SOMMY SF Series User manual

SF Series Intelligent Sensor Indicator Manual
KKSFE02-A0-1
Features :
⊙ Dual lines LED display , upper line shows the measure value ,
lower line display measure units.
⊙ Two alarm output
⊙Universal linear signal and thermocouple signal input
1. Model Illustration
⊙
Easy to operate
0:Without alarm 2:Two alarm
4:48W×48H 6:48W×96H 7:72W×72H 8:96W×48H 9:96W×96H
80:160W×80H(should order) 16:80W×160H(should order)
□
SF
B:DC 24V auxiliary power supply A:DC 12V auxiliary power supply(should order)
Blank:Without auxiliary power supply
□□□
R:Relay alarm output A:Without alarm
For your safety, please read the below content carefully before you use the meter !
Safe Caution
Please comply with the below important points:
Warning An accident may happen if the operation does not comply with the instruction.
Notice An operation that does not comply with the instruction may lead to product damage.
The instruction of the symbol in the manual is as below.
An accident danger may happen in a special condition.
Warning
1. A safty protection equipment must be installed or please contact with us for the relative information if the
product is used under the circumstance such as nuclear control, medical treatment equipment, automobile,
train, airplane, aviation, equipment, etc. Otherwise, it may cause serious loss, fire or person injury.
2. A panel must be installed, otherwise it may cause creepage (leakage).
3. Do not touch wire connectors when the power is on, otherwise you may get an electric shock.
4. Do not dismantle or modify the product. If you have to do so, please contact with us first. Otherwise it may
cause electric shock and fire.
5. Please check the connection number while you connect the power supply wire or input signal, otherwise it may
cause fire.
1. This product cannot be used outdoors. Otherwise the working life of the product will become shorter, or an electric
shock accident may happen.
2. When you connect wire to the power input connectors or signal input connectors, the moment of the No.20 AWG
(0.50 mm2) screw tweaked to the connector is 0.74n.m - 0.9n.m. Otherwise the connectors may be damaged or get fire.
3. Please comply with the rated specification. Otherwise it may cause electric shock or fire, and damage the product.
4. Do not use water or oil base cleaner to clean the product. Otherwise it may cause electric shock or fire.
and damage the product.
5. This product should be avoid working under the circumstance that is flammable, explosive, moist, under sunshine, heat
radiation and vibration. Otherwise it may cause explosion.
6. In this unit it must not have dust or deposit, otherwise it may cause fire or mechanical malfunction.
7. Do not use gasoline, chemical solvent to clean the cover of the product because such solvent can damage it. Please use
some soft cloth with water or alcohol to clean the plastic cover.
Caution
Please read the manual carefully before you use the meter
□
T: temperature sensor signal input , Blank :Voltage/ampere input

4.Panel Indication
2.Ordering Model
Note①:other auxiliary voltage need to be ordered.
Note②:Ex-factory default input signal is 0-10V,if changed to current input from voltage input,skipping the pin on of software as the drawing below.
Ampere Input
Voltage Input
12345
678910
Short connect 3-8、5-10(use the Pin cap ).
mA mAV VmV/RTD
12345
678910
Short connect 2-7、4-9.
mA mAV VmV/RTD
3.Main Technical Parameter
<30mA(220VAC)
0~50℃
45~85%RH
SF4: AC/DC 100~240V SF7/SF8:AC 110/220V±10% SF6/SF80:AC 220V±10%
±0.5%F.S
Ambient temperature
Ambient humidity
Measuring Accuracy
Alarm Output
Total Current
Power Supply
Auxiliary Voltage
Relay 1 output capacity: AC 1A/250V Relay 2 output capacity: AC 3A/250V
24V 30mA (12V auxiliary voltage can be specially ordered)
6.Operation Sequence
℃
cm
Mmm kg gmg Mpa pa ba Mba NWKW RPM Hz KHz mV VKV mA AKA ΩKΩ F
14
35 6 78910 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
2
No.
Symbol
Unit
Note①:Short-time press means press within 1s. Long-time press means press longer than 3s.
Note②:Unit symbol table
KKSFE02-A0-2
Alarm
Input signal
DC 0~10V , 4~20mA,
Auxiliary power supply
DC 24V/30mA
Model
DC 0~5V , 0~20mA
TC/RTD,0~50mV,0~400Ω
DC 0~10V , 4~20mA,
DC 0~5V , 0~20mA
TC/RTD,0~50mV,0~400Ω
No Alarm
Two Alarm Output
No Alarm
Two Alarm Output
Without
①
DC 24V/30mA ①
Without
SF A0
SF A0 T
SF R2B
SF R2B T
AL1 alarm indicate light
AL2 alarm indicate light
Decrease key
Increase key
SET function key
Measured value display
8 8
AL1
AL2
SF8 DIGITAL METER
Unit display
Parameter modification key
(1)SET key: After power on, long-time press SET key to enter into setting MENU; under the state of modifying the unit or value, press SET to confirm after modifying.
(2)“ ”key:At normal state or setting state menu,short-time press to activate parameter value,then the SV parameter value will flash and enter into modifying
state, at this state, Press to realize the modifying of thousand flash hundred flash ten flash unit flash cyclic shift.
→
→
→→
▲
▲
▲
(3)“ ”key:At the modifying state,short time press this key to increase the flashing digit.
(4)“ ”key:At the modifying state,short time press this key to increase the flashing digit.
▲
▲
→
→
LCK=33
LCK=33
→
SET
→
SET
→
SET
→
SET
SET
·
AL1
·
AL2
SET
SET
SET
→
SET
→→
→
→→
→
SET
→
SET
→
SET
→
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
SET
·
AL1
·
AL2
SET
SET
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
AL1
AL2
▲
▲
▲
▲
▲
▲
SET
→
AL1
AL2
AL1
AL2
SET
▲
Power On
long press Set
Alarm 1
Alarm 1 mode
Alarm 1 Hysteresis
Alarm 2
Decimal point
Selection
Filter Constant
Measured value
Amendment
Alarm 2 Hysteresis
Alarm 2 mode
Input signal
selection
Measure range low
limit
Measure range
high limit
Password lock
low signal excision
value
System Reserved
System Reserved
Value before reset
Display method
selection

KKSFE02-A0-3
7. Setting menu
AL1 FL~FH 200
0-1000 1
HY1
AD1
AL2
HY2
AD2
PS
FT
DP
FL
FH
HH/HL
FL~FH 600
HH
0~1000
HH/HL
-1000~1000
1-250
0-3
1
HH
0
20
0/-20
0
1000/1300
LCK 0
Refer to the Input Signal Table
INP
Refer to the Input Signal Table
/
Menu Function name Description Setting range Initial Value
#1 Alarm Value
#1 Alarm Mode
#1 Alarm Hysteresis
#2 Alarm Value
#2 Alarm Mode
#2 Alarm Hysteresis
Modified value
Filter Constant
Decimal point
selection
Display lower limit
Display upper limit
Menu lock password
#1 Alarm Value Setting
#2 Alarm Value Setting
HH: Alarm 1 upper limit HL: Alarm 1 lower limit
#2 Alarm Hysteresis
Measured value modifying
Digital filter for input signal
Decimal point setting
Display lower limit
Display upper limit
#1 Alarm Hysteresis
HH: Alarm 2 upper limit HL: Alarm 2 lower limit
LCK=0,lock unit,LCK=10,lock menu,LCK=33,into advanced menu
Input Signal Choice
SCUT Small signal excision
value
It works when o_SL=2,please refer to description in o_SL to see
the specific function -1999~3999 0
o_SL
Display methods
choice
When o_SL=0,displayed value is less than FL value,it displays
FL value,if displayed value is over FH, it displays FH.
When o_SL=1,display value exceed the limitsof FL、FH (No
exceeding of -1999~4000), exceeded range can still be displayed.
When o_SL=2,display value exceed the limits of FL、FH (No
exceeding of -1999~4000), exceeded range can still be displayed.
if the displayed value is less than SCUT, it will display the lowest
value of FL and SCUT
0~2
0
PSb Reset value
Long-press SET+ ,clear the displayed value to reset,the value
will be reserved in PSb,if you need to reset the value,revise the
PSb to 0.
▲
-1999~4000 0
0
0
KK
CAL
System Reserved
System Reserved
0~9999
Refer to the Input Signal Table
8. Mounting Size
_
0
~
10V
1-1999
~
4000
4
~
20
mA
0
~
5V
1
~
5V
0
~
20
mA
1
1
1
1
1
1
-1999
~
4000
-1999
~
4000
-1999
~
4000
-1999
~
4000
-1999
~
4000
-1999
~
4000
Code Input Type Measuring Range Resolution Accuracy Input Resistance
K
J
E
T
S
PT100
CU50
CU100
0
~
50mV
0
~
400Ω
-20~1300℃
-20~1000℃
-20~600℃
-20~400℃
-20~1700℃
-199.9~610.0℃
-50.0~150.0℃
-50.0~150.0℃
1℃
1℃
1℃
1℃
1℃
0.1℃
0.1℃
0.1℃
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
0.5%F.S
1%F.S
1%F.S
0.5%F.S
0.5%F.S
>100KΩ
>100KΩ
>100KΩ
>100KΩ
>100KΩ
(0.2mA)
(0.2mA)
(0.2mA)
>100KΩ
(0.2mA)
>100KΩ
<300Ω
>100KΩ
>100KΩ
<300Ω
_
_
_
_
Input signal table
4:48H*48W
6:96H*48W
101.0
91.0
10.0
45.0
76.0
25.0
71.0
25.0
45.5
45.5
100.0
84.0
6.0 10.0
91.0
71.0
25.0
114.0
25.0
91.5
45.5
96
48
48
48
+0.5
-0
+0.5
-0
+0.5
-0
+0.5
-0
AL1 AL2
AL1 AL2
SF4 DIGITAL METER
SF6 DIGITAL METER

KKSFE02-A0-4
10. Simple Problem Shooting
Display MessageDisplay Message
Display HHHH / LLLLDisplay HHHH / LLLL
To check input signal connecting well or not.
To check FH, FL value;
To check working temperature is OK or not.
To check input signal selection is right or not.
To check input signal connecting well or not.
To check FH, FL value;
To check working temperature is OK or not.
To check input signal selection is right or not.
Shooting MethodShooting Method
7:72H*72W
100.0
80.0
10.0 10.0
67.5
93.0
25.0
93.0
25.0
68
68
72
72
+0.5
-0
+0.5
-0
AL1 AL2
8:48H*96W
9:96H*96W
100.0
45.0
6.0 10.0
84.0
117.0
25.0
71.0
25.0
91.5
45.5
101.0
91.0
10.0
90.5
117.0
25.0
122.0
25.0
91
91
96
48
96
96
+0.5
-0
+0.5
-0
+0.5
-0
+0.5
-0
AL1
AL2
SF7 DIGITAL METER
SF8 DIGITAL METER
SF9 DIGITAL METER
160
80
80:80H*160W
16:160H*80W
SF1 6 DI GI TAL MET ER
160
80
102
10 81 11
76
182
30
103 25
77+0.5
-0
102
10 81 11
154
154.5 +0.5
-0
187 30
103
25
154.5 +0.5
-0
77+0.5
-0
9. Wire Connection
11
24V/30mA
SF4
SF7 SF9
24V/30mA
SF6/8 SF16/80
AC 110V
This manual suits for next models
4
Other SOMMY Measuring Instrument manuals

SOMMY
SOMMY ES925 Series User manual

SOMMY
SOMMY SF Series User manual

SOMMY
SOMMY SF Series User manual

SOMMY
SOMMY SG8-SVA User manual

SOMMY
SOMMY SF Series User manual

SOMMY
SOMMY EP8 SVA Series User manual

SOMMY
SOMMY EW9L Series User manual

SOMMY
SOMMY EL801 Series User manual

SOMMY
SOMMY ER9 Series User manual