Simplex 4100-5101 User manual

4100U XPS and XNAC
Installation Instructions
2001, Simplex Time Recorder Co.,Westminster, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice.
574-772
Rev. A
This publication describes the installation procedure for 4100-5101 (120 VAC), 4100-5102
(220/230/240 VAC), and 4100-5103 (120 VAC with battery disconnect) Expansion Power
Supplies (XPSs), and the 4100-5115 Expansion NAC Module (XNAC).
Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify Simplex.
This publication discusses the following topics:
Topic See Page #
Cautions and Warnings 2
Expansion Power Supply Modules 3
The Expansion Power Supply (XPS) 4
Step 1. Mounting the XPS 6
Step 2. XPS Configuration 7
Step 3. Internal Wiring 9
Step 4. XPS Field Wiring 11
Step 5. Installing the XNAC 17
Step 6. Troubleshooting 18
Introduction
Inspecting Contents
of Shipment
In this Publication
firealarmresources.com

2
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product and associated
equipment. Product operation and reliability depends upon proper installation.
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED.Upon
unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD -Disconnect electrical field power when making any internal
adjustments or repairs. Servicing should be performed by qualified Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
• Ground yourself before opening or installing components (use the 553-484 Static Control
Kit).
• Prior to installation, keep components wrapped in anti-static material at all times.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply with the
limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a
commercial environment. Operation of this equipment in a residential area may cause interference
in which case the user at his own expense will be required to take whatever measures may be
required to correct the interference.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES -To ensure proper
system operation, this product must be tested in accordance with NFPA72-1996, Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required
after any change, addition or deletion of system components, or after any modification, repair or
adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified.
Cautions and Warnings
firealarmresources.com

3
This publication describes the installation procedure for the following:
• 4100-5101 Expansion Power Supply (XPS), 120 VAC, 60 Hz
• 4100-5102 XPS, 220/230/240 VAC 50/60 Hz
• 4100-5103 XPS, 120 VAC, 60 Hz, with battery disconnect (Canada)
• 4100-5115 Expansion NAC Module (XNAC)
The XPS provides an additional 24 VDC for option cards and for DC notification. An XPS may
supply 24 V card power to modules in the same bay or in other bays. The course of the card power
for modules in a bay is selected by jumpers on the PDI.
The XPS provides 24 VDC to 3 notification appliance circuits, plus an additional three when the
XNAC is installed. NACs can be Class B (Style Y) or Class A (Style Z), and are power limited to
UL864. The NACs support non-addressable TrueAlert and conventional reverse-polarity
operation.
Notification and auxiliary signal power is also provided by the XPS.
The XPS has a 9 A capacity. Each NAC is rated at 3 A. A NAC can also be configured as an
auxiliary power point, in which case it is rated at 2 A. The total load at 24 VDC must be no more
than 9 A. The total load includes NACs (on the XPS or the XNAC Module), auxiliary power, card
power, and signal power used by modules plugged into the same bay.
Note: If NACs are to be used as auxiliary outputs, they must be configured as such in
the 4100U Programmer. Programming may also be required for dedicated
auxiliary outputs; refer to the 4100U Fire Alarm PC Programmer Programming
Manual (574-849).
NACs are monitored for short and open circuits. If a short circuit occurs, the affected NAC will
not be energized.
When the XPS starts up, it automatically starts a NAC mis-wiring test, which checks for NACs
that are shorted together. The test can also be initiated on command from the operator interface.
AC power and battery backup are provided to the XPS through a connection to the PDM.
Expansion Power Supply Modules
Overview
firealarmresources.com

4
Figure 1, below, is an illustration of the XPS.
NAC1 NAC2 NAC3
-- -- --
P1
P3
E5
ATT
T
E4
P2 T2
0
24
E6
CMMS
T
Figure 1. The Expansion Power Supply
Continued on next page
The Expansion Power Supply (XPS)
XPS Features
AUXILIARY
POWER INPUT
(TB2)
PDI CONNECTOR
(reverse side)
AC STATUS LED
(LED4)
XNAC
CONNECTOR
(P3)
NAC TERMINAL
BLOCK (TB1)
NAC STATUS
LEDs:
LED1
LED2
LED3
BATTERY
TROUBLE LED
(LED5)
DEVICE
ADDRESS DIP
SWITCH (SW1)
SIGNAL POWER
CONNECTOR (P1)
POWER/ COMMS
OUTPUT TO
NEXT PDI (P2)
3 A (NAC)
2 A (AUX)
3 A (NAC)
2 A (AUX)
3 A (NAC)
2 A (AUX)
2 A
COMM TROUBLE
LED (LED6)
firealarmresources.com

5
The XPS has the following LEDs:
LED1 (yellow). Illuminates when NAC 1 is active or in a trouble state; otherwise it is off.
LED2 (yellow). Illuminates when NAC 2 is active or in a trouble state; otherwise it is off.
LED3 (yellow). Illuminates when NAC 3 is active or in a trouble state; otherwise it is off.
LED4 (green). Illuminates when the XPS is running off of AC power; otherwise it is off.
LED5 (yellow). General Status LED.
• On steady: Overcurrent tripped.
• Single repeating flash: Battery not connected.
LED6 (yellow). Illuminates when communication loss with the CPU occurs. Normally off.
Table 1 summarizes the input and output specifications for the XPS.
Table 1. Input and Output Specifications
AC Input Specifications
4100-5101 120 VAC @ 60 Hz, nominal (102-132 VAC @ 60 Hz)
4 A Max
4100-5102 220/230/240 VAC @ 50 or 60 Hz
2 A Max
4100-5103 120 VAC @ 60 Hz, nominal (102-132 VAC @ 60 Hz)
DC Output Specifications
All XPSs Minimum: 19.5 VDC
Maximum: 32 VDC
Ripple: 2 VDC p-p @ full load (9 A)
The range of possible temperatures under which the XPS may function are between 0°C (32°F)
and 49°C (120°F).
The XPS operates normally under non-condensing humidity conditions up to 93% with relative
humidity at 32° C (90° F).
The Expansion Power Supply (XPS), Continued
LEDs
Input and Output
Specifications
Environmental
Requirements
firealarmresources.com

6
The XPS is designed to be mounted on the rightmost top and bottom positions of the PDI in a
4100 expansion cabinet. Before mounting the XPS, follow these guidelines:
• Disconnect power to the system or remove power at the breaker before mounting or
installing anything in the unit.
• No more than 30 amps of power are allowed in any cabinet (1-, 2-, or 3-bay). The XPS
uses 9 amps.
Use Figure 2, and the following instructions to mount the XPS.
1. Insert the two tabs on the bottom of the XPS into the rightmost two slots in the cabinet.
2. Push the XPS assembly against the back of the expansion bay.
• Connect to the PDI as shown in Figure 2.
• Correctly align the screwhole at the top of the XPS assembly with the hole in the bay
chassis.
• Use one #6 torx screw to secure the assembly to the expansion box.
Figure 2. XPS Mounting
Continued on next page
Step 1. Mounting the XPS
Guidelines
Mounting
4100 POWER DISTRIBUTION INTERFACE
ASSY 566-084
One #6 torx screw
secures the assembly
to the cabinet
EXPANSION POWER
SUPPL
Y
EXPANSION BA
Y
BACKPLANE with PDI
PDI CONNECTION
Tabs go into slots
PDI connector
firealarmresources.com

7
XPS configuration consists of setting the address switch as described in this section.
The XPS device address is set via DIP switch SW1, which is a bank of eight switches. From left to
right (see Figure 3, below) these switches are designated as SW1-1 through SW1-8. The function
of these switches is as follows:
• SW1-1. This switch sets the baud rate for the internal 4100 communications line
running between the card and the 4100 CPU. Set this switch to ON to communicate.
• SW1-2 through SW1-8. These switches set the card’s address within the 4100 FACP.
Refer to Table 2 for a complete list of the switch settings for all of the possible card
addresses.
Note: You must set these switches to the value assigned to the card by the 4100
Programmer.
18
7
6
5
4
3
2
Figure 3. DIP Switch SW1
Continued on next page
Step 2. XPS Configuration
Overview
Setting the Address
OFF
ON
Dip Switches SW1-2 through
SW1-8 set the Card Address.
Figure shows an Address of 3.
4100 Comm. Baud
Rate. Switch
(SW1-1)
Must Be Set to
ON
firealarmresources.com

8
Table 2. XPS Card Addresses
Continued on next page
Step 2. XPS Configuration, Continued
Setting the Address,
(continued)
Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8 Address SW 1-2 SW 1-3 SW 1-4 SW 1-5 SW 1-6 SW 1-7 SW 1-8
1 ON ON ON ON ON ON OFF 61 ON OFF OFF OFF OFF ON OFF
2 ON ON ON ON ON OFF ON 62 ON OFF OFF OFF OFF OFF ON
3 ON ON ON ON ON OFF OFF 63 ON OFF OFF OFF OFF OFF OFF
4 ON ON ON ON OFF ON ON 64 OFF ON ON ON ON ON ON
5 ON ON ON ON OFF ON OFF 65 OFF ON ON ON ON ON OFF
6 ON ON ON ON OFF OFF ON 66 OFF ON ON ON ON OFF ON
7 ON ON ON ON OFF OFF OFF 67 OFF ON ON ON ON OFF OFF
8 ON ON ON OFF ON ON ON 68 OFF ON ON ON OFF ON ON
9 ON ON ON OFF ON ON OFF 69 OFF ON ON ON OFF ON OFF
10 ON ON ON OFF ON OFF ON 70 OFF ON ON ON OFF OFF ON
11 ON ON ON OFF ON OFF OFF 71 OFF ON ON ON OFF OFF OFF
12 ON ON ON OFF OFF ON ON 72 OFF ON ON OFF ON ON ON
13 ON ON ON OFF OFF ON OFF 73 OFF ON ON OFF ON ON OFF
14 ON ON ON OFF OFF OFF ON 74 OFF ON ON OFF ON OFF ON
15 ON ON ON OFF OFF OFF OFF 75 OFF ON ON OFF ON OFF OFF
16 ON ON OFF ON ON ON ON 76 OFF ON ON OFF OFF ON ON
17 ON ON OFF ON ON ON OFF 77 OFF ON ON OFF OFF ON OFF
18 ON ON OFF ON ON OFF ON 78 OFF ON ON OFF OFF OFF ON
19 ON ON OFF ON ON OFF OFF 79 OFF ON ON OFF OFF OFF OFF
20 ON ON OFF ON OFF ON ON 80 OFF ON OFF ON ON ON ON
21 ON ON OFF ON OFF ON OFF 81 OFF ON OFF ON ON ON OFF
22 ON ON OFF ON OFF OFF ON 82 OFF ON OFF ON ON OFF ON
23 ON ON OFF ON OFF OFF OFF 83 OFF ON OFF ON ON OFF OFF
24 ON ON OFF OFF ON ON ON 84 OFF ON OFF ON OFF ON ON
25 ON ON OFF OFF ON ON OFF 85 OFF ON OFF ON OFF ON OFF
26 ON ON OFF OFF ON OFF ON 86 OFF ON OFF ON OFF OFF ON
27 ON ON OFF OFF ON OFF OFF 87 OFF ON OFF ON OFF OFF OFF
28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON
29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF
30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON
31 ON ON OFF OFF OFF OFF OFF 91 OFF ON OFF OFF ON OFF OFF
32 ON OFF ON ON ON ON ON 92 OFF ON OFF OFF OFF ON ON
33 ON OFF ON ON ON ON OFF 93 OFF ON OFF OFF OFF ON OFF
34 ON OFF ON ON ON OFF ON 94 OFF ON OFF OFF OFF OFF ON
35 ON OFF ON ON ON OFF OFF 95 OFF ON OFF OFF OFF OFF OFF
36 ON OFF ON ON OFF ON ON 96 OFF OFF ON ON ON ON ON
37 ON OFF ON ON OFF ON OFF 97 OFF OFF ON ON ON ON OFF
38 ON OFF ON ON OFF OFF ON 98 OFF OFF ON ON ON OFF ON
39 ON OFF ON ON OFF OFF OFF 99 OFF OFF ON ON ON OFF OFF
40 ON OFF ON OFF ON ON ON 100 OFF OFF ON ON OFF ON ON
41 ON OFF ON OFF ON ON OFF 101 OFF OFF ON ON OFF ON OFF
42 ON OFF ON OFF ON OFF ON 102 OFF OFF ON ON OFF OFF ON
43 ON OFF ON OFF ON OFF OFF 103 OFF OFF ON ON OFF OFF OFF
44 ON OFF ON OFF OFF ON ON 104 OFF OFF ON OFF ON ON ON
45 ON OFF ON OFF OFF ON OFF 105 OFF OFF ON OFF ON ON OFF
46 ON OFF ON OFF OFF OFF ON 106 OFF OFF ON OFF ON OFF ON
47 ON OFF ON OFF OFF OFF OFF 107 OFF OFF ON OFF ON OFF OFF
48 ON OFF OFF ON ON ON ON 108 OFF OFF ON OFF OFF ON ON
49 ON OFF OFF ON ON ON OFF 109 OFF OFF ON OFF OFF ON OFF
50 ON OFF OFF ON ON OFF ON 110 OFF OFF ON OFF OFF OFF ON
51 ON OFF OFF ON ON OFF OFF 111 OFF OFF ON OFF OFF OFF OFF
52 ON OFF OFF ON OFF ON ON 112 OFF OFF OFF ON ON ON ON
53 ON OFF OFF ON OFF ON OFF 113 OFF OFF OFF ON ON ON OFF
54 ON OFF OFF ON OFF OFF ON 114 OFF OFF OFF ON ON OFF ON
55 ON OFF OFF ON OFF OFF OFF 115 OFF OFF OFF ON ON OFF OFF
56 ON OFF OFF OFF ON ON ON 116 OFF OFF OFF ON OFF ON ON
57 ON OFF OFF OFF ON ON OFF 117 OFF OFF OFF ON OFF ON OFF
58 ON OFF OFF OFF ON OFF ON 118 OFF OFF OFF ON OFF OFF ON
59 ON OFF OFF OFF ON OFF OFF 119 OFF OFF OFF ON OFF OFF OFF
60 ON OFF OFF OFF OFF ON ON
firealarmresources.com

9
The XPS gets its power from the power distribution module (PDM). The PDM takes power
directly from the AC mains and the two backup batteries, and distributes power to each bay in the
cabinet.
Figure 4, below, shows the PDM connecting to a host FACP with two XPSs.
Figure 4. System Power
Continued on next page
Step 3. Internal Wiring
Overview
SPS
AC
BTRY
AC
BTRY
AC
BTRY
XPS
XPS SPS = System Power Supply
XPS = Expansion Power Supply
PDM = Power Distribution Module
PDM
INCOMING
AC POWER
BATTERY BATTERY
firealarmresources.com

10
The Power Distribution Module (PDM) connects to the XPS in each bay. One PDM is used per
back box. Use the instructions below to properly connect the PDM to the XPS.
Connect the 734-012 Harness from the top connector on the PDM to the XPS.
1. Wire 120 VAC to the PDM, keeping AC wires at least 1 inch away from all other wires. AC
power must be kept to the right side of the cabinet, in the non-power-limited area.
2. Connect batteries to P5 on the PDM using Harness 733-015.
3. Connect the PDM to the XPS using Harness 734-012.
P1
P2
P3
P4
P5
Figure 5. XPS/PDI Connection
• Feed red and black wires through the side rail to the front of the XPS to prevent wire
damage when the front panel is inserted.a
• Connect the separate red and black wires (with yellow female terminations) to plugs P4
(black) and P5 (red) on the XPS.
• Connect the white and black wires, which terminate together in a white snap-on
connector, to the connector at the bottom of the XPS assembly, as shown below. The
black wire must be closer to the wall at the XPS connection point.
4. Repeat this process for PDM connectors P2 and P3, if applicable.
If the XPS is being installed in a 4100-2301 Expansion Bay,
• Connect the AC power harness (734-049) to the AC power distribution terminal block.
• Connect the battery harness (734-050) to the battery block on the lower right side of the
635-852 Back Box.
Step 3. Internal Wiring, Continued
Power Distribution
Module Connections
4100-2301
Expansion Bay
Wiring
SPS
120 V TO TRANSFORMER
THROUGH BULKHEAD
CONNECTOR
RED WIRE
BLACK WIRE
P4
P5
BATTERY
HARNESS
FUSED AT 15 A
HARNESS 733-015
TO 24 V BATTERY
HARNESS
734-012
PDM
(566-246)
120 V
NEUTRAL
GROUND
BACK BOX
GROUND
SCREW
120 VAC
60 Hz, 4 A
Bulkhead
connector
XPS
ASSEMBLY
firealarmresources.com

11
The XPS provides three outputs for reverse-polarity notification appliance circuits. This section
describes basic NAC wiring from the XPS to 4100-compatible appliances.
The XSPS supports both Class A and Class B NAC wiring.
Class A wiring allows appliances to communicate with the XPS even in the event of an open
circuit somewhere in the loop. Class A wiring requires that two wires are routed from the XPS to
each appliance, and then back again to the XPS.
Table 3 lists the maximum distances from the XPS to the last appliance in a Class A configuration,
depending on wire gauge and current. Use Table 3 to calculate wire distances for your application
if you are using Class A wiring.
Table 3. Class A Wiring Distances
Alarm
Current @
24 V
Max
Distance w/
18 AWG
Max
Distance w/
16 AWG
Max
Distance w/
14 AWG
Max
Distance w/
12 AWG
DC
Resistance
0.25 A 420 ft. 667 ft. 1063 ft. 1691 ft. 6 Ohms
0.50 A 210 ft. 334 ft. 532 ft. 845 ft. 3 Ohms
0.75 A 140 ft. 222 ft. 354 ft. 564 ft. 2 Ohms
1 A 105 ft. 167 ft. 266 ft. 423 ft. 1.5 Ohms
1.25 A 84 ft. 133 ft. 213 ft. 338 ft. 1.2 Ohms
1.50 A 70 ft. 111 ft. 177 ft. 282 ft. 1 Ohm
1.75 A 60 ft. 95 ft. 152 ft. 242 ft. 0.86 Ohm
2 A 53 ft. 83 ft. 133 ft. 211 ft. 0.75 Ohm
2.25 A 47 ft. 74 ft. 118 ft. 188 ft. 0.67 Ohm
2.50 A 42 ft. 67 ft. 106 ft. 169 ft. 0.60 Ohm
2.75 A 38 ft. 61 ft. 97 ft. 154 ft. 0.55 Ohm
3 A 35 ft. 56 ft. 89 ft. 141 ft. 0.50 Ohm
Notes:
• Max Distance = distance from XPS to last appliance.
• This table is calculated at 50 degrees Centigrade. If you are installing in locations
that could be exposed to higher temperatures, refer to NEC Table 8, or contact
Simplex Sales Engineering.
• Distances are based on a 3 V drop, and take into account the worst-case panel
output voltage.
• If CI wire is used instead of housing cable in a fire rated enclosure, reduce wiring
distances by 38 feet for every 10 feet of potential exposure.
Continued on next page
Step 4. XPS Field Wiring
Overview
NAC Wiring Styles
Class A NAC
Wiring Table
firealarmresources.com

12
Table 4 lists the maximum distances from the XPS to the last appliance in a Class B configuration,
depending on wire gauge and current. Use Table 4 to calculate wire distances for your application
if you are using Class B wiring.
Table 4. Class B Wiring Distances
Alarm
Current @
24 V
Max
Distance w/
18 AWG
Max
Distance w/
16 AWG
Max
Distance w/
14 AWG
Max
Distance w/
12 AWG
DC
Resistance
0.25 A 840 ft. 1335 ft. 2126 ft. 3382 ft. 12 Ohms
0.50 A 420 ft. 667 ft. 1063 ft. 1691 ft. 6 Ohms
0.75 A 280 ft. 445 ft. 709 ft. 1127 ft. 4 Ohms
1 A 210 ft. 334 ft. 532 ft. 845 ft. 3 Ohms
1.25 A 168 ft. 267 ft. 425 ft. 676 ft. 2.4 Ohms
1.50 A 140 ft. 222 ft. 354 ft. 564 ft. 2 Ohms
1.75 A 120 ft. 191 ft. 304 ft. 483 ft. 1.71 Ohms
2 A 105 ft. 167 ft. 266 ft. 423 ft. 1.5 Ohms
2.25 A 93 ft. 148 ft. 236 ft. 376 ft. 1.33 Ohms
2.50 A 84 ft. 133 ft. 213 ft. 338 ft. 1.2 Ohms
2.75 A 76 ft. 121 ft. 193 ft. 307 ft. 1.09 Ohms
3 A 70 ft. 111 ft. 177 ft. 282 ft. 1 Ohm
Notes:
• Max Distance = distance from XPS to last appliance.
• This table is calculated at 50 degrees Centigrade. If you are installing in locations
that could be exposed to higher temperatures, refer to NEC Table 8, or contact
Simplex Sales Engineering.
• Distances are based on a 3 V drop, and take into account the worst-case panel
output voltage.
• If CI wire is used instead of housing cable in a fire rated enclosure, reduce wiring
distances by 38 feet for every 10 feet of potential exposure.
Continued on next page
Step 4. XPS Field Wiring, Continued
Class B NAC
Wiring Table
firealarmresources.com

13
The XPS provides three outputs for notification appliance circuits and four inputs for auxiliary
power circuits. This section describes all types of wiring from the XPS to 4100-compatible
appliances.
Review the following guidelines for NACs before you begin NAC field wiring.
• All wiring is 18 AWG (minimum) to 12 AWG (maximum).
• All wiring is supervised and power-limited.
• The maximum alarm current is 3 A per circuit. The supervisory current is 2.03 mA at
24 VDC.
• The nominal voltage rating is 24 VDC, 2 V p-p ripple (maximum).
• The total available current from the SPS or RPS is 9 A. Any current used for card power
by modules plugged into the PDI, as well as any auxiliary 24 VDC current, must be
deducted from the total 9 A available current.
• All wiring that leaves the building requires overvoltage protection. Install module
2081-9044 (3 A) or 2081-9028 (¼ A) inside a UL Listed electrical box wherever wire
enters or exits the building. A maximum of four 2081-9044 Modules may be connected
to one channel. When using the 2081-9044, the maximum alarm current is reduced to ¼
A for that part of the circuit downstream of the module.
• Terminal designations “+” and “-” are for the alarm state.
• Compatible appliances for NACs are:
- 4901-series Horn
- 4903-series A/V
- 4903-series S/V
- 4904-series V/O
• A maximum of 70 appliances can be supported per circuit.
Continued on next page
Step 4. XPS Field Wiring, Continued
Overview
Guidelines
firealarmresources.com

14
To connect the XPS to appliances using Class A wiring, read the following instructions and refer
to Figure 6, below.
1. Route wire between 12 and 18 AWG from the B+ and B- outputs on TB1 of the XPS to
the appropriate inputs on a peripheral notification appliance. Use NAC1, NAC2, or
NAC3.
2. Route wire from the first appliance to the next one. Repeat for each appliance.
3. Route wire from the last appliance to the A+ and A- inputs on the same NAC circuit of
TB1 of the XPS.
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Use the 733-894 End-Of-Line Harness from the “B+” to the “B–” terminals on any
unused circuits.
BB-AA- BB-AA- BB-AA-
Figure 6. Class A Wiring
Continued on next page
Step 4. XPS Field Wiring, Continued
Class A NAC Wiring
NAC 2 NAC 3
BLACK
RED
RED BLACK
XPS
NOTIFICATION
APPLIANCES
TB1
12 AWG to 18 AWG
Important: Conductors must test free of
all grounds.
firealarmresources.com

15
To connect the XPS to appliances using Class B wiring, read the following instructions and refer
to Figure 7, below.
1. Use NAC1, NAC2, or NAC3 to route 12 to 18 AWG wire from B+ and B- on the XPS to
the first appliance.
2. Route wire to the next appliance as shown in the figure. Repeat for each appliance.
3. Use a 10 K Ohm, ½ W resistor (733-894) for supervision at the end of the line.
4. Repeat steps 1 through 3 for each NAC output you want to use.
5. Use the 733-894 End-Of-Line Harness from the “B+” to the “B–” terminals on any
unused circuits.
BB-AA-BB-AA-BB-AA-
Figure 7. Class B Wiring
Continued on next page
Step 4. XPS Field Wiring, Continued
Class B NAC Wiring
XPS
NAC 2 NAC 3
BLACKRED
RED BLACK
RED
NOTIFICATION
APPLIANCES
TB1
12 AWG to 18 AWG
Important: Conductors must test free of
all grounds.
EOL resistor (733-894)
firealarmresources.com

16
The XPS can receive auxiliary power appliances via the dedicated auxiliary power tap (TB2). If
additional power is needed, any of the three NAC outputs can be used as auxiliary power inputs.
Figure 8, below, shows how the XPS should be wired for auxiliary power at any given terminal.
BB-AA-BB-AA-BB-AA-
AUXILIARY
POWER
AUXILIARY
POWER
AUXILIARY
POWER AUXILIARY
POWER
AUX POWER
0V 24V
Figure 8. Auxiliary Power Wiring
Step 4. XPS Field Wiring, Continued
Auxiliary Power
Wiring
TB1
XPS
TB2
Dedicated auxiliary
p
ower screw terminal
NAC points must be
reconfigured as
auxiliary power input
points in the
programmer
• All wiring is 18 AWG (minimum) to 12 AWG (maximum).
• All wiring is power-limited.
• Auxiliary power may be taken from the dedicated auxiliary power tap
or from an unused NAC.
• If auxiliary power is taken from NAC terminals, the NAC must be
configured as an auxiliary power point type in the 4100
Programmer.
• Programming may be required for dedicated auxiliary outputs.
• Remove end-of-line resistors from circuits used for auxiliary
power.
• External wiring is not supervised unless an end-of-line relay is
wired coil to auxiliary power, and Normally Open contacts are
monitored by a system power point. Relay current must be
considered as part of the load.
• All wiring that leaves the building requires overvoltage protection.
Install module 2081-9044 (3 A) or 2081-9028 (¼ A) inside a UL
Listed electrical box wherever wire enters or exits the building. A
maximum of four 2081-9044 Modules may be connected to one
channel. When using the 2081-9044, the maximum alarm current
is reduced to ¼ A for that part of the circuit downstream of the
module.
• All auxiliary power taps are rated at 2 A. The total current
available is 9 amps. This includes NAC, auxiliary, and card
power. Current used for card power by modules plugged into the
PDI, and an current from aux. 24 V, must be deducted from the 9
A available current.
• Voltage rating: 24 VDC (nominal), 2 V P-P ripple (maximum). The
following devices connect to 2 A aux power:
- 2088-series relays and door holders
- 2098-series four-wire smoke detectors
- 2190-series monitor and signal ZAMs
- 4090-series IDNet ZAMs
- 4098-series four-wire smoke detectors and duct detectors
- 2190-9039 Printer
- 4190-9050/9051 4-20 mA ZAMs
- 4603-9101 LCD Annunciator
• Resettable 24 V is obtained from any aux power point by
programming the point as type “resettable 24 V”. Refer to the
Programming Manual for details.
firealarmresources.com

17
The 4100-5115 Expansion NAC Module (XNAC) is an option board that provides three NACs in
addition to the three NACs already on the XPS. The XNAC plugs onto the XPS.
If you are not installing an XNAC, skip this section and continue on to “Step 6: Troubleshooting.”
The XNAC has three NACs, each rated at 3 A. As on the XPS, there is one status LED for each
NAC.
The XNAC mounts to the top of the XPS as shown in the instructions and Figure 9, below.
NAC1 NAC2 NAC3
BB-BB-BB-BB-BB-BB-
P1
P3
LED5
BATT
TBL
LED4
P2 TB2
0V
24V
LED6
COMMS
TBL
Figure 9. Mounting the XNAC
1. Insert plastic standoffs (202-078) and a metal standoff (202-077) to the XPS as shown in
Figure 9.
2. Plug J1 on the XNAC into P3 on the XPS using a header (166-549). The holes on the
edges of the XNAC should be aligned with the tops of the standoffs.
3. Secure the XNAC to the standoffs using four screws.
4. Connect the XNAC’s signal power harness to P1 on the XPS.
The XNAC uses the same wiring rules as TB1 on the XPS. Refer to “Step 4. XPS Field Wiring” to
wire the XNAC to notification appliances. Note that the XNAC cannot be used for auxiliary
power.
Step 5. Installing the XNAC
Overview
The XNAC
Mounting the XNAC
Wiring the XNAC
XPS
INSERT METAL STANDOFF
(202-077) HERE
INSERT PLASTIC STANDOFFS
(202-078) HERE
NAC1 NAC2 NAC3
BB-BB-BB-BB-BB-BB-
P3
LED5
BATT
TBL
J1
XNAC
XPS CONNECTOR
CONNECTS TO P1
ON XPS VI
A
166-549 HEADER
SIGNAL POWER HARNESS
CONNECTS TO P1 ON XPS
P3
NAC 6
NAC 7
NAC 8
P1
firealarmresources.com

574-772
Rev. A
This section describes the messages that may appear on the 4100 display when using the XPS.
Trouble messages appear on the left as titles, and possible causes are listed to the right in the text.
Voltage has fallen below an acceptable level. A problem may exist in the wiring, in the power
distribution module, or into dedicated AC power.
The battery is not connected or is depleted. The precise status of the battery is given by the SPS,
RPS, or XBC. These modules report “Low Battery.” This trouble is merely to indicate a wiring
problem to the XPS (blown fuse, not connected, etc.).
Either the XNAC card is missing even though the XPS was configured to have one, or there is an
unconfigured XNAC card physically installed.
This Trouble is active when a NAC-to-NAC short is detected. The NACs that are shorted are also
indicated. Any combination of NACs 1 through 6 can be miswired together. Up to 4 of these
miswiring conditions can be reported.
Step 6. Troubleshooting
Overview
AC Power Loss
Battery Not
Connected/
Battery Depleted
Expansion NAC
Card Configuration
Mismatch
NAC Miswired
Trouble
firealarmresources.com
Other manuals for 4100-5101
1
This manual suits for next models
3
Table of contents
Other Simplex Control Unit manuals

Simplex
Simplex 2050 User manual

Simplex
Simplex 4100-6069 User manual

Simplex
Simplex 4100 Series User manual

Simplex
Simplex TYCO 4905-9835 User manual

Simplex
Simplex 4100-6065 User manual

Simplex
Simplex MINIPLEX 4100ES Series User manual

Simplex
Simplex 4100 Series User manual

Simplex
Simplex 4090-9116 User manual

Simplex
Simplex Foundation Series User manual

Simplex
Simplex 2008 Series User manual