
 
Addressable notification appliance communications 
include operation of TrueAlert and TrueAlert ES Visible only 
(V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, 
horn/strobe), and strobes of Speaker/Visible (S/V) notification 
appliances. (S/V appliances require separate speaker wiring.) 
IDNAC SLC addressable communications allow each horn and 
strobe to be individually controlled using a single two-wire 
circuit, confirms the wiring connections to the individual 
notification appliance’s electronic circuit, and confirms 
communications between each appliance and the fire alarm 
control panel. Addressable communications increases 
supervision integrity versus conventional notification systems 
by providing supervision beyond the circuit wiring to each 
individual appliance and by constantly verifying the ability of 
each appliance to communicate with the control panel. 
Individual Appliance Status and Settings. The fire alarm 
control panel monitors and records each addressable notification 
appliance status, type of appliance, and its configured appliance 
settings. A fault in any individual appliance automatically 
reports a trouble condition to the control panel. 
TrueAlert ES Addressable Appliance Reference 
 
A/O (horn) V/O (strobe) A/V (horn/strobe) 
Virtual NACs Provide Control Convenience. For control 
convenience, IDNAC notification appliances can be grouped 
into Virtual NACS (VNACs) for group control, grouping that 
can be made across SLCs, not defined by their wiring 
connection. 
Panel Control Convenience. Applicable operation settings 
for each appliance can be programmed without having to 
replace appliances or remove them from the wall or ceiling. An 
appliance’s VNAC notification zone can be easily changed 
through programming without having to add additional circuits, 
conduit, and wiring. Audible and visible appliances for non-Fire 
Emergency Communications notification can be programmed to 
operate separately on the same pair of wires as the fire alarm 
notification appliances. The result is lower installation, retrofit, 
and overall life-cycle cost of ownership compared with 
traditional conventional notification systems. 
Installation, Retrofit, and Life-Cycle Cost Benefits. 
With each addressable appliance capable of being controlled 
separately on the same two-wire IDNAC SLC, installation time 
and expense for both retrofit and new construction can be 
significantly reduced. When Class B wiring is used, wiring can 
be “T-tapped” allowing more savings in distance, wire, conduit 
(size and utilization), and overall installation efficiency. 
Location Information, Diagnostics and 
Troubleshooting. Each addressable notification appliance 
has its own 40 character custom label to identify the location of 
the appliance and to aid in troubleshooting fault conditions. In 
conventional notification systems, conventional appliances are 
not capable of communicating with the control panel. Fault 
reporting on a conventional system is limited to the circuit 
wiring and the entire area (zone) covered by appliances on the 
notification appliance circuit (NAC) making it much more 
difficult and costly to locate and correct the source of a 
 
problem. Using the TrueAlert magnet test allows each appliance 
to individually identify its candela setting and address and to 
briefly operate if desired, and using the TrueAlert ES 
Appliance Self-Test feature provides detailed performance 
verification per appliance. 
TrueAlert ES Appliance Self-Test Operation 
 
On-Board Test Sensors. TrueAlert ES appliances are 
equipped with on-board sensors to detect strobe and/or horn 
output allowing efficient and unobtrusive Self-Testing. When 
Automatic Self-Test is initiated from the control panel, each 
appliance within the selected VNAC group will briefly operate 
and then report its Self-Test status to the control panel, all 
within several seconds. Silent Self-Test can be selected to test 
only visible appliance if desired. The control panel is in a 
trouble condition during testing and in the event of an alarm, 
Self-Test is automatically terminated. Additionally, Automatic 
Self-Test can be scheduled to occur at a convenient time on a 
regular basis. 
Automatic Self-Test results are communicated to the 
control panel with a time and date stamp and are stored in 
memory. Results are viewable at the front panel display and 
printed reports can be generated from the panel service port. 
Individual Self-Test is selected from the control panel when 
individual appliances need to be observed to operate. Each 
appliance in the selected VNAC group will turn on its LED 
until individually activated by applying a magnet. After 
performing the individual test, the appliance LED turns off to 
indicate completion. Results are recorded the same as during the 
automatic test. 
 
IDNAC SLC Hardware Reference 
 
The Enhanced System Supply provides two, 3 A IDNAC 
SLCs for control and power to TrueAlert ES and TrueAlert 
addressable notification appliances. Both power supplies 
incorporate an efficient switching design that provides a 
regulated output of 29 VDC, even during battery operation. 
With 29 VDC minimum output at the panel, addressable 
notification SLCs can support wiring distances 2 to 3 times 
farther than available with conventional notification, or support 
more appliances per SLC, or work with smaller gauge wiring, 
or combinations of these benefits. The result is installation and 
maintenance savings with high assurance that appliances that 
operate during normal system testing will operate during worst 
case alarm conditions. 
IDNAC SLC Appliance Wiring Reference 
 
IDNAC SLC Capacity: Up to 127 addresses and up to 139 unit 
loads (appliances are typically one unit load, devices such as 
Isolators may require more than one load, refer to individual 
device data sheet for specific information) 
Recommended Wire Type UTP, unshielded twisted pair 
Maximum wire length 
allowed with “T-Taps” for 
Class B wiring, per SLC 
10,000 ft (3048 m) 
Maximum wire length per 
SLC to any appliance 4000 ft (1219 m) 
Appliance Supervisory 
Current 1 unit load = 0.8 mA per appliance 
Wiring Connections Terminals for 20 to 12 AWG 
(0.52 mm2to 3.31 mm2) 
 5 S4010-0011-5 11/2015
 IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification