Thermo-chiller Series HRS
Note 1) It should have no condensation.
Note 2) If tap water is used, use water that conforms to Water Quality Standards of the
Japan Refrigeration and Air Conditioning Industry Association (JRA GL-02-1994
cooling water system - circulating type - make-up water).
Note 3) qAmbient temperature: 25°C, wCirculating fluid temperature: 20°C, eCirculating
fluid rated flow, rCirculating fluid: Tap water, tFacility water temperature: 25°C
Refer to the cooling capacity graph on pages 13 and 14 for details.
Note 4) Use a 15% ethylene glycol aqueous solution if operating in a place where the circu-
lating fluid temperature is 10°C or less.
Note 5) Outlet temperature when the circulating fluid flow is rated flow, and the circulating flu-
id outlet and return port are directly connected. Installation environment and the pow-
er supply are within specification range and stable.
Note 6)
The capacity at the thermo-chiller outlet when the circulating fluid temperature is 20°C.
Note 7) Required min. flow rate for cooling capacity or maintaining the temperature stability.
The specification of the cooling capacity and the temperature stability may not be
satisfied if the flow rate is lower than the rated flow. (In such a case, use a by-pass
piping set (sold separately).)
Note 8) Purchase an earth leakage breaker with current sensitivity of 30 mA separately.
(A product with an optional earth leakage breaker (option B) is also available.)
Note 9) Front: 1 m, height: 1 m, stable with no load, Other conditions →Note 3)
Note 10) Weight in the dry state without circulating fluids
Note 11)
Required flow rate when a load for the cooling capacity is applied at a circulating fluid tem-
perature of 20°C, and circulating fluid rated flow and facility water temperature of 25°C.
Note 12) It is not provided for HRS050/060.
Note 13)
If the product is used at altitude of 1000 m or higher, refer to “Operating Environment/
Storage Environment” (page 41) Item 14 “*For altitude of 1000 m or higher”.
How to Order
Specifications *There are different values from standard specifications. Refer to pages 23 to 25 for details.
018 W 20HRS
Water-cooled refrigeration
Cooling capacity
Pipe thread type
Power supply Note)
Note) UL Standards: Applicable to 60 Hz only
Note) UL Standards: Applicable to 60 Hz only
CE-, UL-compliant models
Note) UL Standards: Applicable to 60 Hz only
HRS030/060: Pending
Model CE UL
HRS012 V V
HRS018 V V
HRS024 V V
HRS030 — —
HRS050 V V
HRS060 — —
Model
HRS012-Wl-20 HRS018-Wl-20 HRS024-Wl-20 HRS030-Wl-20 HRS050-Wl-20 HRS060-Wl-20
Cooling method Water-cooled refrigeration
Refrigerant R407C (HFC) R410A (HFC)
Control method PID control
Ambient temperature/humidity Note 1)
Temperature: 5 to 40°C, High-temperature environment specifications (option): 5 to 45°C, Humidity: 30 to 70%
Circulating fluid system
Circulating fluid Note 2) Tap water, 15% ethylene glycol aqueous solution Note 4)
Set temperature range Note 1)
5 to 40
Cooling capacity Note 3) (50/60 Hz) W1100/1300 1700/1900 2100/2400 2600/3200 4700/5100 4900/5900
Heating capacity Note 3) (50/60 Hz) W 530/650 400/600 1000/1300
Temperature stability Note 5) °C±0.1
Pump
Rated flow Note 6) Note 7) (50/60 Hz)
L/min
7 (0.13 MPa)/7 (0.18 MPa)
23 (0.24 MPa)/28 (0.32 MPa) 23 (0.21 MPa)/28 (0.29 MPa)
Maximum flow rate (50/60 Hz)
L/min
27/29 34/40 31/42 29/38
Maximum pump head (50/60 Hz) m 14/19 50
Output W200 550
Tank capacity L Approx. 5
Port size Rc1/2
Fluid contact material Stainless steel, Copper (Heat exchanger brazing), Bronze, Alumina ceramic,
Carbon, PP, PE, POM, FKM, EPDM, PVC
Facility water system
Temperature range °C5 to 40
Pressure range
MPa
0.3 to 0.5
Required flow rate Note 11) (50/60 Hz)
L/min
8 12 14 15 16 17
Inlet-outlet pressure differential of facility water
MPa 0.3 or more
Port size Rc3/8
Fluid contact material Stainless steel, Copper (Heat exchanger brazing), Bronze, Synthetic rubber
Electrical system
Power supply Single-phase 200 to 230 VAC (50/60 Hz)
Allowable voltage range ±10%
Circuit protector A 10 20
Applicable earth leakage breaker capacity Note 8)
A10 20
Rated operating current A 4.6/5.1 4.7/5.2 5.1/5.9 5.2/6.0 7.6/10 7.6/10.4
Rated power consumption Note 3) (50/60 Hz)
kVA 0.9/1.0 0.9/1.0 1.0/1.2 1.0/1.2 1.5/2.0 1.5/2.1
Noise level Note 9) (50/60 Hz) dB 60/61 62/65 65/68 66/68
Accessories
Fitting (for drain outlet) 1 pc. Note 12), Input/output signal connector 1 pc., Power supply connector 1 pc. Note 12),
Operation manual (for installation/operation) 1, Quick manual (with a clear case) 1 Note 12),
Alarm code list sticker 1, Ferritic core (for communication) 1 pc.
Power supply cable should be ordered the option (sold separately) or prepared by the user.
Weight Note 10) kg 43 46 67
Cooling method
WWater-cooled refrigeration
Symbol Power supply
20 Single-phase 200 to 230 VAC (50/60 Hz)
Nil Rc
F
G (with PT-G conversion fitting set)
N
NPT
(
with PT-NPT conversion fitting set)
012
Cooling capacity 1100/1300 W (50/60 Hz)
018
Cooling capacity 1700/1900 W (50/60 Hz)
024
Cooling capacity 2100/2400 W (50/60 Hz)
030
Cooling capacity 2600/3200 W (50/60 Hz)
050
Cooling capacity 4700/5100 W (50/60 Hz)
060
Cooling capacity 4900/5900 W (50/60 Hz)
Option
¡When multiple options are combined, indicate symbols in
alphabetical order.
Note) The cooling capacity will decrease by about 300 W from
the value in the catalog.
Symbol
Option
Applicable model
Nil None
HRS012/018/024
030/050/060
BWith earth leakage breaker
JWith automatic water fill function
M
Applicable to DI water (deionized water) piping
T
High-pressure pump mounted Note)
HRS012/018/024/030
a