Implement diagnostic bits in the process data.
Diagnosis items
· Over current error
· Rated flow error
· Accumulated flow error
· Flow sensor failure
· Temperature sensor failure
· Internal product malfunction
Diagnosis items
· Rated flow error
· Above/Below the rated pressure range
· Above/Below the rated temperature range
·
Error (Over current, Outside of zero-clear range, Version does not match)
·
System error (Flow/Temperature sensor failure, Internal malfunction)
Process Data
Bit offset Item Note
0 OUT1 output 0: OFF 1: ON
1 OUT2 output 0: OFF 1: ON
8 Flow rate diagnosis 0: OFF 1: ON
14 Fixed output 0: OFF 1: ON
15 Error (Failure) 0: OFF 1: ON
16 to 31
Measured flow rate value
Signed 16 bit
Process Data
Bit offset Item Note
0
Accumulated flow SW1
0: OFF 1: ON
1
Accumulated flow SW2
0: OFF 1: ON
2 Flow rate SW1 0: OFF 1: ON
3 Flow rate SW2 0: OFF 1: ON
4 Temperature SW1 0: OFF 1: ON
5 Temperature SW2 0: OFF 1: ON
6 Pressure SW1 0: OFF 1: ON
7 Pressure SW2 0: OFF 1: ON
8 Flow rate unit 0: L 1: ft3
9 Flow rate criteria 0: STD 1: nor
10 Flow rate diagnosis 0: Normal
1: HHH
Bit offset Item Note
11
Temperature diagnosis
0: Normal 1: HHH/LLL
12
Pressure diagnosis
0: Normal 1: HHH/LLL
13 Fixed output
0: Normal output 1: Fixed output
14 Error 0: Normal 1: Abnormal
15 System error 0: Normal 1: Abnormal
16 to 31
Measured pressure value
Signed 16 bit
32 to 47
Measured temperature value
Signed 16 bit
48 to 63
Measured flow rate value
Signed 16 bit
64 to 79
Accumulated flow rate lower limit
Unsigned 32 bit
80 to 95
Accumulated flow rate upper limit
Bit offset 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Item Measured flow rate value (PD)
Bit offset 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Item Error
(Failure)
Fixed output
Reservation
Flow rate diagnosis
Reservation OUT2 OUT1
Switch output
Bit offset 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80
Item Accumulated flow rate upper limit (PD)
Bit offset 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64
Item Accumulated flow rate lower limit (PD)
Bit offset 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48
Item Measured flow rate value (PD)
Bit offset 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32
Item Measured temperature value (PD)
Bit offset 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Item Measured pressure value (PD)
Bit offset 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Item
System error
Error
Fixed output
Pressure diagnosis
Temperature diagnosis
Flow rate diagnosis
Flow rate criteria
Flow rate unit
Pressure 2 Pressure 1
Temperature 2 Temperature 1
Flow rate 2
Flow rate 1
Accumulated flow 2 Accumulated flow 1
The diagnostic bit in the cyclic process data makes it easy to find problems with the equipment.
It is possible to find problems with the equipment in real time using the cyclic (periodic)
data and to monitor such problems in detail with the noncyclic (aperiodic) data.
Application Example
M/C
M/C
M/C
Flow control for each branch line
Can be used for the flow control, etc.,
of the main line and branch lines
The instantaneous flow, set value, and
accumulated value can be checked at
the same time.
Main line flow control
3-Color Display Digital Flow Switch for Large Flow PF3AmH(-L) Series