SPX FLOW ME Series User manual

ME Series
Mist Eliminator
Models: ME125, ME250, ME500, ME1100, ME1500,
ME2100, ME2400, ME3000
FORM NO.: 3148671 REVISION: 12/2019 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT.
INSTRUCTION MANUAL

2
DESCRIPTION
The Mist Eliminator is a coalescing type oil removal lter designed to
remove oil and water aerosols from a compressed air system. It consists
of a highly engineered, loosely packed, glass ber lter cartridge housed
in a heavy duty ASME stamped pressure vessel.
Compressed air is directed into the vessel and through the lter cartridge
where entrained water and oil aerosols are captured by the bers. The
captured particles move along the bers and coalesce into larger droplets
which gravitate to the bottom of the cartridge. Here they fall into the vessel
sump and are discharged from the system.
CONTENTS
GENERAL SAFETY INFORMATION ....................... 2
RECEIVING INSTRUCTIONS ................................. 2
DESCRIPTION ........................................................ 2
1.0 INSTALLATION ................................................. 3
2.0 OPERATION ...................................................... 5
3.0 MAINTENANCE ................................................ 5
DIMENSIONS AND WEIGHTS ................................ 6
WARRANTY ............................................................ 7
GENERAL SAFETY INFORMATION
A. Pressurized devices
This equipment is a pressure containing device
• Do not exceed maximum operating pressure shown on the serial
number tag.
• Make sure equipment is depressurized before working on or
disassembling for service.
• A pressure relief device must be added to the equipment.
B. Breathing air
• Air treated by this equipment may not be suitable for breathing
without further purication.
Refer to OSHA standard 1910.134 for the requirements for breath-
ing quality air.
RECEIVING INSTRUCTIONS
A. Receiving
This shipment has been thoroughly checked, packed, and inspected
before leaving our plant. It was received in good condition by the carrier
and was so acknowledged.
1. Check for visible loss or damage
If this shipment shows evidence of loss or damage at the time of
delivery to you, insist that a notation of this loss or damage be made
on the delivery receipt by the carrier’s agent.
2. Check for concealed loss or damage
When a shipment has been delivered to you in apparent good
order, but concealed damage is found upon unpacking, notify the
carrier immediately and insist on his agent inspecting the shipment.
Fifteen days from receipt of shipment is the maximum time limit for
requesting such inspection. Concealed damage claims are not our
responsibility as our terms are F.O.B. point of shipment.

3
1.0 INSTALLATION
1.1 System cleaning
The compressed air system should be purged prior to the installation
of the Mist Eliminator.
• Solid particles should be removed from upstream lines in order to
prevent any loose dirt, rust, or scale from entering the lter and
causing a premature increase in pressure drop.
• Residual oil should be ushed from down-stream lines otherwise
considerable time will be necessary before the desired air quality
is available at the point-of-use.
1.2 Location in a compressed air system
Aftercooler/separator - It is strongly recommended that the Mist
Eliminator be installed at a point where the compressed air is as cool
as possible. In most cases the Mist Eliminator will have to be installed
downstream of an aftercooler to provide an inlet temperature below
the 150°F (65°C) maximum. While inlet temperatures as high as
150°F (65°C) are possible, this will allow some oil to remain a vapor
and pass through the lter. Lower inlet temperatures (preferably
below 120°F [49°C]) will have allowed more of the oil vapor present
to condense into liquid droplets which can then be removed by the
Mist Eliminator.
Refrigerated dryers - The Mist Eliminator should be installed down-
stream of a refrigerated dryer to remove any oil that may have
condensed inside the dryer.
Desiccant dryers - The Mist Eliminator should be installed upstream
of a desiccant dryer to prevent oil from contaminating the desiccant.
The distance between the Separator and Mist Eliminator must be
minimized to avoid over loading with water. A drop in temperature
from 110°F (43°C) to 105°F (41°C) will condense enough liquid water
to overload the Mist Eliminator.
1.3 Service clearance
Make certain that clearance exists above the lter to allow removal
and replacement of the lter cartridge.
1.4 Foundation
The Mist Eliminator can be installed on any at, level oor with suf-
cient strength to support the required weight. Mounting holes are
available for anchoring if desirable.
NOTE: Mount so that inlet and outlet connections are horizontal (vessel
is vertical). Separated and coalesced liquids drain by gravity downwards
through the cartridge and drop to and are collected in the lter sump. The
vessel must be mounted nearly plumb vertically so that drainage will not
be impeded and ltration eciency reduced.
A typical installation will also include:
Manual or Automatic Drains
Dierential Pressure Gauge
Isolation Valves and by-pass piping
1.5 Connections
Connect inlet and outlet piping to the compressed air system.
NOTE: Flow Direction - Check to ensure that the air ow is in the
proper direction as indicated on the vessel. Air ow direction through
the lter cartridge must be from the inside out.

4
1.6 Drain provisions
The bottom of the pressure vessel is provided with a drain plug for
shipping purposes. Provision for manual or automatic draining is
necessary for proper operation.
Do not attempt to remove drain plug if the unit is
pressurized.
A. Manual Drain - When draining is performed manually on a
regular, periodic basis, a simple (open/shut) valve piped to
the drain port may be used to drain the vessel. When draining
manually, the valve should be opened slowly to avoid rapid
depressurization and possible cartridge damage.
B. Automatic Drain - Where regular manual draining is not per-
formed, an automatic condensate drain should be used. A variety
of drains are available from the manufacturer. Pipe automatic
drains to the drain port.
An isolation valve is recommended if servicing drain is desired
while the system is pressurized.
1.7 Dierential pressure gauge
1. Maximum voltage switching 100 volts AC/DC
Maximum switching current 0.30 AMP
Maximum carrying current 1 AMP
Contact rating: 10 VA
A gauge and installation kit are shipped separately packaged
for eld installation. Gauge may be installed on vessel or on a
nearby wall using the wall mounting bracket supplied.
NOTE: Make certain O-rings are in place on the bottom of the
gauge body.
Connect the low pressure transmission bolt (bolt next to red band
on gauge) to the gauge port at the lter outlet (downstream side
of lter).
Connect the high pressure transmission bolt (bolt next to green
band on gauge) to the gauge port at the lter inlet (upstream
side of lter).
Torque bolts to 25 +/- 5 inch-oz. Do not over tighten.
1.8 Operating limitations
1. Maximum Working Pressure:
Standard ASME Coded Units 150 psig (10.3 bar)
NOTE: If using external drain, do not exceed pressure rating of
drain.
2. Maximum Pressure Dierential - 30 psi (2.1 bar)
IMPORTANT: Under normal circumstances the pressure dif-
ferential across the lter should not exceed 30 psi (2.1 bar);
excessive pressure drop may cause lter cartridge failure. Filter
cartridge change-out recommended at 3 psi (0.2 bar).
3. Maximum Operating Temperature - 150°F (65°C)
NOTE: Temperatures above 120°F (49°C) are not recommended
since ltration eciency may decrease.
4. Chemical Resistance - Compressed air does not normally contain
contaminants which will adversely aect the lter cartridge.
However, some hydrocarbons, acids, bases and certain
other chemicals can attack parts of the lter assembly. These
contaminants are usually introduced through the compressor
intake under certain environmental conditions.
Provision should be made to prevent this in order to protect the
entire compressed air system. On questionable applications
consult factory prior to installation.

5
2.0 OPERATION
2.1 After installation slowly pressurize Mist Eliminator and inspect for
leaks. Operation is continuous and automatic.
2.2 Periodic checks are recommended to insure continuous separation
and ltration eciency.
A.. Check pressure drop
1. Check for excessive pressure drop. Pressure drop in excess
of 3 psi (0.2 bar) indicates that the cartridge should be re-
placed.
IMPORTANT: Pressure drop should never exceed 30 psi
(2.1 bar).
2. Check for sudden reduction in pressure drop. This might
indicate a leak through the lter cartridge due to damage
from chemical attack or excessive pressure drop.
B. Check the flow, pressure, and temperature to make sure
that the lter is not being operated beyond its rated capacity.
See Section 1.8 for operating Limitations and Section 2.3 to
determine maximum ow capacity.
C. Check for proper drainage. See that manual drains are drained
periodically and that automatic drains are functioning.
2.3 Determining maximum ow capacity
Maximum air ow for the various lters at 100 psig (7 bar) is indicated
in Table 1. To determine maximum air ows at inlet pressures other
than 100 psig (7 bar), multiply ow from Table 1 by multiplier from
Table 2 that corresponds to the minimum operating pressure at the
inlet of the lter.
2.4 Maximum Operating Conditions
Maximum Working Pressure: 150 psig (10.3 bar)
ASME coded pressure vessels
Maximum Operating Temperature: 150°F (65°C)
TABLE 1
Model
Number
Flow scfm @
100 psig, 7 bar
ME125
ME250
ME500
ME1100
ME1500
ME2100
ME2400
ME3000
125
250
500
1100
1500
2100
2400
3000
TABLE 2
Minimum
Inlet Pressure
psig / bar
Multiplier
20 / 1.4
30 / 2.1
40 / 2.8
60 / 4.1
80 / 5.5
100 / 7.0
120 / 8.3
150 / 10.3
0.30
0.39
0.48
0.65
0.82
1.00
1.17
1.43
3.0 MAINTENANCE
3.1 When to replace lter cartridge
A. Initial (dry) pressure drop: 1 psi (0.07 bar) nominal.
B. Operating pressure drop: During operation the lter cartridge
becomes liquid loaded (wetted). At rated flow conditions,
operating pressure drop will normally be: 0.5 to 1 psi (0.035 to
0.07 bar). Further pressure drop will occur only as the cartridge
becomes loaded with solid particles.
C. Change out pressure drop: IT IS RECOMMENDED THAT THE
CARTRIDGE BE REPLACED FOR MAXIMUM FILTRATION
EFFICIENCY WHEN PRESSURE DROP REACHES 3 PSI
(0.2 BAR).
NOTE: Pressure drop after ow interruption.
When ow is interrupted for several hours, the pressure drop may tempo-
rarily increase upon the resumption of ow. Normally, within one hour, the
pressure drop should return to where it was prior to stopping the ow. This
phenomenon is not cause for lter cartridge replacement. It is due both
to residual liquids contained within the cartridge “pooling” and a change
in the viscosity of these liquids due to a temporary temperature change.
3.2. Procedure for lter cartridge replacement
THIS FILTER IS A PRESSURE CONTAINING DEVICE. DEPRESSURIZE
BEFORE SERVICING.
A. By-pass the lter assembly to permit servicing.
B. Depressurize the lter assembly slowly by opening blow down
valve.
C. Remove bolts securing the lter top to the vessel.
D. Remove the top ange of the lter complete with lter element.
E. Clean the inside of the vessel and inspect for any signs of cor-
rosion.
F. Unscrew the lter element from the top ange. Discard the ele-
ment in accordance with applicable regulations.
Used elements typically hold contaminants, such as compressor
lubricants and particulate matter.
G. Thread new element into top ange.
H. Replace top ange (complete with new lter element).
I. Reinstall bolts to secure lter top.
J. Slowly repressurize lter housing and check for any leaks.

6
NOTES: Dimensions and Weights are for reference only. Request certied drawings for construction purposes.
DIMENSIONS AND WEIGHTS
NOTES
1. All models meet the requirements of the A.S.M.E.
Boiler and Pressure Vessel Code and have the code
stamp applied.
2. Vessels with 4” or 6” nozzles have anges only. The
bolt holes straddle the vertical center line.
3. Maximum operating temperature for all vessels is
150°F (66°C).
Nominal Air Flow @ 100PSIG 125 SCFM 250 SCFM 500 SCFM 1100 SCFM 1500 SCFM 2100 SCFM 2400 SCFM 3000 SCFM
Vessel Type Type I Type I Type I Type Il Type Il Type Ill Type Ill Type Ill
Shell Size
(O.D.)
Inches
(mm)
14
(356)
14
(356)
14
(356)
16
(406)
18
(457)
24
(610)
24
(610)
24
(610)
Inlet Connection 2” FLG
150# CL
2” FLG
150# CL
2-1/2” FLG
150# CL
4” FLG
150# CL
4” FLG
150# CL
4” FLG
150# CL
4” FLG
150# CL
4” FLG
150# CL
Outlet Connection 2”
NPT (F)
2”
NPT (F)
2-1/2”
NPT (F)
4” FLG
150# CL
4” FLG
150# CL
4” FLG
150# CL
4” FLG
150# CL
4” FLG
150# CL
“A” INCHES
(mm)
17-3/4
(451)
17-3/4
(451)
17-15/16
(456)
25-13/16
(656)
26-13/16
(681)
32-13/16
(833)
32-13/16
(833)
32-13/16
(833)
“B” INCHES
(mm)
37-1/8
(943)
37-1/8
(943)
48-1/16
(1221)
72-3/4
(1848)
80-1/8
(2035)
89-3/8
(2270)
89-3/8
(2270)
89-3/8
(2270)
“C” INCHES
(mm)
27-1/8
(689)
27-1/8
(689)
36-1/2
(927)
55-1/8
(1400)
62-1/2
(1588)
71-1/2
(1816)
71-1/2
(1816)
71-1/2
(1816)
“D” INCHES
(mm)
11-1/2
(292)
11-1/2
(292)
11-1/2
(292)
11-1/2
(292)
11-1/2
(292)
11-1/2
(292)
11-1/2
(292)
11-1/2
(292)
“E” INCHES
(mm)
14
(356)
14
(356)
14
(356)
16
(406)
18
(457)
24
(610)
24
(610)
24
(610)
“F” INCHES
(mm)
12
(305)
15
(381)
27
(686)
46
(1168)
46
(1168)
36
(914)
50
(1270)
62
(1574)
Filter Assembly
Weight
POUNDS
(kg)
185
(84)
185
(84)
220
(100)
350
(159)
390
(177)
700
(318)
715
(324)
730
(331)
Replacement Crtg
Weight
POUNDS
(kg)
15
(7)
20
(9)
35
(16)
60
(28)
80
(37)
120
(55)
135
(62)
150
(68)
Drain Size Connection 1” NPT 1” NPT 1” NPT 1” NPT 1” NPT 1” NPT 1” NPT 1” NPT
Replacement Cartridge
Catalog Number 4001416 4001417 4001418 4001419 4001421 4001422 4001423 4001424

7
Mist Eliminator Warranty and Conditions of Sale
1. Mist Eliminator Coalescing Filter Cartridge 5 Year Guarantee Statement:
Seller guarantees that the coalescing lter cartridge shall not require replacement for ve (5) years after
shipment by Seller. This guarantee is based on the lter as delivered and is contingent upon the following:
a) the lter is installed and operated as specied in the Installation and Operating Manual supplied with the
lter and
b) operation of the lter is within the lter specication limits.
2. Mist Eliminator 5 Year Warranty Statement:
Seller warrants that the lter will be free from defects due to materials or workmanship for ve (5) years after
shipment by Seller. If within thirty (30) days after Buyer’s discovery of any such defects, Buyer noties Seller
thereof in writing, seller shall, at its options and as the exclusive remedy for this warranty, promptly repair or
replace the portion of the lter found to be defective. Failure by Buyer to give Seller such written notice within
the applicable time period specied above, shall be deemed a waiver of buyer’s claim for such defects.
The warranty covers parts only for the warranty period. Products repaired or replaced under warranty shall be
warranted for the unexpired portion of the warranty applying to the original product. This warranty is based on
the lter as delivered and is contingent upon the following:
a) the lter is installed and operated as specied in the Installation and Operating Manual supplied with the
lter and
b) operation of the lter is within the lter specication limits. The maximum damages liability of the
manufacturer or seller is the original purchase price of the product or part.
The foregoing warranty is exclusive and in lieu of all warranties, whether written, oral, or statutory, and is
expressed in lieu of the implied warranty of merchantability and the implied warranty of tness for a particular
purpose.
The manufacturer shall not be liable for loss or damage by reason of strict liability in tort or its negligence in
whatever manner including design, manufacture or inspection of the equipment or its failure to discover, report,
repair, or modify latent defects inherent therein.
The manufacturer, his representative or distributors shall not be liable for loss of use of the product or incidental
or consequential costs, expense, or damages incurred by the buyer, whether arising from breach of warranty,
negligence or strict liability in tort.
SERVICE DEPARTMENT: (724) 746-1100

ME SERIES
Mist Eliminator
Models: ME125, ME250, ME500,
ME1100, ME1500, ME2100,
ME2400, ME3000
SPX FLOW, INC.
4647 S.W. 40th Avenue
Ocala, Florida 34474-5788 U.S.A.
P: (724) 745-1555
E: ft.dehydration.order.entry@spxflow.com
www.spxflow.com/deltech
Improvements and research are continuous at SPX FLOW, Inc.
Specifications may change without notice.
ISSUED 12/2019 Form No. 3148671 Revision: E
COPYRIGHT ©2019 SPX FLOW, Inc.
This manual suits for next models
8
Table of contents
Other SPX FLOW Water Filtration System manuals
Popular Water Filtration System manuals by other brands

SpectraPure
SpectraPure MAXCAP D1 Installation and operating manual

Netafim
Netafim SANDSTORM installation manual

aquarius direct
aquarius direct AD300 installation guide

Waterdrop
Waterdrop WD-AS08 instruction manual

Rozone
Rozone ROWASHER operating manual

BWT
BWT ROC Clinic One Installation and operating instructions