P4 Parameter Function: To set the differential.
SET key.
the P4
parameter,
To change
press the
O O
from 0.1 C to 20.0 C when RS = 0.
Differential between cut out and cut
in temperature can be set between
O O
1 C to 20 C when RS = 1 or
Use UP/DOWN keys to set desired
value.
Example : If the set point is set at
O
10.0 C and differential is set at
O
2.0 C, then when the system
O
reaches 10.0 C, the relay will cut
O
out. Since the differential is 2.0 C,
the relay will cut in (restart) at
O O O
12.0 C (10.0 C+2.0 C).
O
0.1 C
O
1 C
Min Max
Fac.
RS = 0
O
20.0 C O
2.0 C
Min Max
Fac.
RS = 1
O
20 C O
2 C
P5 Parameter Function: To set probe calibration.
To change
the P5
parameter,
press the
SET key.
RS = 0.
Use UP/DOWN keys to set desired
value.
In time it may be possible that the
display may be offset by a degree or
so.
To compensate for this error, you
may need to add or minus the
degrees required to achieve the
correct temperature. Setting value is
O O
from -10 C to 10 C when RS = 1 or
O O
from -10.0 C to 10.0 C when
Example : The temperature on
O
the display is 28.0 C, whereas the
O
actual temperature is 30.0 C. You
will need to set the P5 mode to 2.0,
which means that once out of the
programming mode, the
temperature will show
O O O
30.0 C (28.0 C + 2.0 C).
O
-10.0 C
Min Max
Fac.
RS = 0
O
10.0 C O
0.0 C
Min Max
Fac.
RS = 1
O
-10 C O
10 C O
0 C
P6 Parameter Function: To set time delay
between relay restart time.
To change
the P6
parameter,
press the
SET key.
This parameter is used to protect the
compressor from restarting in a short
period of time and can be set
between 0 to 99 minutes.
Use UP/DOWN keys to set desired
value.
Example : If this parameter is set at
3 minutes, the relay will cut off at the
set temperature, but will not restart
for a minimum of 3 minutes, even if
the differential is achieved earlier.
This parameter is good to protect the
life of the compressor when there
are power fluctuations and the
compressor is switched off and on
within a few seconds.
Flashing
Time delay in progress
0 Min
Min Max
Fac.
99 Min 3 Min
P1 Parameter
Function: To set controller for heating
or cooling.
To change
the P1
parameter,
press the
SET key.
0
Min Max
Fac.
RS = 0 / 1
1 0
Use UP/DOWN keys to get desired
value & press set to confirm.
0: Cooling mode
1: Heating mode.
Function: To set minimum allowable
low temperature set point.
Use UP/DOWN keys to set desired
value. Once set at a particular value,
this will not allow the set point to go
below this value.
Example : Setting this parameter at
O
-30.0 C will not allow the set point to
O
go below -30.0 C. Also, if the
O
temperature reaches -30.0 C, the
display will show Lt (LowTemp.)
indicating that the temperature has
gone below the value in this
parameter.
P3 Parameter
To change
the P3
parameter,
press the
SET key.
(Message on display)
O
-40.0 C
O
-40 C
Min Max
Fac.
RS = 0
O
XX C O
-40.0 C
Min Max
Fac.
RS = 1
O
XX C O
-40 C
XX = Set Point
P2 Parameter
Function: To set maximum allowable
high temperature limit.
To change
the P2
parameter,
press the
SET key.
Example : Setting this parameter
O
at 25.0 C will not allow the set point to
O
go above 25.0 C. Also, if the
O
temperature reaches 25.0 C, the
display will show Ht (High Temp.)
indicating that the temperature has
gone above the value in this
parameter.
(Message on display)
H
O
XX C
Min Max
Fac.
RS = 0
O
50.0 C O
50.0 C
Min Max
Fac.
RS = 1
O
XX C
O
99 C O
50 C
Once set at a particular value, this
will not allow the set point to go
above this value.
Use UP/DOWN keys to set desired
value.
XX = Set Point