manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Accessories
  8. •
  9. System Sensor 2351PTIRAUS User manual

System Sensor 2351PTIRAUS User manual

3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
FIGURE 1. WIRING DIAGRAM
2
31
2
33
1
2
1
(–)
(+)
+ -
Compatible
Control Panel
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
supervise connections.
CLOSE LOOP OPTIONAL WIRING
Remote
Annunciator
(–)
(+)
RA
+–
+
RA
+–
+
RA
+–
+
C0129-10AUS
FIGURE 2. ROTARY ADDRESS SWITCHES
TENS ONES
9
10
11
12
13
14
15
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
C0162-00
FIGURE 3. FEATURES OF THE PTIR DETECTOR
Base Alignment Notch
Infrared
Light
Pipe
Magnet Test Point
Thermistors
Infrared
Light
Pipe
LEDs
C2050-00
FIGURE 4. CLEANING THE PTIR DETECTOR
Cover
Removal
Tabs
Sensor Cover
Sensing Chamber
Cover and Screen
Infrared
Light
Pipe
Thermistors
Sensing
Chamber
}
C2044-00
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication)
Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
Operating Humidity Range: 15% to 90% Relative Humidity, Non-condensing
Operating Temperature Range: -10°C to 50°C
Air Velocity: 0 to 91.4 m/min.
Height: 51 mm installed in B501AUS-W/B501AUS-IV Base
Diameter: 104 mm installed in B501AUS-W/B501AUS-IV Base
Weight: 95 g
Isolator Load Rating: 0.0063*
Applicable Standards: AS 7240.7 and AS 7240.5 (Class A2S)
*Please refer to your isolator base/module manual for isolator calculation instructions.
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ).
GENERAL DESCRIPTION
2351PTIRAUS and 2351PTIRAUS-IV are plug-in type multi-criteria smoke sen-
sors that offer a photoelectric sensing chamber combined with a fixed tem-
perature heat detector and infrared (IR) sensors.
All sensors transmit an analog representation of smoke density over a commu-
nication line to a control panel. Rotary dial switches are provided for setting
the sensor’s address. (See Figure 2.)
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100Z).
Fire Alarm and Control panels offer different feature sets across different mod-
els. As a result, certain features of the photoelectric sensors may be available
on some control panels, but not on others.
2351PTIRAUS and 2351PTIRAUS-IV will support only CLIP (Classic Loop In-
terface Protocol) mode. The possible features available in the multi-criteria
smoke sensors, if supported by the control unit are:
1. The sensor’s LEDs can operate in three ways—on, off, and blinking—and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 99 addresses.
Please refer to the operation manual for the control panel for specific opera-
tion. The photoelectric sensors require compatible addressable communica-
tions to function properly. Connect these sensors to listed-compatible control
panels only.
Compatible bases: B501AUS-W/B501AUS-IV.
SPACING
System Sensor recommends spacing sensors in compliance with
AS 1670.1:2015. All detectors should be spaced and installed in accordance
with the requirements of the relevant authority having jurisdiction. For spe-
cific information regarding sensor spacing, placement, and special applica-
tions, refer to AS 1670.1:2015 or the Smoke Detector Application Guide.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting.
Improper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the base wiring diagram.
(See Figure 1.)
2. Set the desired address on the sensor address switches. (See Figure 2.)
I56-6764-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
2351PTIRAUS and 2351PTIRAUS-IV
Multi-Criteria Photoelectric,
Thermal and Infrared Sensor
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
1 I56-6764-001
6/23/2021
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
TAMPER RESISTANCE
2351PTIRAUS and 2351PTIRAUS-IV includes a tamper-resistant capability that
prevents removal from the base without the use of a tool. Refer to the base
manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensitivity
readings are available through the fire alarm control panel (FACP). Refer to the
manufacturer’s published instructions for proper use.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet
electronically simulates smoke in the sensing chamber, testing the sensor
electronics and connections to the control panel.
a. Hold the test magnet in the magnet test area as shown in Figure 3.
b. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs to
blink, latch on, or latch off. Refer to the control panel technical documen-
tation for sensor LED status operation and expected delay to alarm.
NOTE: The magnet test initiates an approximately 10 minute period when
the detector's signal processing software routines are not active.
B. Smoke Entry
Canned aerosol simulated smoke (canned smoke agent) may be used for
smoke entry testing of the smoke detector.
The multi-criteria smoke sensor uses algorithms to process signals re-
ceived from multiple sensors to determine alarm conditions and reduce
false alarms. Therefore, a single burst of canned smoke will not immedi-
ately place the detector into an alarm condition because the detector al-
gorithms correctly determine a burst of canned smoke is not fire. In order
to perform functional testing of the photoelectric sensor, the device must
be placed into test mode. Test mode allows the detector to isolate the indi-
vidual sensors for testing. The device can be placed into test mode through
either of the following methods.
a. Put the device into test mode by holding a test magnet in the magnet
test area as shown in Figure 3 for 6-12 seconds.
NOTE: If the magnet is held in place for too long the fire alarm test func-
tion will be triggered. (See Magnet Test, above.) Reset the panel and pro-
ceed with testing the smoke entry portion of the device.
b. Perform smoke entry testing immediately following the magnet test. The
magnet test initiates an approximately 10 minute period when the detec-
tor’s signal processing software routines are not active.
Once in test mode, test the smoke detector using one of the tested and ap-
proved aerosol smoke products. Refer to the manufacturer’s published in-
structions for proper use of the canned smoke agent. When used properly,
the canned smoke agent will cause the smoke detector to go into alarm.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary
by manufacturer. Misuse or overuse of these products may have long term
adverse effects on the smoke detector. Consult the canned smoke agent manu-
facturer’s published instructions for any further warnings or caution statements.
C. Direct Heat Method (Hair Dryer of 1000-1500 watts)
A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward the thermistor, holding the heat source approximately
30 cm from the detector in order to avoid damaging the plastic housing.
The detector will reset only after it has had sufficient time to cool. Make
sure both thermistors are tested individually.
A sensor that fails any of these tests may need to be cleaned as described
under CLEANING, and retested. When testing is complete, restore the system
to normal operation and notify the proper authorities that the system is back
in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place.
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently push-
ing it until it locks into place. Make sure that the thermistors do not be-
come bent under the cover.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
Note: Dispose of electronic waste according to national and local regulations
when scrapping or replacing a device. Do not discard as general trash.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
ON-SITE SENSITIVITY ADJUSTMENT
The sensitivity for this device is set at FDCIE.
For the AFP-3030 panel, alarm sensitivity levels 2-8 meet the sensitivity level
requirement of the AS 7240.7 & AS 7240.5 standards. Sensitivity level 9 is
thermal only and complies with the requirement of AS 7240.5 standard.
For more information on sensitivity settings refer to the manufacturer's Fire
Alarm Control Panel manual.
System Sensor®is a registered trademark of Honeywell International, Inc.
Australian
Standard
Lic. SMK40640-2
SAI-Global
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the
tamper seal on the packaging is present and
unbroken and the product has not been tampered
with since leaving the factory. Do not install this
product if there are any indications of tampering.
If there are any signs of tampering the product
should be returned to the point of purchase.
It is the responsibility of the system owner to
ensure that all system components, i.e. devices,
panels, wiring etc., are adequately protected to
avoid tampering of the system that could result
in information disclosure, spoofing, and integrity
violation.
SUPPLEMENTAL INFORMATION
For Limitations of Fire Alarm Systems,
please go to:
http://www.systemsensor.com/
en-us/Documents/I56-1558.pdf
Limitations of
Fire Alarm Systems
2 I56-6764-001
©2021 System Sensor. 6/23/2021

This manual suits for next models

1

Other System Sensor Accessories manuals

System Sensor 200 Series User manual

System Sensor

System Sensor 200 Series User manual

System Sensor 52051E-RF User manual

System Sensor

System Sensor 52051E-RF User manual

System Sensor FAAST LT User manual

System Sensor

System Sensor FAAST LT User manual

System Sensor 7351A User manual

System Sensor

System Sensor 7351A User manual

System Sensor SMB500 User manual

System Sensor

System Sensor SMB500 User manual

System Sensor 7251 User manual

System Sensor

System Sensor 7251 User manual

System Sensor B401BH User manual

System Sensor

System Sensor B401BH User manual

System Sensor SPECTR Alert ADVANCE CHSR User manual

System Sensor

System Sensor SPECTR Alert ADVANCE CHSR User manual

System Sensor 5451EIS User manual

System Sensor

System Sensor 5451EIS User manual

System Sensor 7351 User manual

System Sensor

System Sensor 7351 User manual

System Sensor 2351BR User manual

System Sensor

System Sensor 2351BR User manual

System Sensor 22051E-RF User manual

System Sensor

System Sensor 22051E-RF User manual

System Sensor 22051EISE User manual

System Sensor

System Sensor 22051EISE User manual

System Sensor 2251CTLE User manual

System Sensor

System Sensor 2251CTLE User manual

System Sensor RA400Z User manual

System Sensor

System Sensor RA400Z User manual

System Sensor B200SR User manual

System Sensor

System Sensor B200SR User manual

System Sensor 2251TLE User manual

System Sensor

System Sensor 2251TLE User manual

System Sensor 22051TEI User manual

System Sensor

System Sensor 22051TEI User manual

System Sensor 22051TLE User manual

System Sensor

System Sensor 22051TLE User manual

System Sensor SENS-RDR User manual

System Sensor

System Sensor SENS-RDR User manual

System Sensor 2251BR User manual

System Sensor

System Sensor 2251BR User manual

System Sensor 22051E User manual

System Sensor

System Sensor 22051E User manual

System Sensor 2251TM User manual

System Sensor

System Sensor 2251TM User manual

System Sensor B200SR-LF-WH User manual

System Sensor

System Sensor B200SR-LF-WH User manual

Popular Accessories manuals by other brands

Frigidaire FGM0205KB installation instructions

Frigidaire

Frigidaire FGM0205KB installation instructions

Omron E3F brochure

Omron

Omron E3F brochure

COUGAR Aqua 280 ARGB manual

COUGAR

COUGAR Aqua 280 ARGB manual

Cedes TOF/Start-EA Installation and operation manual

Cedes

Cedes TOF/Start-EA Installation and operation manual

NOW Solutions 7483 Instructions & Care

NOW Solutions

NOW Solutions 7483 Instructions & Care

Scame electrical solutions OPTIMA-EX 24V Series Installation, use and maintenance

Scame electrical solutions

Scame electrical solutions OPTIMA-EX 24V Series Installation, use and maintenance

Olympus BL-AC10DS-A2 user manual

Olympus

Olympus BL-AC10DS-A2 user manual

Vega VEGAPULS 61 Quick setup guide

Vega

Vega VEGAPULS 61 Quick setup guide

Nevco MPCX 1500 Operator instructions

Nevco

Nevco MPCX 1500 Operator instructions

Dometic Club/Ace Pro Side Wings operating manual

Dometic

Dometic Club/Ace Pro Side Wings operating manual

LaZee Tek eeZee Mouse CURSOR quick start

LaZee Tek

LaZee Tek eeZee Mouse CURSOR quick start

Thermo Scientific 3110 Operating and maintenance manual

Thermo Scientific

Thermo Scientific 3110 Operating and maintenance manual

Steren TIM-270 instruction manual

Steren

Steren TIM-270 instruction manual

Giropes BAXTRAN BR16 user manual

Giropes

Giropes BAXTRAN BR16 user manual

Nordic Deltaco PB-C1004 user manual

Nordic

Nordic Deltaco PB-C1004 user manual

LEGRAND 0 503 96 manual

LEGRAND

LEGRAND 0 503 96 manual

RUSTA 6257-0013 manual

RUSTA

RUSTA 6257-0013 manual

Panasonic MA6Z121 Specification sheet

Panasonic

Panasonic MA6Z121 Specification sheet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.