8INSSDHX0622
MENU STRUCTURE
MAIN MENU
USER INTERFACE
The electronic control is equipped with
a user interface that displays the duct
temperature, error codes and operating
modes. The main menu displays the
air temperature after the coil identied
according to the direction of air ow.
To navigate between menus, press the
MENU button on the user interface. Use
the up ▲ and down ▼ buttons to change
the value displayed in the selected menu.
The value will ash in editing mode. To
conrm the desired value displayed, press
MENU or wait (30 sec.) and the main menu
will automatically be displayed.
To return to the main menu (duct
temperature), keep pressing and releasing
the MENU button until the main menu
displays the duct air temperature, or
wait (30 sec.) and the main menu will
automatically be displayed.
OPERATING MODES
NOTE 1: Displayed by default. Indicates the temperature after the coil in the direction of air ow.
NOTE 2: To recalibrate, press and hold down the MENU button for eight seconds. When the CAL menu is selected, the SCR/Relay outputs are
identied by r1, r2, r3, etc. The number that follows represents the power of the element in relation to the system (from 0 to 9). Recalibration can
take up to ve minutes depending on the number of stage power.
NOTE 3: In this menu, the inputs and outputs can be tested using the ▼▲ buttons. The inputs are identied as 1. for W1, 2. for W2, 3. for W3
and 10. for 0-10 V. If a signal is on for the corresponding input, the display will read ON. For the 0-10 V input, a 4 V level is required for a valid
condition. If the display reads On, the outputs may be activated one at a time for a maximum of eight seconds. If an output is identied as ON,
the corresponding output is activated.
NOTE 4: The ERR error menu only appears when there are one or more system errors. Use the ▼▲ buttons to verify the active error code(s). To
delete the resolved errors, press and hold down the MENU button for eight seconds while the ERR menu is selected.
NOTE 5: Connected to the air velocity sensor (optional).
MODE DESCRIPTION
MENU
W1 MODE If the W1 signal is on and air is owing (NOTE 5), the elements are activated and modulated to reach and
maintain the temperature setpoint (duct temperature sensor).
W12 MODE
If the W1 signal is on and air is owing (NOTE 5), 60% of the elements are activated.
If the W1 and W2 signals are on and air is owing (NOTE 5), all the elements are activated (100%).
The duct temperature is always limited to the set point temperature (duct temperature sensor).
W123 MODE
If the W1 signal is on and air is owing (NOTE 5), 40% of the elements are activated.
If the W1 and W2 signals are on and air is owing (NOTE 5), 70 % of the elements are activated.
If the W1, W2 and W3 signals are on and air is owing (NOTE 5), all the elements are activated (100%).
The duct temperature is still limited to the set point temperature (duct temperature sensor).
0-10 V MODE If there is a signal between 0-10 Vdc and air is owing (NOTE 5), a percentage of the elements is activated and
modulated. The duct temperature is still limited to the set point temperature (duct temperature sensor).
SELF MODE If air is owing, the elements are activated and modulated without external control to reach and maintain
the set point temperature (power supply temperature sensor after the coil, in the direction of air ow).
OFF MODE
The OFF mode turns the unit off.
Warning: The power circuit is still on even when the device is in OFF mode.