7
NT 874 638 B
ISOM AS420
Mise en service
Avant la mise en service, il est indispensable de contrôler si le
branchement de l´ISOM est correct.
Caractéristiques techniques AS420
Coordination de l´isolement selon CEI 60664-1/CEI 60664-3
Tensionassignée..................................................................................................................... 250V
Qualitédiélectrique/degrédepollution ........................................................................ 2,5kV/III
Séparationsûre (isolationrenforcée)entre:
............................................................... (A1,A2)-(L1,L2,E,KE,T/R)-(11-12-14)-(21-22-24)
Essaidiélectriqueselon CEI61010-1...................................................................................2,21kV
Tension d´alimentation
AS420:
Tensiond´alimentationUs.................................................................. AC16...72V/DC9,6...94V
GammedefréquencesUs...................................................................................... 42...460Hz/DC
AS420:
Tensiond´alimentationUs...................................................................................AC/DC70...300V
GammedefréquencesUs........................................................................................ 42...460Hz,DC
Consommationpropre.......................................................................................................... ≤3VA
Réseau IT surveillé
TensionréseauUn........................................................................................................ AC0...300V
Fréquencenominalefn.................................................................................................. 42...460Hz
Valeurs de seuil
ValeurdeseuilRan1 (ALARM1) .....................................................................................1...200k
Ω
ValeurdeseuilRan2 (ALARM2) .....................................................................................1...200k
Ω
FonctionPreset:
Un≤72V:Ran1(ALARM1)/Ran2(ALARM2) ........................................................ 20k
Ω
/10k
Ω
Un>72V:Ran1(ALARM1)/Ran2(ALARM2) ........................................................ 46k
Ω
/23k
Ω
Toléranceduseuil(1...5k
Ω
)/(5...200k
Ω
) ................................................... ±0,5k
Ω /
±15%
Hystérèse(1...5k
Ω
)/(5...200k
Ω
).................................................................. +1k
Ω /
+25%
Temps de réponse
Tempsderéponsetan pourRF=0,5xRanetCe=1μF........................................................ ≤1s
Temporisationdedémarraget............................................................................................. 0...10s
Duréedefermetureton ......................................................................................................... 0...99s
Circuit de mesure
TensiondemesureUm............................................................................................................±12V
CourantdemesureIm(pourRF=0
Ω
).......................................................................... ≤200μA
RésistanceinterneDCRi..................................................................................................... ≥62k
Ω
ImpédanceZipour50Hz.................................................................................................... ≥60k
Ω
TensionDCmaxi.étrangèreUfg..................................................................................... ≤DC300V
CapacitédefuiteCe.............................................................................................................. ≤20μF
Affichage, mémoire
Affichage.......................................................................écranLC,multi fonctions,nonrétroéclairé
Zoned´affichage,valeurmesurée............................................................................. 1k
Ω
...1M
Ω
Erreurmaximaledefonctionnement (1...5k
Ω
) ............................................................ ±0,5k
Ω
Erreurmaximaledefonctionnement (5k
Ω
...1M
Ω
) ....................................................... ±15%
Motdepasse ..................................................................................................................off/0...999
Mémorisationdesdéfauts(relaisd´alarme) ....................................................................... on/off
Entrées
LongueurducâbletoucheTest-/Resetexterne ................................................................. ≤ 10m
Nombre et type
Nombre ........................................................................................................... 2(inverseursK1,K2)
Modedetravail .................................................................... courantderepos/ courantdetravail
Pour vérifier le branchement correct de l'appareil, il
estconseillé,avantlamiseenservicedel´installation,
de contrôler son bon fonctionnement au moyen
d´unevraiemiseàlaterre,lecaséchéantparuneré-
sistanceRFdevaleuradéquate.
Commissioning
Prior to commissioning, check proper connection of the
A-ISOMETER®.
Technical data AS420
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Ratedinsulationvoltage...........................................................................................................250V
Ratedimpulsevoltage/Pollutiondegree........................................................................2.5kV/III
Protectiveseparation(reinforcedinsulation)between:
..............................................................(A1,A2)-(L1,L2,E,KE,T/R)-(11,12,14)-(21,22,24)
Voltagetestacc.IEC61010-1 .............................................................................................. 2.21kV
Supply voltage
AS420:
SupplyvoltageUs................................................................................ AC16...72V/DC9.6...94V
FrequencyrangeUs................................................................................................42...460Hz/DC
AS420:
SupplyvoltageUs................................................................................................. AC/DC70...300V
FrequencyrangeUs................................................................................................. 42...460Hz,DC
Powerconsumption.............................................................................................................. ≤3VA
IT System being monitored
NominalsystemvoltageUn......................................................................................... AC0...300V
Nominalfrequencyfn..................................................................................................... 42...460Hz
Response values
ResponsevalueRan1(ALARM1)..............................................................................1k
Ω
...200k
Ω
ResponsevalueRan1(ALARM2)..............................................................................1k
Ω
...200k
Ω
Presetfunction:
Un≤72V:Ran1(ALARM1)/Ran2(ALARM2)........................................................ 20k
Ω
/10k
Ω
Un>72V:Ran1(ALARM1)/Ran2(ALARM2)........................................................ 46k
Ω
/23k
Ω
Operatingerror(1...5k
Ω
)/(5...200k
Ω
)........................................... ±0.5k
Ω /
±15%
Hysteresis(1...5k
Ω
)/(5...200k
Ω
) ....................................................................+1k
Ω /
+25%
Time response
Responsetime tanatRF=0,5xRanandCe=1μF...............................................................≤1s
Startingdelayt ......................................................................................................................0...10s
Responsedelayton ................................................................................................................0...99s
Measuring circuit
MeasuringvoltageUm............................................................................................................. ±12V
MeasuringcurrentIm(RF=0
Ω
).................................................................................. ≤200μA
Internald.c.resistanceRi.................................................................................................... ≥62k
Ω
InternalimpedanceZi(50Hz)........................................................................................... ≥60k
Ω
Admissibleextraneousd.c.voltageUfg......................................................................... ≤DC300V
SystemleakagecapacitanceCe........................................................................................... ≤20μF
Displays, memory
Display...................................................................... LCdisplay,multi-functional,non-illuminated
Displayrange,measuringvalue ................................................................................ 1k
Ω
...1M
Ω
Operatingerror(1...5k
Ω
) ................................................................................................±0.5k
Ω
Percentageoperatingerror(5k
Ω
...1M
Ω
) ........................................................................±15%
Password........................................................................................................................ off/0...999
Faultmemory(alarmrelay) ................................................................................................. on/off
Inputs
Cablelengthexternaltest/resetbutton.............................................................................. ≤10m
Switching elements
Numberof....................................................................................... 2(changeovercontactsK1,K2)
Operatingprinciple....................................................................... (N/Ooperation)(N/Coperation)
Electricalendurance............................................................................ 10000switchingoperations
Itisrecommendedtocarryoutafunctionaltestusing
agenuineearthfault,e.g.viaasuitableresistance!