Adjusting
This procedure may take a number of trials to set up
correctly. The system will be functioning correctly when
the ADV opens long enough to drain almost all the
condensate from the system. Do not drain completely, as
this will drain costly compressed air.
1. Pressurize the system.
2. Set the “ON” button (1) to 10 seconds and note when
the condensate fully dispensed. Then back off by
approximately one-half second.
3. Set the “OFF” buton (2) to 5 minutes, to start. When
the ADV energizes, watch the discharge for air
escaping following the condensate discharge. Repeat
the steps outlined in 2 and 3, by adjusting the
“ON/OFF” buttons until the proper time is achieved to
effectively remove the condensate without loosing
costly air pressure.
NOTE: Changes in seasons and humidity may have an
affect on the “ON/OFF” time settings. If so readjust the
settings.
Maintenance
It is necessary to periodically clean the screen located in
the Strainer Ball Valve. Failure to do this may cause
damage to the compressed air system resulting in costly
shutdown. To do this maintenance procedure, perform
the following steps:
1. Isolate the strainer screen by rotating the blue ball
valve handle (4) 90° clockwise to the closed position.
2. Unscrew the knurled end cap and remove it along
with the stainless steel screen.
3. Clean debris from end cap and screen.
4. Place screen into end cap and screw the assembly
into Strainer Ball Valve.
5. Rotate blue handle 90° counter-clockwise to reopen
and pressurize the sytem.
Trouble Shooting
Caution: Whenever servicing the ADV, be sure to remove sytem pressure form the immediate system.
1. Valve will not close: Typically caused by particulates and debris in the valve causing the seals not to
properly close.
Action: ADV25 series and up: Remove top nut and remove the coil-timer assembly. Unscrew guide
assembly by large hex nut and remove. Use care as not to lose
plunger and spring assembly. Carefully remove diaphragm
assembly. Clean internal and parts. Reassemble in reverse order
and pressurize.
Action: ADV10 series: Remove top nut and remove the coil-timer assembly. Unscrew
stainless steel stop from atop brass guide with pliers. Carefully
remove plunger and return spring using care as to not lose plunger
or spring. Clean valve internals and plunger. Reassemble in reverse
order and pressurize.
2. Valve will not open:
Action: Check supply to insure presence of electrical power.
Action: Disassemble valve per the instructions above (Item 1) and check for debris interfering with
the movement of the plunger. Clean and reassemble.
Spare Parts
Spare parts are available. Consult your supplier for price
and availability.
Warranty
The manufacturer warranties its products to be free of
defects in material and workmanship for a period of one
year from the date of delivery.
NOTE: If the product fails within the warranty and is to
be returned, call Spirax Sarco for a “Return Authorization
Number”. This procedure must be followed to insure
proper action and closure.
Spirax Sarco Applications Engineering Department
Toll Free at: 1-800-833-3246