Simplex 4100 Series User manual

Cautions, warnings, and regulatory information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents
of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
EYE SAFETY HAZARD Under certain fibreoptic application conditions, the optical output of this device may exceed eye safety limits. Do
not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
FCC RULES AND REGULATIONS – PART 15. This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with
NFPA72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
NFPA 72® is a registered trademark of the National Fire Protection Association.
Introduction
This publication describes the installation procedure for the 4100-6014/4120-6014 and 4120-6078 Network Interface Cards (NIC) and the following
media modules:
• 4100-0144/4120-0144 Modem Media Card (non-4100U/4100ES only)
• 4100-6056 Wired Media Card (4100U/4100ES only)
4100-0142/4120-0142 Wired Media Card (non-4100U/4100ES only)
• 4100-6057 Fiber Media Card (4100U/4100ES only)
4100-0143/4120-0143 Fiber Media Card (non-4100U/4100ES only)
• 4100-6301 - 4120 SM-L Duplex Fiber Media Card
4100-6302 - 4120 SM-R Duplex Fiber Media Card
4100-6303 - 4120 MM-L Duplex Fiber Media Card
4100-6304 - 4120 MM-R Duplex Fiber Media Card
Related documentation
• Field Wiring Diagram for 4100 Power Limited (841-731)
• Field Wiring Diagram for 4100 Non Power Limited (841-995)
• 4100ES Fire Alarm System Installation Guide (574-848)
579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction
*0579182V*

Introduction to the 4100 NIC
The NIC is a slave card that uses the standard 4100 serial bus to communicate with the master. The NIC connects FACPs in a network, allowing
communication between each panel via fiber, modem, or twisted shielded pair wire in a Class X wiring configuration.
The NIC is designed to be connected in a point-to-point arrangement, so one wire fault does not cause the entire system to fail. The point-to-point
arrangement provides the most secure and fault- tolerant wiring possible.
Two types of media boards can be used with the NIC.
• The Fiber-Optic Media Card can be used for electrically noisy environments or for connecting externally to other buildings.
• Non-4100U/4100ES only: the Modem Media Card is typically used when a large transmission distance is required.
The Wired Media Card is used in all other types of applications.
Up to two media boards can be plugged into each NIC. The same NIC can use a combination of two types of media boards (for example, a NIC may
have a wired media card connected to port 1 and a fiber-optic media card connected to port 2).
page 2 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Illustration
Figure 1 shows the 4100-6014 and the 4100-6078 NICs.
Figure 1: 4100-6014 and 4100-6078 NICs
NIC LED indications
The 4100-6014 and the 4100-6078 NIC modules have the following LEDs:
LED1 (yellow). Illuminates when the NIC has not established a communications link with the 4100 master.
LED2 (red). Illuminates when a data '0' is received at the left port.
LED3 (green). Illuminates when a data '0' is transmitted at the left port.
LED4 (red). Illuminates when a data '0' is received at the right port.
LED5 (green). Illuminates when a data '0' is transmitted at the right port.
Figure 2, Figure 3 , Figure 4, and Figure 5 are illustrations of four motherboards (apart from the default CPU motherboard) that can be used with the
4100 NIC.
The 565-274 Master Motherboard holds two daughter cards: the 4100 master controller card and the 4100 NIC.
The 565-275 Class B Motherboard holds the 4100 NIC by itself.
The 566-227 4100U/4100ES Master Motherboard holds a CPU card and a NIC.
The 566-398 4100ES RUI+ master motherboard holds a CPU card and a NIC.
page 3 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Figure 2: UT Motherboard with City Connection (565-274)
Figure 3: Class B Motherboard (565-275)
NIC card LED indications
page 4 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Figure 4: 4100U/4100ES CPU Master Motherboard (566-227)
page 5 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Figure 5: RUI+ CPU master motherboard (566-938)
Media module illustrations
You can plug seven modules into the 4100-6014 and the 4100-6078 NICs:
• 4100-6301 - 4120 SM-L Duplex Fiber Media Card (566-1198)
• 4100-6302 - 4120 SM-R Duplex Fiber Media Card (566-1197)
• 4100-6303 - 4120 MM-L Duplex Fiber Media Card (566-1200)
• 4100-6304 - 4120 MM-R Duplex Fiber Media Card (566-1199)
• 4100-6057 Fiber-Optic Media Card (565-261, 566-376, or 746-109)
• 4100-6056 Wired Media Card (565-413)
• 4100-0144/ 4120-0144 Modem Media Card (565-279 or 566-338; non-4100U /4100ES only)
Each module is shown below.
page 6 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Figure 6: 4120 Duplex Fiber Media Cards, 4010-9819 and 4007-9814 Fiber-Optic Media Cards
page 7 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Figure 7: 4100-6056 Wired Media Card
Figure 8: 4100/4120-0144 Modem Media Card (Non-4100U/4100ES only)
page 8 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Specifications
Refer to the following table for electrical and environmental requirements for the 4100 NIC and media cards.
Table 1: Electrical and environmental specifications
Electrical specifications
NIC (565-516) Startup, no media cards: 8 VDC at 110 mA Nominal, no media cards: 20 to 32 VDC at 0 mA
NIC (566-793) Nominal, no media cards: 20 to 32 VDC at 46 mA
Modem Media Card
(566-279, 566-338)
5 VDC at 180 mA max.
Dual Fiber Media Card (746-109) Using 24 V power supply: 20 VDC at 140 mA max.
Using 5 V power supply: 5 VDC at 130 mA max.
Duplex Fiber Media Card
(566-1197, 566-1198, 566-1199,
566-1200)
Using 24 V power supply: 24 VDC at 55 mA max.
Using 5 V power supply: 5 VDC at 220 mA max.
Wired Media Card (565-413) 55 mA max at 24 VDC
Output Voltage: 4.75 V min to 5.25 V max.
Environmental specifications
Operating temperature 32 ° to 120 °F (0 ° to 49 °C)
Humidity 10% to 93% relative humidity at 90 °F (32 °C)
Dual fiber-optic specifications (746-109 only)
Fiber type Multi-mode
Interface ST Connector
Wavelength 850nm
50/125 um fiber
High setting: 17 dB
Medium setting: 11.6 dB
Low setting: 6.6 dB
Allowed losses
62.5 um fiber
High setting: 20.4 dB
Medium setting: 16dB
Low setting: 11 dB
The low power setting is preferred for all 62.5 um fiber links less than 11 dB and 50 um fiber links less than 6.6 dB. JW1 is used to adjust the link
power budget. If you encounter communication problems, ensure the fiber connections comply with ANSI/TIA/EIA 568-C.3 or later industry standard.
Table 2: Duplex fiber-optic specifications
Duplex fiber-optic specifications (566-1197, 566-1198, 566-1199, or 566-1200) only
Multi-mode Right: 566-1199, Left: 566-1200Fiber Type
Single-mode Right: 566-1197, Left: 566-1198
Interface SC Connector
Right Media (SM and MM) 1310 nm transmit; 1550 nm receiveWavelength
Left Media (SM and MM) 1550 nm transmit; 1310 nm receive
50/125 um fiber 18 dB/5 kmMulti-mode
62.5/125 um fiber 18 dB/5 km
Allowed losses / distances
Single-mode 9/125 um fiber 22 dB/25 km
If you encounter communication problems, ensure fiber connections comply with ANSI/TIA/EIA 568-C.3 or later industry standard.
Initial acceptance test requirements for fiber optic installations are as follows:
• An initial acceptance test of each fiber link shall be performed as stated in NFPA 72. A fiber link is defined as all fiber segments, including patch
cords, which create a fiber path from one fiber media board to another. The fiber lines shall be tested using an OTDR. The OTDR will measure
the attenuation of the fiber as well as indicate the presence and location of connectors and any defects in the link. The fiber infrastructure
shall be accepted for use only after it has been determined it meets or exceeds industry standard ANSI TIA/EIA 568-C.3 or later (Electronic
Industries Alliance/Telecommunications Industry Association, Optical Fiber Cabling Components Standard).
• OTDR Launch and Receive cables of appropriate length shall be used. If a single cable is used, each link shall be tested in both directions.
• Multi-mode fiber links shall be measured at 850 nm and 1300 nm.
• Single-mode fiber links shall be measured at 1310 nm and 1550 nm.
page 9 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Jumper settings
The NIC card, along with the fiber, modem, and wired media cards, all have jumpers that must be set.
Motherboard jumper settings
NIC-compatible jumper settings on CPU motherboards depend on which motherboards are used.
Motherboard 565-274:
• JW1 and JW2 must be installed.
• Jumper plugs P5-P8 must not be installed.
Motherboard 566-227:
P10: Port 1 settings.
P11: Port 2 settings.
• P10/P11 position 1 - 2: Network card (NIC) attached to the CPU motherboard (default).
• P10/P11 position 2 - 3: RS-232/2120 card attached to the CPU motherboard.
Motherboard 566-938:
P10: Port 1 settings.
P11: Port 2 settings.
• P10/P11 position 1 - 2: Network card (NIC) attached to CPU motherboard (default).
• P10/P11 position 2 - 3: RS-232/2120 card attached to CPU motherboard.
NIC address setting
Use SW2 to set the NIC card address.
NIC jumper settings
Set two shunt jumper ports on the NIC card: P3 and P4.
P3: Determines the NIC data transmission rate, 57.6 kbits/second or 9600 bits/second.
• Position 1 - 2 (the right two pins) or no pins jumpered: 57.6 kbits/second.
• Position 2 - 3 (the left two pins): 9600 bits/second.
P4: Determines the data protocol, 8-bit or 9-bit, that the NIC card is using.
• Position 1 - 2 (the right two pins) or no pins jumpered: 9-bit.
• Position 2 - 3 (the left two pins): 8-bit.
All settings are labeled on the card.
Wired media card jumper settings
P2: Tells the system which wire type to use.
• Positions 1 – 2, 5 – 6, and 7 – 8: 18 AWG shielded, twisted pair wiring.
• Remove all jumpers to specify 24 AWG twisted pair telephone cable wiring.
P3 and P4: Use to improve shorted line sensing with shorter communications lines.
• Present on Rev C (and later) of the Media Module (565-413).
• For 18 ga communications lines of 5 kft or less, or 24 ga communications lines of 2 kft or less, install P3 and P4 jumpers in position 2-3.
• For longer lines, install jumpers in position 1-2.
Important: When using the wired media card, the earth fault detection is performed on the left port only. Cut and remove R1 from the media card on
the right port.
Modem Media Card jumper settings
Non-4100U/4100ES only. P4 and P5 on the modem media card tell the system how the card is used.
P4: Sets the card up as a network media card or a standalone modem.
• Position 1 - 2 (required): Sets the card up as a network media card, a service modem, or a physical bridge.
• Position 2 - 3: Sets the card up as a stand-alone modem.
P5: Specifies which connector is used for data transmission.
• Position 1 - 2: Use for modem media board or stand-alone modem. It specifies that the transmission data comes from the 40-pin connector
(J1).
• Position 2 - 3: Use for service modem or physical bridge. Specifies that the transmission data comes from the 10-pin RS-232 connector (P1).
page 10 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Dual fiber media jumper settings (746-109 only)
Use JW1 to adjust the link power budget. If communication problems occur, ensure the fiber connections comply with ANSI/TIA/EIA 568-C.3 or later
industry standards. A low power setting is preferred for all 62.5um fiber links less than 11 dB, and 50 um fiber links less than 6.6dB.
Table 3: Dual fiber media jumper settings (746-109 only)
50/125 um fiber multi-mode 62.5/125 um fiber multi-mode
High setting: 17 dB High setting: 20.4 dB
Medium setting: 11.6 dB Medium setting: 16 dB
Low setting: 6.6 dB Low setting: 11 dB
Duplex fiber media diagnostics (566-1197, 566-1198, 566-1199, or 566-1200 only)
SW1 displays the diagnostics on the diagnostic LEDs. Press to display the type and thresholds reached.
• Hold for 3 seconds to toggle between the Normal and Advanced diagnostics mode.
• Hold for 6 seconds to clear the counters.
Note: If SW2-4 is set to advanced diagnostics, and if you press and hold SW1 for 3 seconds, the card does not toggle between the diagnostic modes.
The mode is set to advanced.
SW2 configures the diagnostics display and the offline test modes. Refer to 579-1233 for more information on 4120 Duplex Fiber Media Card
Diagnostics. Switch SW2 is a bank of four DIP switches. From left to right (see Figure 8), these switches are SW2-1 to SW2-4.
Figure 9: DIP switch SW2
Position Description ON OFF
1 Offline test mode Disable Enable
2 Fiber data loopback Disable Enable
3 Select normal/low thresholds to monitor diagnostic LEDs Normal Low
4 Select normal / advanced diagnostics Normal Advanced
Note: If either test mode (SW2-1 and/or SW2-2) is enabled, normal 4120 network traffic is disrupted.
Setting the NIC daughter card address
Switch SW2 on the 4100 NIC is a bank of eight dip switches. From left to right, see Figure 10, switches are SW2-1 through SW2-8. The purpose of these
switches is as follows:
• SW2-1. This switch sets the baud rate for the internal 4100 communications line running between the card and the 4100 CPU. Set this switch
to ON.
• SW2-2 through SW2-8. These switches set the card's address within the 4100 FACP. Refer to Figure 11 for a complete list of the switch
settings for all possible card addresses.
Note: You must set these switches to the value assigned to the card by the Programmer.
Figure 10: DIP switch SW2
page 11 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Figure 11: 4100-6014 and 4100-6078 Module Card addresses
page 12 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Mounting Media Cards to the NIC
The first step of the installation process is to identify the media cards that have to be connected to the NIC, and connect them properly.
Media Card Retainer
The media card retainer provided is required for compliance with California Administrative Code Chapter 6, Seismic Evaluation Procedures for
Hospital Buildings and is recommended for all installations. Do not discard the media card retainer.
Note: For cards that do not have retainers installed, or to order replacements for a broken retainer, use part number 650-1732. Two retainers per
card are required.
Figure 12: Media card retainer
Media board mounting
Refer to Figure 13 as you read the following instructions.
Connect P1 on the wired media card, or J1 on the modem or fiber media cards, to P5 (the left port) on the NIC. Verify the card clicks into the media
card retainer.
To connect a second media card to the same NIC, connect it as described above, but use P6 (the right port) on the NIC.
The 4100-6301 and the 4100-6303 Duplex Fiber Media Cards are left cards. Insert the cards in the corresponding network card left port (P5).
The 4100-6302 and the 4100-6304 Duplex Fiber Media cards are right card. Insert the cards in the corresponding network card right port (P6).
Note: Any two types of media cards can be connected to the same NIC.
Figure 13: Mounting the media card
page 13 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Installing motherboards into 2975-91xx Back Boxes (Non-4100U/4100ES)
Mount the NIC card to 2975-91xx Master Controller Bays (4100) or, for the 4100U/4100ES, mount the NIC card to 2975-94xx CPU Bays. This section
describes mounting into 4100 Master Controller Bays.
Installing into a 2975-91xx Master Controller Bay
Use the following guidelines when installing into a master controller bay.
1. If the 565-274 Master Motherboard is used, install it in the leftmost position of the bay. If the 565-274 Master Motherboard is not used, install the
CPU motherboard in the leftmost position of the bay.
2. Install the power supply in the rightmost position of the bay.
3. Install relay cards in the slots immediately to the left of the power supply. This is necessary to allow for the proper routing of non-power limited
wiring (120 VAC wiring connected to the relay card).
4. If used, install the Class B motherboard (565-275) to the left of the relay cards. If a physical bridge is used with the Class B motherboard, it must
be to the right of any motherboards using NICs. This allows for earth ground detection via the physical bridge.
Installing the motherboard
1. Position the motherboard.
a. 565-274 Master Motherboard: if it is not already installed, orient with the connector labeled J3 on the right and the header labeled P1 on
the left.
b. 565-275 Class B Motherboard: orient with the connector labeled J1 on the right and the header labeled P1 on the left.
2. 565-275 Class B Motherboard only: Slide the motherboard to the left until the pins are completely inserted in the connector of a previously
installed motherboard.
3. Secure the motherboard to the chassis with four torx screws.
Figure 14: Installing the motherboard into a 4100 Master Controller Bay
page 14 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Installing Motherboards into 2975-94xx Back Boxes (4100U/4100ES)
The NIC card can be mounted to either 2975-91xx Master Controller Bays (4100) or, for the 4100U/4100ES, 2975-94xx CPU Bays. This section
describes mounting into 4100U or 4100ES CPU Bays.
Installing into a 2975-94xx CPU Bay
Up to two motherboards may be installed with the system CPU in the CPU bay. In most cases, the NIC is used with the CPU motherboard. If
this is the case, you can skip this section. If you are installing an additional motherboard that uses the NIC, follow the directions below.
1. Orient the motherboard with the connector labeled J1 on the right and the header labeled P1 on the left.
2. Slide the motherboard to the right until the pins from P1 on the motherboard to the right are completely inserted in the motherboard’s J1
connector.
3. Attach four lockwashers and metal standoffs to the chassis, and secure the motherboard to the chassis using four #6 screws.
Figure 15: Installing the Motherboard into a 4100U/4100ES CPU Bay
page 15 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Installing the Daughter Card
Installing into a 2975-94xx CPU Bay
The 4100 NIC daughter card, shown in Figure 16, inserts into motherboards as follows:
• If you use the 565-274 Master Motherboard, insert the NIC daughter card into connector J1.
• If you use the 566-227 or 565-275 CPU Motherboard, insert the NIC daughter card into connector J2.
• If you use the 566-938 RUI+ CPU motherboard, insert the NIC daughter card into connector J6.
Figure 16: Installing the daughter card
page 16 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Wiring
The type of wiring used depends on the type of media cards being used in the system. The only time the motherboard terminals are used is when
wired media cards are plugged into the daughter card. Otherwise, modem and fiber connections are made straight to and from the media cards.
General Guidelines
Make sure these guidelines are accounted for before wiring:
• All wires must be 18 AWG, or as the local code dictates.
• Conductors must test free of all grounds.
• All wiring must be done using copper conductors only, unless noted otherwise.
• If shielded wire is used,
- The metallic continuity of the shield must be maintained throughout the entire cable length.
- The entire length of the cable must have a resistance greater than 1 Megohm to earth ground.
• Underground wiring must be free of all water.
• In areas of high lightning activity, or in areas that have large power surges, the 2081-9027 Transient Suppressor should be used on monitor
points.
• Wires must not be run through elevator shafts.
• Wires that run in plenum must be in conduit.
• Splicing is permitted. All spliced connections must either be soldered (resin-core solder), crimped in metal sleeves, or encapsulated with an
epoxy resin. When soldering or crimped metal sleeves are used, the junction must be insulated with a high-grade electrical tape that is as
sound as the original insulating jacket. Shield continuity must be maintained throughout.
• A system ground must be provided for earth detection and lightning protection devices. This connection must comply with approved earth
detection per NFPA780.
• Only system wiring can be run together in the same conduit.
Power-Limited Guidelines
Make sure these guidelines are accounted for before wiring for power-limited systems:
• Non-power limited field wiring (AC power, batteries, City connection) must be installed and routed in the shaded areas shown in Figure 17.
• Power-limited field wiring must be installed and routed in the non-shaded areas shown in Figure 17, with the exception of City wiring.
• Excess slack should be kept to a minimum inside the back box enclosure. The wiring should be neatly dressed and bundled together using the
wire ties provided with the equipment. Anchor power-limited wiring to tie points, as shown in Figure 17.
Figure 17: Power-limited wiring
• Tie the wiring located between bays to the internal wiring troughs, if applicable.
page 17 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

• When powering remote units or switching power through relay contacts, power for these circuits must be provided by a power-limited power
supply that listed for fire-protective signaling use. An EOL relay must be used to supervise the auxiliary power circuit.
• Auxiliary power only: Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit. In order to connect a
circuit using power-limited wiring, the devices being powered must all be addressable, or a UL Listed EOL relay must be used to supervise the
circuit. Refer to the figure below for wiring directions for the EOL relay.
Figure 18: EOL relay
NIC wiring guidelines
• Network nodes must be wired right to left port, regardless of the media type selected.
• Class X protection is achieved by wiring the nodes in a loop fashion. A single fault (except an Earth fault) will cause the network to reconfigure
for degraded Class X and Class B operation. A second fault (except an Earth fault) will result in the network dividing into two separate networks.
• Class B is achieved by wiring the nodes in a linear fashion. Class B networks are not fault-tolerant and a single fault (except an Earth fault) will
result in the network dividing into two separate networks.
• Earth fault detection is performed on the left port only. When a network Earth fault occurs, the trouble is only reported on the node whose left
port is connected to the span.
• All 18 AWG wiring used with 4100-6056 Wired Media Cards must be twisted shielded pair. All 24 AWG (telephone cable) used with 4100-6056
must be twisted pair. When shielded cable is used, the shield must be terminated to chassis Earth on the left port only.
• It is permissible to use mixed media in a network. For example, some spans may be “wired media” while others are optical fiber or telephone
modem.
• Each NIC has a jumper for selecting between network data rates of 57.6 kbps and 9.6kbps. All cards in the network must be set for the same
rate. (When modem media or physical bridging is used, the data rate must be set for 9.6 kbps).
• Each NIC has a jumper for selecting between 8-bit and 9-bit network protocols. All cards in the network must be set for the same network
protocol. (When modem media or physical bridging is used, the protocol must be set for 8-bit).
• All network wiring except the shield is supervised.
• When wiring leaves the building, 2081-9044 Overvoltage Protectors are required. One overvoltage protector is installed where wiring leaves
the building; another is installed where wiring enters the next building.
• Transient Suppressor 748-599 is required for each modem-to-telephone line connection.
page 18 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

Figure 19: Transient suppressor
Dual Fiber-Optic Wiring (746-109 only)
Connectors U1 (transmitter) and U2 (receiver) on the Dual Fiber-Optic Media Card are used to connect 4100-6014 and 4100-6078 NICs across parts of
a network.
The maximum distance between nodes when using fiber cable is dependent on the size of the cable. Table 4 lists the maximum cable lengths.
Note: ST connectors with long strain relief boots are to be used with the fiber optic cable.
Figure 20 shows how two network nodes are connected via fiber-optic cable.
Figure 20: Dual fiber wiring
Dual fiber-optic connection types (746-109 only)
Dual fiber-optic cable connections. The standard fiber optic that connections between the 4120 Network nodes uses two fiber optic cables: one
for transmit, and the other for receive. This connection allows for optimum communications distance.
The available communications distance is determined by the properties of the specific fiber cable used. Distances can be determined using the
information and examples shown below in Table 4.
Single Fiber-optic cable connections. For applications where a single fiber cable is available, or where use of a single cable is desired, using a model
4190-9010 Bi-Directional Coupler at each node combines the separate transmit and receive signals into a single path (refer to the requirements list).
This connection allows use of a single fiber cable, but it does reduce communications distance as indicated in the information and examples shown
below in Table 4 and Table 5.
page 19 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction

4190-9010 coupler requirements
The 4190-9010 Coupler (271-012) is used with the 565-261 Fiber-Optic Media Board, revision “C” or higher, the 566-376, or the 746-109. Two
4190-9010 Bi-Directional Couplers are required per connection, one at each node.
The 4190-9010 is equipped with type ST connectors. To make type ST to type ST connections, an ST to ST coupler, by others, is required. ST to ST
Couplers are available from:
Black Box, part # FO200
Fiber Instrument Sales, part # F1-8101
Newark Electronics, part # 95F2097
(or equivalent)
Figure 21: Coupler wiring
The available communications distance is determined by the properties of the specific fiber cable used, the overall link topology, and the
available power budget.
Table 4: Dual fiber-optic cable communications distance examples
Fiber Type 1* MIFL 2 Power margin Distance 3 Budget 3 Coupler/Splice Loss
50/125
numerical aperture = 0.2
3 dB/km 3 dB 15,000 ft (4.57 km) 17 dB
62.5/125
numerical aperture = 0.275
3.50 dB/km 3 dB 15,000 ft (4.57 km) 20.4 dB
0.75dB max for each mated pair
connection
0.30dB max for each fusion splice
* See notes at bottom of page
Table 5: Single fiber-optic cable communications distance examples using 4190-9010 Bi-Directional Couplers
Fiber Type 1 MIFL 2 Power margin Distance 3 Budget 3 4190-9010
Coupler Loss
ST to ST Coupler
Loss
50/125
numerical aperture = 0.2
3 dB/km 7,650 ft
(2.33 km)
3 dB
62.5/125
numerical aperture = 0.275
3.2 dB/km
2 dB
8,200 ft
(2.5 km)
21.4 dB 9.4 dB
2 dB
Notes:
1. Fiber Type: Cable specifications are for 50 or 62.5 micron core with 125 micron cladding, multi-mode graded index fiber. Wavelength = 850 nm.
2. MIFL: Maximum individual fiber loss. Numbers shown are for example reference only, refer to specific cable for exact specification.
3. Distance: The maximum distance between nodes is determined by the total loss from the transmitter to the associated receiver (fiber loss,
connector loss, splice loss and safety margin) or the maximum distance listed, whichever is smaller. Budget using 4190-9010 Bi-Directional
Coupler is the same with either size cable. The coupler input cables are 62.5/125 fiber which allows launch power to be the same.
4. Link Budget: Measure attenuation at wavelength 850nm.
5. Dual fiber optic distances are for 746-109, 565-261 and 565-376 fiber media modules. Single fiber-optic distances require use of 4190-9010 Bi-
Directional Couplers.
page 20 579-182 Rev. V
4100/4120-6014, 4100-6078 NICs and 4100/4120-Series Media Modules Installation Instruction
Other manuals for 4100 Series
9
This manual suits for next models
8
Table of contents
Other Simplex Control Unit manuals

Simplex
Simplex 4100-5101 User manual

Simplex
Simplex TYCO 4905-9835 User manual

Simplex
Simplex 2004 Series User manual

Simplex
Simplex 4001-9810 User manual

Simplex
Simplex 2050 User manual

Simplex
Simplex 4100-6069 User manual

Simplex
Simplex 4090-9116 User manual

Simplex
Simplex 2050 User manual

Simplex
Simplex 4100 Series User manual

Simplex
Simplex MINIPLEX 4100ES Series User manual