• Do not install the product in duct systems where the equiva-
lent duct length is less than 25 feet (7.6 meters).
• To prevent damage to the dryer or to the product, do not in-
stall the DPV 22–2, #75104 within 5 linear feet (1.5 linear
meters) or further than 40 linear feet (12 linear meters) from
the dryer outlet.
• Do not install the product in the exhaust duct system of a
dryer if it is not permitted to do so.
• Do not install insulated ducting upstream of the product.
• Do not use the product with high output dryers.
• When cutting or drilling into walls or ceilings, watch for elec-
trical wiring and other hidden utilities to prevent damage.
• Ducted exhaust fans must always be released to the
outdoors
• Do not block the air intakes or exhaust.
• Do not mount this product in an outdoor location.
• Do not clean the product with chemicals that can cause cor-
rosion or water hotter than 140° Fahrenheit (60° Celsius).
• Do not let unwanted objects enter the product.
• Do not use this product to remove hazardous or explosive
material and vapours.
• Do not exhaust air hotter than 167° Fahrenheit (75° Celsius).
• Do not mount this product in kitchens.
• Do not release air into spaces within walls or into attics,
crawl spaces, or garages.
• If the LED light on the indicator panel starts to flash, do not
use the dryer. See section 5 Troubleshooting.
• To prevent the possibility of dryer fan cavitation and/or re-
leasing hotter air than allowed for the drying cycle and com-
promising drying times, the airflow of the product must not
exceed the dryer fan capacity.
2.3 Personal protective equipment
Use personal protective equipment during all work on the
product.
• Approved eye protection
• Approved protective helmet
• Approved hearing protection
• Approved protective gloves
• Approved protective shoes
• Approved work clothing
3 Installation
3.1 To Do Before the Installation
Caution
This is a cord-connected product. Do not
try to field wire the product. Tampering with
the electrical enclosure voids the UL mark-
ing and the manufacturer’s warranty.
3.1.1 To Calculate the Duct Run
This product is able to overcome equivalent duct lengths up to
125 feet (38 meters) on duct systems with 4 inch (102mm) di-
ameter galvanized, steel ducts. It is also able to hold an air ve-
locity of 1200 fpm (6.10 m/s).
To calculate the length of your planned duct system, measure
from the dryer to the external release point in the roof or the
wall.
For each 45° elbow, add 2–1/2 feet (0.76 meters) to your total
duct system calculations. Add 5 feet (1.5 meters) for every 90°
elbow.
3.1.2 To Select the Product Location
Caution
To prevent damage to the dryer or to the
product, do not install the DPV 22–2,
#75104 within 5 linear feet (1.5 linear me-
ters) or further than 40 linear feet (12 linear
meters) from the dryer outlet.
Note:
If the product is installed less than 15 feet (4.6 meters) from
the dryer outlet, install a secondary lint trap between the dry-
er and the product.
Note:
Stretch flex ducting is not allowed for clothes dryer exhaust
applications.
Fantech recommends using a Mounting Bracket (included) to
install the product to a rafter or a joist. A vertical rigid duct may
be used to hold the product if the duct is safely stabilized (refer
to local codes prior to supporting the product in the duct alone).
Refer to section 6.1 To Maintain the Product for inspection
recommendations.
Correctly seal all duct connections to prevent leakage and loss
of product performance.
3.1.3 About the Indicator Panel
The product is equipped with a remote-mounted, low voltage
operation indicator panel and a 50–foot cable. We recommend
mounting this panel to a wall using applicable fasteners.
This wall-mounted indicator panel has a blue LED light that vis-
ually alerts the user of any malfunctions.
3