IM-S27-06 CH Issue 24
2.3 Adjusting the setpoint
(Refer to SX100 Operator's Manual)
Note: This setting is normally set to 0°C . It does not represent the running setpoint
temperature. Setting the temperature at this level will prevent the steam valve opening with
no circulating pump running.
The actual running temperature is normally set from the 'Program settings', and is set for
each segment of the program (Refer to Tables 2 and 3, and 'Example of how to set a
program', page 8).
With the setpoint programmer in BASE MODE (i.e with the RUN, HLD, SET and PRG indicators
OFF), the two main displays will show the process variable value (upper display) and the setpoint
value (lower display – Read only).
To change the setpoint value:
-Press the SCROLL key until the message area displays one of ;
Ctr SP °C, Ctr SP °F or Ctr SP (according to input range)
(Note: Factory set to indicate 'Ctr SP 0°C').
-Use the UP and DOWN keys to change the setpoint value (in the lower display) as required.
-When the setpoint value is set as desired, press the SCROLL key again to return to the initial
display. The controller will remain in BASE MODE.
2.4 Defining and viewing a program
(PROGRAM DEFINE MODE)
The setpoint programmer may be put into PROGRAM DEFINE MODE from either BASE MODE
or PROGRAM RUN MODE i.e. with a program currently running.
Entry into PROGRAM DEFINE MODE:
-Press the SCROLL and UP keys simultaneously. The lower main display will show '0'
and the message display will show: 'Unlock'.
-Use the UP and DOWN keys to set the value in the lower main display to the PROGRAM
DEFINE MODE lock value and then press the SCROLL key.
(Note: This value is initially factory set to 10).
The setpoint programmer will now enter PROGRAM DEFINE MODE, i.e the SET and PRG
indicators will go ON and the operator will be able to edit programs and segments.
-The PROF button should then be used to either select 'A' in the 'P No.' window if choosing
to view/modify settings common to all programs, or to select Nos.,1 to 8 for viewing/modifying
settings which apply to those program Nos., only (Refer to Tables 1, 2 and 3).
-The MODE key can then be used:
i-to switch to CONTROLLER DEFINE MODE
(i.e PRG led goes off, SET led stays on.) refer to Table 4.
ii - to show a message display.
-To return to PROGRAM DEFINE MODE press the MODE key; to return to BASE MODE,
press the SCROLL key.
-After entering PROGRAM DEFINE MODE the SCROLL key can be used to step through
the sequence.
-The displayed Program Number may be changed using the PROG key and the displayed
Segment Number may be changed using the RUN/HOLD key.