542 932 B - 06/14 - EN
QUICK START 
EN
ATyS gM
Automatic
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
■ Packaging and contents are in good condition.
■ The product reference corresponds to the order.
■ Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
■This product must always be installed and commissioned
by qualified and approved personnel.
■Maintenance and servicing operations should be
performed by trained and authorised personnel.
■Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
■ Always use an appropriate voltage detection device to
confirm the absence of voltage.
■ Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
■ In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
■ Bridging bars and 125A or 160A.
■ Control voltage transformer (400Vac -> 230Vac).
■ Voltage sensine and power supply TAP.
■ Terminal shrouds.
■ Additionnal aux contact block.
■ Polycarbonate enclosure.
■ Polycarbonate extension box.
■ Power Connection Terminals.
■ Sealable cover.
Printing informations: 1 color Black. White paper 90g/m2.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
Subject to change without notice.
STEP 1
Cabinet / Back
Plate Installation
STEP 3
CONTROL /
AUX POWER
terminal
connections
STEP 2
Connecting the
POWER section
STEP 4
CHECK
STEP 5
Programming
Installation and Commissioning STEP 6A
Automatic Operation
STEP 6C
Padlocking
STEP 6B
Emergency Manual
Operation
STEP 3
CONTROL / AUX POWER Terminals and wiring
Type Terminal no. Status of
 Description Output
characteristics
Recommended
connection
cross-section
Auxiliary contact
block
1309 0001
11/12/14 11 14
12 Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
21/22/24 21 24
22 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 01 04
02 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
Auxiliary contact
block
1309 0011
11/12/14 11 14
12
21 24
22
01 04
02
Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
21/22/24 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
207 208 209 210
63 64 73 74
2 4 6 8
135 7
2 4 6 8
135 7
2468
1357
2468
1357
/
I1 I2 I3
O1 O2
LOAD
Type Terminal no. Application Status of the
contact Description Output
characteristics
Recommended
connection
cross-section
Inputs I1: 207 / 208 Network/Network With priority
Dry potential free
contact
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
Without priority
Network-Genset. Automatic retransfer
Manual Retransfer
I1: 207 / 209 Network/Network Source priority 1
Dry potential free
contact
Source priority 2
Network-Genset. Stop the test on load
Test on load
I3: 207 / 210 Network-Network or
Network-Generating
set
AUTO mode
Dry potential free
contact
Automatic mode inhibition
Outputs O1: 63 / 64 Network-Network or
Network-Generating
set
Product not available :
- Manual mode
- Command default
- Electronic default
- No source
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Product available
O2: 73 / 74 Network-Genset.
No start command genset
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Generating set starting
Ensure that the product is in
Manual Mode (front cover
open).
230/127V~
3ph 4wires
230/127V~
3ph 3wires
Slotted head 3mm 0,5 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 0001
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 0011
Pozidriv PZ2 - 1 Nm
Use 20mm
screws for
1 module
U
s
1
m
r
se 20
m
c
rews
mo
du
Us
sc
1
Use 35mm
screws for
2 modules
!
Auxiliary contacts:
Fitting of auxiliary contacts:
1309 0001 or 1309 0011
To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one NO/
NC changeover contact for each position (I-0-II). To install use the long screws supplied with the module.
www.socomec.com
www.socomec.com/en/atys-g-m
To download, brochures, catalogues and technical manuals.
STEP 1
The ATyS M is delivered with
padlocking configured to the
O position.
To allow padlocking in all
positions (I - O - II), configure

installation. (Screw is located
at the back of the product).
STEP 3
Posidriv PZ2
2,2 lb-in 0,25 Nm
Posidriv PZ2
2
Posidriv PZ2
Posidriv PZ2
Installation Padlocking configuration
Caution: Ensure that the product is installed on a flat rigid surface.
53
46
73,5
45
340
326
131,5
131,5
52 104 176
47
Recommended orientation
Recommended Ok Ok Ok Ok Ok
Posidriv PZ1
1 Nm
Tighten to avoid

DIN RAIL
IEC 60715
6 mounting brackets
6x M6 screw - 2,5 Nm
2x
2x
STEP 2
Power Terminal Connections
Source supply side
Hexagonal Metric
Allen size 4
5,0 Nm
It is essential to tighten


WG
m2
m2*
WG
!
X8
!""#$%&'
2
connections.
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
Load side
bridging bar.
125A: 1309 4006
160A: 1309 4016
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
10 to
70 mm²
15mm
MAX : 2
340
26
116
245
143
350
18
13
324
!
Step 1
Step 2
Step 3
FT
STEP 5
Programming
Check
STEP 6A
Automatic operation
Close the front cover as shown to put the
product into automatic mode.
STEP 4
Whilst in manual mode, check the
wiring and if ok power up the
product.
STEP 6C
Padlocking mode
*In order to padlock put the product in
manual mode.
*
Pull the locking mechanism and insert
a padlock as shown.
*As standard padlocking in the 0 position.
Configurable to I-0-II (see step 1).
STEP 6B
Manual operation
*Open the front cover as shown to put
into manual mode.
*
Use the handle situated in the front
panel under the cover to operate the
transfer switch.
*
Check the changeover switch position
on the indicator before operating.
To simplify operation
use the handle with the
extension provided. (Max 8 Nm)
90º 90º
Extension
1x 4-8 mm
The LED signalling and operation is only active when the product supply is available.
To set the dip switches, it is necessary to open the Auto/Manual cover.
Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the defined thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
Source LED ON LED OFF LED blinking
Source 1
available
Source 1
missing or
out of
range
- a timer is
counting
down
- test mode
Source 2
available
Source 2
missing or
out of
range
- a timer is
counting
down
Source availability LED
*E: No stop in O position
*F: 2s stop in O position
Stop in 0 position: E-F
*C: 50 Hz
*D: 60 Hz
Frequency: C-D
*A: 3P
*B: 1P
Type of network: A-B
*G: Network - Genset
*H: Network - Network
Type of application: G-H
HYST: 20 %6U/F
6U: 5-20%
6F: 3-10%
Dip switch settings Led info
A
Source voltage
supply configuration
B
Loss of priority source timer
127/230 Vac version 230/400 Vac version
Un (P-P):
208-240 Vac
Un (P-N):
120-138 Vac
Un (P-P):
380-420 Vac
Un (P-N):
220-240 Vac
FT: 0-30 sec.
U/F [HYST]
[HYST]
RT: 0-30 min.
U/F
Timer settings
C D
Fault reset

LED ON LED OFF LED blinking
Fault Product OK Wait
Auto mode Manual
mode
Manual
retransfer
Fault and state of the product Leds
RT

Other manuals for ATyS g M

3

Other socomec Switch manuals

socomec INOSYS LBS Series User manual

socomec

socomec INOSYS LBS Series User manual

socomec ATyS 3S User manual

socomec

socomec ATyS 3S User manual

socomec ATyS User manual

socomec

socomec ATyS User manual

socomec ATyS s User manual

socomec

socomec ATyS s User manual

socomec ATyS d H User manual

socomec

socomec ATyS d H User manual

socomec SIRCO PV 600A User manual

socomec

socomec SIRCO PV 600A User manual

socomec COMO CS 25A User manual

socomec

socomec COMO CS 25A User manual

socomec ATyS g M User manual

socomec

socomec ATyS g M User manual

socomec ATyS FT User manual

socomec

socomec ATyS FT User manual

socomec ATyS p User manual

socomec

socomec ATyS p User manual

socomec ATyS Series User manual

socomec

socomec ATyS Series User manual

socomec SIRCO 100A User manual

socomec

socomec SIRCO 100A User manual

socomec ATyS g M User manual

socomec

socomec ATyS g M User manual

socomec STATYS XS 16A User manual

socomec

socomec STATYS XS 16A User manual

socomec Sirco MV 100 User manual

socomec

socomec Sirco MV 100 User manual

socomec ATyS d H User manual

socomec

socomec ATyS d H User manual

socomec ATyS d M User manual

socomec

socomec ATyS d M User manual

socomec ATyS User manual

socomec

socomec ATyS User manual

socomec SIRCOVER 100A User manual

socomec

socomec SIRCOVER 100A User manual

socomec Sirco MV 100 User manual

socomec

socomec Sirco MV 100 User manual

socomec 400A User manual

socomec

socomec 400A User manual

socomec 16A User manual

socomec

socomec 16A User manual

socomec ATyS t User manual

socomec

socomec ATyS t User manual

socomec ATyS p User manual

socomec

socomec ATyS p User manual

Popular Switch manuals by other brands

Brocade Communications Systems AM866A - StorageWorks 8/8 Base SAN Switch Administrator's guide

Brocade Communications Systems

Brocade Communications Systems AM866A - StorageWorks 8/8 Base SAN Switch Administrator's guide

Brocade Communications Systems A7533A - Brocade 4Gb SAN Switch Base Reference

Brocade Communications Systems

Brocade Communications Systems A7533A - Brocade 4Gb SAN Switch Base Reference

Keysight U7108 Series Operating and service manual

Keysight

Keysight U7108 Series Operating and service manual

Z-Wave TZ67G instruction manual

Z-Wave

Z-Wave TZ67G instruction manual

Pepperl+Fuchs Vibracon LVL-A7 manual

Pepperl+Fuchs

Pepperl+Fuchs Vibracon LVL-A7 manual

KELCO E30 Programming instructions

KELCO

KELCO E30 Programming instructions

Emos P5729T manual

Emos

Emos P5729T manual

Niko 05-060-01 manual

Niko

Niko 05-060-01 manual

Digitus DS-12851 user manual

Digitus

Digitus DS-12851 user manual

Crestron CLW-LSWEX-1GD Installation and operation guide

Crestron

Crestron CLW-LSWEX-1GD Installation and operation guide

Network Technologies KEEMUX-P2 Installation and operation manual

Network Technologies

Network Technologies KEEMUX-P2 Installation and operation manual

TRENDnet TU-400E Quick installation guide

TRENDnet

TRENDnet TU-400E Quick installation guide

LEGRAND 0 883 26 quick start guide

LEGRAND

LEGRAND 0 883 26 quick start guide

TP-Link JetStream TL-SL5428E reference guide

TP-Link

TP-Link JetStream TL-SL5428E reference guide

sprecher + schuh L11-NU600-1753 installation instructions

sprecher + schuh

sprecher + schuh L11-NU600-1753 installation instructions

Cablexpert DSW-HDMI-33 user manual

Cablexpert

Cablexpert DSW-HDMI-33 user manual

Leonton EG5-0501-SFP Series user manual

Leonton

Leonton EG5-0501-SFP Series user manual

iNels RFSA-61M installation manual

iNels

iNels RFSA-61M installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.