HGM8100N Genset Controller User Manual Page 8 of 66
3PERFORMANCE AND CHARACTERISTICS
HGM8110N: used for single automation systems, can control genset start/stop through remote start
signals.
HGM8120N: AMF (Auto Mains Failure), updates based on HGM8110N, moreover, has mains electric
quantity monitoring and mains/generator automatic transfer control function, especially for
automatic system composed by generator and mains.
Main characteristics are as below:
1) With ARM-based 32-bit SCM, highly integrated hardware, high reliability.
2) Vacuum fluorescent display (VFD) or LCD display (able to control heating according to the
environment temperature), selectable Chinese/English interface which can be chosen at the site,
making commissioning convenience for factory personnel.
3) LCD adopts hard screen acrylic material with good wear-resisting and scratch-resisting.
4) Silicone panel and pushbuttons can be used in extreme temperature environment.
5) RS485 communication interface enables “Three remote functions” (remote control, remote
measuring and remote communication) according to MODBUS protocol.
6) Ethernet monitoring can be realized via ETHERNET communication interface (need controller
with Ethernet interface).
7) Equipped with SMS (Short Message Service) function. When genset is alarming, controller can
send short messages via SMS automatically to max. 5 telephone numbers. Besides, generator
status can be controlled and checked using SMS.
8) Equipped with CANBUS port and can communicate with J1939 genset. Not only can monitor
frequently-used data (such as water temperature, oil pressure, speed, fuel consumption and so
on) of ECU machine, but also control starting up, shutdown, raising speed and speed droop via
CANBUS port (need controller with CANBUS interface).
9) Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems
with voltage 120/240V and frequency 50/60Hz.
10) Collects and shows 3-phase voltage, current, power parameter and frequency of generator or
mains.
Mains Generator
Line voltage (Uab, Ubc, and Uca) Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc) Phase voltage (Ua, Ub, and Uc)
Phase sequence Phase sequence
Frequency Hz Frequency Hz
Load
Current Ia, Ib, Ic A (unit)
Each phase and total active power P kW (unit)
Each phase and total reactive power Q Kvar (unit)
Each phase and total apparent power S kVA (unit)
Each phase and average power factor λ 1 (unit)
Accumulate total generator power W kWh, kVarh, kVAh (unit)
Earth current I A (unit)
11) For Mains, controller has over and under voltage, over and under frequency, loss of phase and
phase sequence wrong detection functions; for generator, controller has over and under voltage,
over and under frequency, loss of phase, phase sequence wrong, over and reverse power, over
current functions.
12) 3 fixed analog sensors (temperature, oil pressure and liquid level).