
 
Automatic Extinguishing Release Systems 
 
These systems automatically activate electrically 
controlled actuators for the release of a fire extinguishing 
agent (such as dry chemical, water spray, foam, CO2,or 
clean agent) in response to fire detection device inputs as 
determined by programming of the host fire alarm control 
panel. 
Automatic Extinguishing Release System Panels 
are required to have a minimum of 24 hours of standby 
power. Initiating devices must be Listed/Approved for the 
application, and may be wired either Class A or B. 
Control actuators must be electrically compatible with the 
control panel circuits and power supplies, and are wired 
Class B to provide coil supervision. 
Deluge or Preaction Sprinkler Systems 
 
These systems automatically activate water control 
actuators in response to fire detection device inputs. 
Deluge Sprinkler Systems employ open sprinkler 
heads and provide water flow when the fire detection 
system activates a common automatic water control 
actuator. They are used to deliver water simultaneously 
through all of the system sprinkler heads. This type of 
system is applicable where the immediate application of 
large quantities of water over large areas is the proper fire 
response. 
Preaction Sprinkler Systems are similar to deluge 
systems except that normally closed sprinkler heads are 
used and supervisory air pressure is maintained in the 
pipe. Operation requires both an activated sprinkler head 
and an activated fire alarm initiating device with specific 
programming determined at the host fire alarm control 
panel. 
Releasing System Requirements 
 
1. Releasing actuators are controlled from a 
Suppression Release Peripheral (4090-9005 or 
4090-9006). Connections are 2-wire, Class B releasing 
circuits with only one 24 VDC actuator per circuit. 
Where applicable, two, 12 VDC actuators in series, or 
one 12 VDC actuator with manufacturer supplied 
resistor may be used. 
2. Coil Supervision Module 2081-9046 must be wired 
electrically before the actuator and located in the 
actuator wiring junction box. (Refer to diagram on 
page 5.) The connected RAC provides continuity 
supervision of the actuator coil and wiring and 
provides short circuit supervision to the coil 
supervision module. 
3. Cross-zoning or other alarm initiation logic per 
system requirements, is to be implemented by 
programming at the fire alarm control panel. 
4. UL Listed Automatic Extinguishing Releasing 
operation requires that: battery standby must be a 
minimum of 24 hours with 5 minutes of alarm and that 
listed actuators are used, refer to list on page 6. 
 
Releasing System Requirements (Continued) 
 
5. FM Approved Automatic Extinguishing Release 
requires secondary standby to be a minimum of 
24 hours with 5 minutes of alarm. Actuators must be 
electrically compatible. 
6. FM Approved Deluge and Preaction Sprinkler 
operation requires that: initiating device circuits be 
Class A and wired to Listed/Approved devices; 
standby power capacity must be a minimum of 90 
hours with 10 minutes of alarm; and that approved 
Automatic Water Control Valves must be used. (Refer 
to actuator list on page 7.) 
7. Maintenance Switches, one per RAC, are required 
per NFPA 72, the National Fire Alarm and Signaling 
Code to allow the system to be tested or serviced 
without actuating the fire suppression systems. Their 
use may not be allowed in some jurisdictions, always 
confirm local requirements. When used, Simplex 
Maintenance Switches are required to ensure that 
operation initiates a supervisory condition. 
8. Abort Switches are available when abort operation is 
required. When used, connect to an addressable 
Supervised IAM model 4090-9001 or similar 
addressable adapter module. The Simplex abort switch 
and the IAM mount in a single gang box, 2-1/2” 
minimum depth. 
9. Addressable Manual Releasing Stations are used to 
initiate activation of the releasing actuators with the 
appropriate time delay implemented by the fire alarm 
control panel. 
10. Notification Requirements. Each hazard area 
typically requires general audible and visible fire 
alarm notification and additional dedicated NACs for 
area releasing status notification. Use of the 4009 
IDNet NAC Extender will provide the required 
additional NACs. 
11. Additional 4010 Reference. Refer to Installation and 
Operating Instructions 574-052 and Field Wiring 
Diagram 842-058 for additional 4010 releasing and 
general panel information. 
12. Additional Suppression Release Peripheral 
Reference. Refer to Installation Instructions 579-385. 
 
Additional Releasing Systems Reference 
 
For additional information, refer to Factory Mutual 
Research Corporation (FMRC) “FMRC Approval Guide,” 
FM Approval standard “Deluge Systems and Preaction 
Systems.” 
Please note that proper operation of releasing control 
systems requires that the system design, installation, and 
maintenance be performed correctly and in accordance 
with all applicable local and national codes, and 
equipment manufacturer’s instructions. No liability for 
total system operation is assumed or implied. 
 2 S4010-0003-5 6/2013