
 
Menu Selection and Response Keys (Cont’d) 
 
Disable/Enable toggles status of the displayed circuit. 
Exit/Clear provides a path out of the chosen menu and 
allows manual entries to be cleared. 
Enter confirms the selection made and enters program 
changes into memory. 
Left, Previous, Next, and Right arrow keys move the 
display cursor or select screens or specific choices, 
depending on the displayed functional area. 
4005 System Optional Modules 
 
Class A, 4 Circuit Adaptor Module for either IDCs 
or NACs (4005-9806): 
•Individually isolated circuit design adapts either IDCs or 
NACs for Class A operation allowing a combination of 
circuit types 
•Mounts on top of the module, maintaining full module 
capacity 
Power Distribution Module (4005-9807): 
•Extends 4005 capacity to ten plug-in modules 
•Mounts on left side of 4005 chassis 
•Required when plug-in module requirements extend 
beyond five and/or for connection of expansion power 
supply 4005-9813 
City Circuit Module (4005-9809): 
•Single circuit, selectable as local energy, reverse 
polarity, or form “C” contact 
•Reverse polarity is selectable for Alarm/Trouble, Alarm, 
Supervisory, or Trouble only reporting 
•Up to two modules mount directly to 4005 chassis below 
the CPU assembly 
Expansion Power Supply (4005-9813): 
•Provides power-limited and regulated 24 VDC to 
Expansion Module 4005-9807; rated 5 A for Special 
Application Appliances and 2 A for Regulated 24 DC 
power 
•Installs on the left side of the 4005 chassis and fits 
behind expansion modules, allowing full module 
capacity 
•Switch selectable for 120 VAC or 240 VAC 
•Provides additional power for notification appliances, 
4-wire detectors, annunciator power, or other fire alarm 
auxiliary functions 
4005 System Capacity Expansion Modules 
 
Optional and expansion modules can be easily installed and 
programmed on-site. Their “snap-in-place” design installs 
without tools or hardware, allowing configuration for the 
initial system capacity or for later system expansion. 
2 Circuit IDC with 2 Circuit NAC/Relay 
(4005-9803): 
•Two, standard low current IDCs, for up to 20 detectors 
per IDC, 2 mA maximum 
 
Capacity Expansion Modules (Continued) 
 
•Two circuits, individually on-site selectable as either 
Class B NAC, or N.O. or N.C. relay circuits 
•Combined on one plug-in module 
•Operation and programming is the same as the standard 
control panel IDCs and NAC/Relay circuits 
4 Circuit IDC Module (4005-9804): 
•Four, standard low current IDCs on one plug-in module, 
for up to 20 detectors per IDC, 2 mA maximum 
•Operation and programming is the same as the standard 
control panel IDCs 
4 Circuit NAC/Relay Module (4005-9805): 
•Four, NAC/Relay Circuits on one plug-in module 
•Operation and programming is the same as the standard 
control panel NAC/Relay circuits 
8 Circuit I/O Module (4005-9808): 
•Select each circuit as either an input or output 
•Input mode supervises hard wired connections to 4601 
Series annunciator switches or utility switch inputs 
•Output mode is rated 24 VDC, 150 mA open collector 
driver, short circuit protected, UL listed for pilot duty 
•Output mode provides supervised auxiliary control of a 
compatible annunciator or remote relay for emergency 
control in accordance with NFPA 72 and NFPA 101 
4 Circuit IDC, High Current, Required for 
Detectors with Relay Bases (4005-9824): 
•Four, high current IDCs on one plug-in module 
•High current operation for up to 30 detectors per IDC, 
3 mA maximum detector power (required for detectors 
with relay bases) 
•Operation and programming is the same as the standard 
control panel IDCs 
Accessories 
 
4602 Series Annunciators: 
•Supervised serial communications using twisted, 
shielded pair 
•SCU has 16 LED zone status indicators 
•RCU has 8 LED zone status indicators, Power-On LED 
and Trouble LED, Local tone-alert, and keyswitch 
enabling of Trouble and Alarm Silence, System Reset, 
and Manual Evacuation 
4601 Series Annunciators: 
•Provides LED status indications and switches for 
acknowledge, silence, and reset 
•Modular design allows sizing as needed 
4005-9150 and 4002 Adapter Kits for Retrofit: 
•Replace existing 4002 Fire Alarm Control Panels with 
the 4005 panel features, supplied with high current IDC 
modules for convenient retrofit 
•Cabinet, door, and electronics may be ordered separately 
to satisfy early cabinet (backbox) installation 
requirements 
 5 S4005-0001-9 3/2009