IM-P113 -04 CMGT Issue 2
UIB45 Sealed Inverted Bucket Steam Trap for use with Pipeline Connectors
Note: Before actioning any installation observe the 'Safety information' in Section 1.
3.1 Check materials, pressure and temperature and their maximum values. If the maximum operating limit
is included in the system to prevent overpressurisation.
3.2
3.3
appropriate, before installation on steam or other high temperature applications.
3.4 The UIB45 can be installed on any pipeline connector. See separate Installation and Maintenance
Ensure that both gaskets are clean and undamaged and that the transfer holes are clear. Place the
UIB body against the connector gasket face, ensuring that the trap itself is vertical so the bucket
always rises and falls in a vertical plain.
thread lubricant to the threads of the connector screws (10
the mating gasket faces are in parallel, intimate contact. Tighten the screws evenly and gradually
to the recommended torque value (see Table 1). Open isolation valves slowly until normal operating
conditions are achieved.
3.5 Inverted bucket steam traps do not permit rapid release of air. On process applications, in particular,
trap. If it is below, and is leaking or left open, the waterseal could be blown away leading to steam
damage can be reduced by thermal insulation.
3.6 The inlet of the trap should be below the drain point of the plant being drained, so that a waterseal
can be maintained around the open end of the bucket. When installed in a horizontal pipeline a small
3.7 Where the trap discharges into a closed condensate return system or where there is a lift at the trap,
3.8 If the trap has to be installed at a higher point than the drainage point, then a small bore riser into
internal waterseal.
3.9 If the trap is installed on a superheated steam system application, then a non return valve should be
Priming of the trap with water may be required before commissioning.
3.10 Check for leaks.
Note 1:
a temperature of 100 °C (212 °F).
Note 2: On all blast discharge steam traps check valves and sight glasses must be installed at least 1 metre
(3 ft) downstream of the trap.
3. Installation