HGM9420N_HGM9420LT GENSET CONTROLLER USER MANUAL
HGM9420N_HGM9420LT Genset Controller 2019-12-10 Version 1.0 Page 18 of 112
4.4 AUTO START/STOP OPERATION
4.4.1 ILLUSTRATION
Press button and the indicator beside is illuminated, which means the genset is at Auto Start
Mode.
4.4.2 AUTOMATIC START SEQUENCE
a) HGM9420N_HGM9420LT start conditions:
Mains enabled: when mains is abnormal (over voltage, under voltage, over frequency, under frequency,
loss of phase, reverse phase sequence), controller enters "Mains Abnormal Delay", LCD mains status
line displays countdown. When mains abnormal delay is over, it enters "Start Delay"; or when remote
start (on load) input is active, it enters "Start Delay".
Mains disabled or Mains only displayed: when remote start (onload) input is active, it enters "Start
Delay".
b) ―Start Delay‖ countdown will be displayed on genset status line;
c) When start delay is over, preheating relay is energized (if configured), ‗preheat delay XX s‘
information will be displayed on status line;
d) After the above delay, the fuel relay is energized, and then the start relay is engaged. During the
‗start time‘, if the genset does not start, then fuel relay and start relay stops outputting, and enter
‗crank rest time‘, waiting for next crank;
e) Should the start continues beyond the set attempts, the controller issues ‗start failure‘and stops the
genset and at the same time alarm page on LCD displays ‗start failure alarm‘;
f) If it starts during the attempts, it enters ‗safety on time‘, and during this period Low Oil Pressure,
High Temperature, Under speed and Charge Alternator Failure alarms are all inactive; After ‗safety
on time‘, it enters ‗start idle delay‘(if configured);
g) During ‗start idle delay‘, under speed, under frequency, under voltage alarms are inhibited. When
this delay is over, ‗warming up delay‘ is initiated (if configured);
h) When synchronous transfer is disabled, mains abnormal start or remote start (onload) input is active,
and when warming up delay is over, if gen is normal, gen status indicator is illuminated; if gens
voltage, frequency meet the onload requirements, gen close relay outputs and genset takes the
load. Gen supply indicator is illuminated, and genset enters normal running status; if genset voltage
or frequency is not normal, controller issues alarm and shutdowns (LCD alarm page displays gen
alarm type);
i) When synchronous transfer is enabled, mains is normal and remote start (onload) input is active,
when warming up delay is over, if gen is normal, then gen status indicator is illuminated. Controller
issues close signal after waiting for genset and mains meeting the sync. requirement; after
controller detects gen close feedback, it immediately issues mains open signal, and genset takes
the load.
j) When synchronous transfer is enabled, mains abnormal start, and warming up delay is over, if gen
is normal, gen status indicator is illuminated; if genset voltage, frequency is up to the load
requirement, then gen close relay outputs, and genset takes the load. Gen supply indicator is
illuminated and genset enters normal running status.
NOTE: When Remote Start is applied to start (Off Load), the procedure is the same as above. Only when it is in