ATySgM - 542933D - SOCOMEC
8EN
3. QUICK START
3.1. Quick Start ATySgM (2P)
quick start 40-160A (2P)
EN
ATyS gM
Automatic
Transfer Switching Equipment
Printing informations: 1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
Subject to change without notice.
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
nPackaging and contents are in good condition.
nThe product reference corresponds to the order.
nContents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
nThis product must always be installed and commissioned
by qualified and approved personnel.
nMaintenance and servicing operations should be
performed by trained and authorised personnel.
nDo not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
nAlways use an appropriate voltage detection device to
confirm the absence of voltage.
nEnsure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
nIn case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
nBridging bars and 125A or 160A.
nControl voltage transformer (400Vac -> 230Vac).
nVoltage sensine and power supply TAP.
nTerminal shrouds.
nAdditionnal aux contact block.
nPolycarbonate enclosure.
nPolycarbonate extension box.
nPower Connection Terminals.
nSealable cover.
STEP 1
Cabinet / Back
Plate Installation
STEP 3
CONTROL /
AUX POWER
terminal
connections
STEP 2
Connecting the
POWER section
STEP 4
CHECK
STEP 5
Programming
Installation and Commissioning STEP 6A
Automatic Operation
STEP 6C
Padlocking
STEP 6B
Emergency Manual
Operation
STEP 3
CONTROL / AUX POWER Terminals and wiring
Ensure that the product is in Manual
Mode (front cover open).
Slotted head 3mm 0,5 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 1011
2 4 6 8
135 7
2 4 6 8
1 3 5 7
207 208 209 210
63 64 73 74
6 mm /
Capacité de raccordement
0,236 "
# 20 to # 14 AWG
0,5 to 2,5 mm
0,5 to 1,5 mm2
2
# 20 to # 16 AWG
Slotted head 3 mm
3,97 lb-in 0,5 Nm
2 4 6 8
135 7
2 4 6 8
135 7
2 4 6 8
1 3 5 7
2 4 6 8
1 3 5 7
/
I1 I2 I3
O1 O2
207 208 209 210
63 64 73 74
/
I1 I2 I3
O1 O2
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
www.socomec.com
www.socomec.com/operating-instructions
To download, brochures, catalogues and technical manuals.
STEP 1
The ATyS M is delivered with
padlocking configured to the
O position.
To allow padlocking in all
positions (I - O - II), configure
the ATySM as follows before
installation. (Screw is located
at the back of the product).
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in 0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in 0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in 0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in 0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
2,2 lb-in 0,25 Nm
2 X
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in 0,25 Nm
2 X
Installation Padlocking configuration
Caution: Ensure that the product is installed on a flat rigid surface.
Recommended orientation
Recommended Ok Ok Ok Ok Ok
Posidriv PZ1
1 Nm
Tighten to avoid
movementonthe DINrail.
2x
2x
!
DIN RAIL
IEC 60715
MAX : 2
235
26
116
13
222
235
131,5
131,5
47
52 176
224
4 mounting brackets
6x M6 screw - 2,5 Nm
STEP 2
Power Terminal Connections
Source supply side
Hexagonal Metric
Allen size 4
5,0 Nm
It is essential to tighten all used
terminals, with cables and/or
bridging bars, before use.
Voltage taps provide 2x ≤ 1.5mm2connections.
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
Load side
bridging bar.
125A: 1309 2006
160A: 1309 2016
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
10 to
70 mm²
15mm
Type Terminal no. Status of
thecontact Description Output
characteristics
Recommended
connection
cross-section
Auxiliary contact
block
1309 1001
11/12/14 11 14
12 Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
21/22/24 21 24
22 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 01 04
02 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
Auxiliary contact
block
1309 1011
11/12/14 11 14
12
21 24
22
01 04
02
Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
21/22/24 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
Type Terminal no. Application Status of the
contact Description Output
characteristics
Recommended
connection
cross-section
Inputs I1: 207 / 208 Network/Network With priority
Dry potential free
contact
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
Without priority
Network-Genset. Automatic retransfer
Manual Retransfer
I1: 207 / 209 Network/Network Source priority 1
Dry potential free
contact
Source priority 2
Network-Genset. Stop the test on load
Test on load
I3: 207 / 210 Network-Network or
Network-Generating
set
AUTO mode Dry potential free
contact
Automatic mode inhibition
Outputs O1: 63 / 64 Network-Network or
Network-Generating
set
Product not available :
- Manual mode
- Command default
- Electronic default
- No source
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Product available
O2: 73 / 74 Network-Genset.
No start command genset
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Generating set starting
Pozidriv PZ2 - 1 Nm
Use 20mm
screws for
1 module
Use 35mm
screws for
2 modules
!
Auxiliary contacts:
Fitting of auxiliary contacts:
1309 1001 or 1309 1011
To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one NO/
NC changeover contact for each position (I-0-II). To install use the long screws supplied with the module.
OKOK
OKOK
Allen size 4
Hexagonal Metric
44.1 lb-in 5,0 Nm
15 mm / 0,59 "
# 8 to # 00 AWG
10 to 70 mm2
10 to 70 mm2*
# 8 to # 00 AWG
!X4
OKOK
OKOK
Allen size 4
Hexagonal Metric
44.1 lb-in 5,0 Nm
15 mm / 0,59 "
# 8 to # 00 AWG
10 to 70 mm2
10 to 70 mm2*
# 8 to # 00 AWG