
R u n T i m e : R u n n i n g
0 y 0 d 2 h 2 8 m
Run Time Screen: Displays the status of the MotorSaver®and the total motor run time.
MotorSaver®Status: The following codes may be displayed:
§Running - The MotorSaver’s contacts are energized and the motor is running.
§MotorOff - The MotorSaver’s contacts are energized, but the motor is not
running.
§Pend Flt - A fault is detected. The trip delay timer is incrementing—the
MotorSaver®will trip when the trip delay setpoint is met. If the fault
condition ends, the pending fault will clear and the trip delay timer
will decrement back down to zero.
§Tripped - The MotorSaver®tripped due to a fault condition. The fault can be
viewed on the following screen. Fault #1 is the last fault (most
recent), fault #2 the second to last fault, and so on.
§Restart - The MotorSaver®is timing through the restart delay on power-up.
This is a normal function.
OR
The MotorSaver®tripped due to a fault condition. The condition has
cleared and the MotorSaver®is timing through the restart delay
before energizing the contacts.
OR
The motor has been turned off and the MotorSaver®is timing
though the set restart delay to prevent rapid cycling.
§Manual - The MotorSaver®tripped, the fault condition has cleared, but the
restart delay is set to MAN (manual). Turn the restart delay out of
the manual position to allow the motor to restart.
OR
The MotorSaver®is set to MAN (manual) at power-up. Turn the
restart delay setting out of MAN to energize the contacts.
§CFLckOut - The MotorSaver®Model 455 has tripped due to a load-side problem
such as contactor failure, worn or pitted contacts, loose or broken
wires, etc. A manual reset is always required when this fault occurs.
Run Time: The definition of run time is the total length of time a particular MotorSaver®
Model 455 has run a motor—also called “run hours.”
Note: To reset the Model 455’s run hours, first remove power. Make a note of each of
the Model 455’s adjustable settings. Turn all of the setpoint knobs to the
minimum position, i.e., VOLT. ADJ. and RESTART fully counter-clockwise;
UNBALANCE TRIP AND TRIP DELAY fully clockwise. Apply power momentarily,
then remove power again to readjust each setting back to the noted/desired level.
Reapply power.