HAT820 Dual Power ATS Controller User Manual
HAT820 Dual Power ATS Controller 2019-05-25 Version 1.0 Page 5 of 52
3PERFORMANCE AND CHARACTERISTICS
——System type can be set as Mains-Power Generation, Power Generation-Mains, Mains-Mains,
Power Generation-Power Generation;
——4.3-inch large LCD Display of single color, 240x128 pixel with white backlight, multiple language
display (Simplified Chinese, Engligh, and Other), default language for Other is Traditional Chinese,
and tuch-button operation;
——Collect and display 2-way 3-phase voltages, frequency and phase sequence;
——Collect and display loading active power, reactive power, apparent power, power factor and
current;
——Independent over current warning and trip alarm functions for S1 and S2;
——NEL trip function;
——Display of accumulated active power, accumulated reactive power, accumulated close times,
accumulated automatic transfer times, and mains outage transfer times for S1 and S2;
——Display of continuous power supply time, accumulated power supply time for S1 and S2,
accumulated automatic transfer running time;
——For energy-accumulated switch, it has function of breaker close when switch PF (close is well
prepared) signal is active;
——Functions of over voltage, under voltage, over frequency, under frequency, over current, loss of
phase, and inverse phase sequence;
——Auto/Manual status switchover is set, and breaker close/open can be controlled manually in
manual mode;
——All parameters can be configured on site, and it applies password verification, which can prevent
non-professional mistake operation;
——Commissioning can be done on site manually to do start/stop operation of genset;
——Function of breaker re-close function;
——Close output can be pulse or continuous output;
——2-way N wire isolated design;
——Real time clock display, event log function with recording cyclical 200 data;
——Scheduled detecting start/scheduled not start function for genset; it can be set to run for once,
each month, or each week, and running with loading or not can also be set;
——It can control two gensets, realizing cyclical running, master running, and balanced time running;
——Wide range of DC power supply, which can bear max. 80V DC input transiently;
——AC power supply can be phase voltage (L, N), or wire voltage (L, L) with supply range: (90~576)V;
——Large space between AC input wire terminals, which can bear 625V voltage input;
——Loading end is live or not can be detected;
——2 ways of RS485 isolated communication ports are set, which has remote control, remote
communication, remote measurement, and remote regulation functions by ModBus-RTU
communication protocol; it can also remote control genset start, stop, breaker close and open
functions;
——Suitable for multiple AC system types (3-phase 4-line, 3-phase 3-line, 1-phase 2-line, 2-phase
3-line methods);
——Modular structure design, flame retarding ABS shell, pluggable connecting terminal, and
embedded installation method, with compact structure and convenient installation.