QUICK START
EN
ATyS tM
Automatic
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
■ Packaging and contents are in good condition.
■ The product reference corresponds to the order.
■ Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension rod
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
■This product must always be installed and commissioned
by qualified and approved personnel.
■Maintenance and servicing operations should be
performed by trained and authorised personnel.
■Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
■ Always use an appropriate voltage detection device to
confirm the absence of voltage.
■ Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
■ In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
■ Bridging bars 125A or 160A.
■ Control voltage transformer (400Vac -> 230Vac).
■ Voltage sensing and power supply tap.
■ Terminal shrouds.
■ Auxilliary contact blocks.
■ Polycarbonate enclosure.
■ Polycarbonate extension box.
■ Power Connection Terminals.
■ Sealable cover.
Printing informations: 1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
Sub
ect to chan
e without notice.
STEP 1
Cabinet / Back
Plate Installation
STEP 3
CONTROL /
AUX POWER
terminal
connections
STEP 2
Connecting the
POWER section
STEP 4
CHECK
STEP 5
Programming
Installation and Commissioning STEP 6A
Automatic Operation
STEP 6C
Padlocking
STEP 6B
Emergency Manual
Operation
STEP 3
STEP 6A
Check
Automatic
operation
STEP 5
Programming
CO
■Auto conf. of the network voltage and frequency.
1.Put dipswitch A-B to
position B. (All Led's
should be blinking).
2. When the LED’s
become a steady light
ON, configuration of
the network is ready.
3. Put dipswitch A-B
back to A.
■Set dip switches C-D, E-F, G-H ■
Close the front cover as
shown to put the product
into automatic mode.
HYST: 20 % of 6U/F settings
E: No stop in O position
F: 2s stop in 0 position
G: With priority
H: Without priority
STEP 4
Whilst in manual mode, check
the wiring and if ok power up
the product.
A: Ready
B: Auto Conf
(Auto-configuration)
Setting mode A-B
Thresholds C-D
Stop in 0 position E-F
Priority G-H
STEP 6B
Manual operation
Open the front cover as
shown to put into manual
mode.
Use the handle situated in
the front panel under the cover to operate the
transfer switch.
Check the changeover switch position on the
indicator before operating.
To simplify operation
use the handle with the
extension provided. (Max 8 Nm)
90º 90º
Extension
2 4 6 8
135 7
2 4
13
2468
1357
24
13
LOAD
www.socomec.com
www.socomec.com/en/atys-t-m
To download, brochures, catalogues and technical manuals.
STEP 6C
Padlocking mode
1x 4-8 mm
In order to padlock put the
product in manual mode.
Pull the locking mecha-
nism and insert a padlock
as shown.
As standard padlocking in the 0 position.
Configurable to I-0-II (see step 1).