: Digital switch 1.001 1 bit CRT
43 Control on/off switch 1.001 1 bit CRT
CONTROL: use for DIP switch Setting à2: VRF
It is a command to turn on and off the VRF equipment.
0 - Off; 1-On
44 Control vane up/down
position
counter pulses
(0..255) 5.010 1 byte CRT
CONTROL: use for DIP switch Setting à2: VRF
It is a command to set the vane position of the VRF equipment.
0 – Auto; 1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4; 5 - Pos5; 6 - Pos6; 7 - Pos7; 8 - Pos8;
9 - Pos9; 10 - Pos10
45 Control vane up/down
swing boolean 1.002 1 bit CRT
CONTROL: use for DIP switch Setting à2: VRF
It is a command to set the vane to a stop position or auto swing.
The vane position depends on the object, Control vane up/down position (44).
0 - Stop; 1 – Swing
46 Control eco mode start/stop 1.01 1 bit CRT
CONTROL: use for DIP switch Setting à2: VRF
It is a command to enable or disable the ECO mode of the VRF equipment.
0 - Stop; 1 – Start
47 Status on/off Switch 1.001 1 bit CWU
STATUS: use for DIP switch Setting à2: VRF
A value is received from a KNX control device to turn on and off the VRF
equipment. 0 - Off; 1-On
48 Status vane up/down
position
counter pulses
(0..255) 5.010 1 byte CWU
STATUS: use for DIP switch Setting à2: VRF
A value is received from a KNX control device to set the vane position of the VRF
equipment.
0 – Auto; 1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4; 5 - Pos5; 6 - Pos6; 7 - Pos7; 8 - Pos8;
9 - Pos9; 10 - Pos10
49 Status vane up/down
swing boolean 1.002 1 bit CWU
STATUS: use for DIP switch Setting à2: VRF
A value is received from a KNX control device to set the vane of the VRF
equipment to stop or auto swing. 0 - Stop; 1 – Swing
50 Status eco mode Switch 1.001 1 bit CWU
STATUS: use for DIP switch Setting à2: VRF
A value is received from a KNX control device to set the VRF equipment in ECO
mode. 0 - Off; 1-On
51 Room relative humidity Humidity % 9.007 2 bytes CRT CONTROL: all DIP switch Settings
It is the command to send out for the current value of relative humidity.
53 Room temp: Economy
heating setpoint
temperature
value (°C) 9.001 2 bytes CWU STATUS: all DIP switch Settings
A value is received from a KNX control device to update parameter P11.
55 Application selection:
State
counter pulses
(0..255) 5.010 2 bytes CR
CONTROL: all DIP switch Settings
A value is required to be read out from RDF880KN/NF for the current DIP SW
setting. Refer to dip switch position selection.
1 - UFH only; 2 - VRF only; 3 - both VRF & UFH
56 Sub application:
Preselection
counter pulses
(0..255) 5.010 1 byte CRT
CONTROL: use for DIP switch Setting à3: BOTH
It is a command to send out for the current sub selection below within a combined
UFH and VRF/VRF unit.
1 - UFH only; 2 - VRF only; 3 - both VRF & UFH
57 Sub application:
State
counter pulses
(0..255) 5.010 1 byte CWU
STATUS: use for DIP switch Setting à3: BOTH
A value is received from a KNX control device for the current sub selection below
within a combined UFH and VRF/VRF unit.
1 - UFH only; 2 - VRF only; 3 - both VRF & UFH
C: Communication; R: Read; W: Write; T: Transmission; U: Update
Notes: The current RDF880KN/NF is based on a Floor Heating Controller with additional VRF HMI. Therefore, to turn on the controller, effectively, it is to turn on the UFH application.
1. In a UFH application selected via DIP switch setting or remote configuration, the operations are identical to RDD810KN/NF while all VRF relevant S-mode objects are invisible.
2. In a VRF application selected via DIP switch setting or remote configuration, UFH application will not be turned ON remotely via any KNX control devices or locally via HMI.
3. In a combined application (both UFH and VRF) selected via DIP switch setting or remote configuration, the object Sub Application (56, 57) can be used by any KNX control devices
to do remote selection of applications (UFH only, VRF only or UFH & VRF) required. But the objects: Time Switch/Schedule (12, 13, 14, and 15) or ECO mode (10, 18) via any KNX
control devices remotely will turn on/off both VRF and UFH. Therefore, it is not recommended to use objects: Time Switch/Schedule (12, 13, 14, and 15) or ECO mode (10, 18).
*) If object Fan operation (33) is used together with object Fan speed (36), the value “0 – Auto” of object Fan speed (36) cannot be used. If these two objects are not used together, the
value “0 – Auto“ can be used.