TAC 2413 User manual

ControllerTAC 2413
Handbook
0-004-7614-0 (GB), 1998-10-23
100 %
0 %
+
+
TAC improves indoor climate and
reduces operating costs through open
solutions for demanding users.


TAC AB, 1998-10-23
Contents
0-004-7614-0 (GB), i (ii)
TAC 2413 Handbook
TAC 2413 Handbook
ThisdocumentcontainsinformationwhichisthepropertyofTACandisthereforemadeavailableonlytothosewhouseandmaintainTACequipment. Disclosure of,
copyingorusingthisdocumentortheinformationinitforanyotherpurposeis strictly forbidden.
TACreservestherighttomakechangesoradditionstothematerialas necessary.
© 1998 TAC AB
Contents
1 This handbook............................................................................................................. 1:1
1.1 Overview............................................................................................................................................. 1:1
1.2 How you may use this handbook ...................................................................................................... 1:2
1.3 Documentation for the controller..................................................................................................... 1:2
2 The air handling controller TAC 2413....................................................................... 2:1
2.1 Function .............................................................................................................................................. 2:1
3 Using the operator’s panel.......................................................................................... 3:1
3.1 Introduction ....................................................................................................................................... 3:1
3.2 What is shown in the display window? ............................................................................................ 3:1
3.2.1 Parameter numbers and parameter values ........................................................................................... 3:2
3.2.2 Operating modes.................................................................................................................................. 3:3
3.2.3 Weekly program .................................................................................................................................. 3:4
3.2.4 Outputs of the controller...................................................................................................................... 3:5
3.2.5 Alarms ................................................................................................................................................. 3:5
3.3 How are the buttons used? ................................................................................................................ 3:6
4 Day-to-day usage ......................................................................................................... 4:1
4.1 Introduction ....................................................................................................................................... 4:1
4.2 Reading temperatures ....................................................................................................................... 4:1
4.3 Setting temperatures ......................................................................................................................... 4:2
4.4 Setting weekly programs for timed operation................................................................................. 4:2
4.4.1 Weekly program one speed operation, 1/2 speed operation................................................................ 4:2
4.4.2 Weekly program 1/1 speed .................................................................................................................. 4:3
4.4.3 Yearly program for holidays................................................................................................................ 4:3
4.5 Reading and resetting alarms........................................................................................................... 4:5
4.6 Choosing the operating mode ........................................................................................................... 4:5
4.7 Setting the clock ................................................................................................................................. 4:6
5 Installation ................................................................................................................... 5:1

TAC AB, 1998-10-23
Contents
TAC 2413 Handbook
ii (ii), 0-004-7614-0 (GB)
5.1 Mounting ............................................................................................................................................ 5:1
5.2 Connection.......................................................................................................................................... 5:4
5.3 Terminal blocks.................................................................................................................................. 5:6
5.4 Cable lengths ...................................................................................................................................... 5:6
5.5 Commissioning................................................................................................................................... 5:7
6 Troubleshooting ........................................................................................................... 6:1
7 Functional description ................................................................................................ 7:1
7.1 Introduction ....................................................................................................................................... 7:1
7.2 Operating modes of the controller ................................................................................................... 7:1
7.3 Air handling ....................................................................................................................................... 7:3
7.3.1 Fan operation ....................................................................................................................................... 7:3
7.3.2 Temperature control............................................................................................................................. 7:5
7.3.3 Outdoor compensation ........................................................................................................................ 7:6
7.3.4 Night heating ....................................................................................................................................... 7:7
7.3.5 Night cooling ....................................................................................................................................... 7:8
7.3.6 CO2 / SPC ........................................................................................................................................... 7:9
7.3.7 Mixed air damper .............................................................................................................................. 7:10
7.3.8 Heat recovery..................................................................................................................................... 7:10
7.3.9 Heating coil ....................................................................................................................................... 7:12
7.3.10 Electric heating .................................................................................................................................. 7:14
7.3.11 Cooling coil ....................................................................................................................................... 7:14
7.3.12 Cooling coil, DX cooling, DX........................................................................................................... 7:16
7.3.13 Cooling recovery ............................................................................................................................... 7:17
7.4 Clock ................................................................................................................................................. 7:18
7.4.1 Summer time ..................................................................................................................................... 7:18
7.4.2 Summer period .................................................................................................................................. 7:18
7.5 Timer programs ............................................................................................................................... 7:19
7.6 Alarms .............................................................................................................................................. 7:19
7.6.1 Fan alarms ......................................................................................................................................... 7:19
7.6.2 Fire alarm........................................................................................................................................... 7:20
7.6.3 Frost protection alarm ....................................................................................................................... 7:21
7.6.4 Pump/Overheating alarm ................................................................................................................... 7:21
7.6.5 Freezing alarm ................................................................................................................................... 7:22
7.6.6 Efficiency alarm................................................................................................................................. 7:22
7.6.7 Deviation alarm ................................................................................................................................. 7:23
7.7 Memory backup ............................................................................................................................... 7:23
7.8 Cold start .......................................................................................................................................... 7:23
8 Technical data .............................................................................................................. 8:1
AppendixA: Commissioning protocol/
List of parameters .......................................................................................................App:1
Index .................................................................................................................................. Ind:1

TAC AB, 1998-10-23 0-004-7614-0 (GB), 1:1 (4)
TAC 2413 Handbook This handbook
1 This handbook
1.1 Overview
Chapter 2,The air handling controllerTAC 2413
This chapter provides a short introduction to the controller.
Chapter 3,Using the operator’s panel
This chapter will provide you with a more detailed explanation of
how to read and set values using the buttons and the display
window.
Chapter 4, Day-to-day usage
This chapter will give you enough information to be able to
handle the controller during normal operation.
Chapter 5, Installation
This chapter will show you how to install, connect and get the
controller to operate.
Chapter 6,Troubleshooting
This chapter contains measures, which you may take on your
own, to find and remedy a possible malfunction in the control
system.
Chapter 7, Functional description
There is a description in detail of all the functions and parameters
of the controller here.
Chapter 8,Technical data
You will find all the technical data of TAC 2413 here.
Appendix A,
Commissioning protocol/List of parameters
There is a commisioning protocol here which will provide you
with support when you are commissioning the controller. All the
parameters of the controller are listed here.

1:2 (4), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook This handbook
Index
At the end of the handbook, you will find an index containing
page references.
1.2 How you may use this handbook
The TAC 2413 Handbook describes all the functions and procedu-
res that are needed to install, commission and use the controller.
The TAC 2413 controller, as well as other products in the
TAC 2000 family, must not be used for purposes other than that
which it was constructed for.
The installation, connection and maintenance is required to be
performed by authorized staff.
During normal operation
If you are only going to read or set temperatures and other para-
meters during normal operation, it is sufficient to read Chapter 3,
Using the operator’s panel, and Chapter 4, Day-to-day usage.
You may also make use of the Quick Reference which is located
on the front of the controller.
During installation and commissioning
If you are going to install and commission the controller, you
should read Chapter 5, Installation. The document which is in-
cluded with the controller, TAC2413 Installation instructions, may
be used for this purpose as well. The commissioning protocol is
included in that document, but it is appendix A in this handbook
as well.
During troubleshooting
When there is something wrong with the controller, you should
read Chapter 3, Using the operator’s panel,Chapter 4, Day-to-
day usage and Chapter 6, Troubleshooting.
1.3 Documentation for the controller
Enclosed documentation
The documents below are supplied with the controller. They con-
tain all the information you need to be able to install and commis-
sion the controller.
•TAC2413 Installation instructions/Commissioning protocol
(part number 0FL-3891)
•TAC2413 Quick Reference (part number 0FL-3898)

TAC AB, 1998-10-23 0-004-7614-0 (GB), 1:3 (4)
TAC 2413 Handbook This handbook
Supplementary documentation
There is more information to be found in the document below. It
may be ordered from your nearest TAC sales or service office:
•Data sheet TAC 2000 (part number 0-003-1745)

1:4 (4), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook This handbook
Blank page.

TAC AB, 1998-10-23 0-004-7614-0 (GB), 2:1 (2)
TAC 2413 Handbook The air handling controller TAC 2413
2 The air handling controllerTAC 2413
TAC 2413 is a digital controller which is able to control, monitor and
supervise air handling units (AHU) in buildings.
TAC 2413 controls the room temperature or the supply air temperature
by controlling a heating coil, a cooling coil and heat recovery in se-
quence. The controller also contains functions for timed operation,
alarms, pump and fan control, and so on.
TAC 2413 has a clock which may be used to set weekly and yearly
programs, as well as powerful control functions for automatic opera-
tion. Reading and setting temperatures and other parameters is a
simple process. The display window provides you with clear informa-
tion in the form of numbers and symbols.
The controller may be mounted on a norm rail EN 500 22
(TS 35 mm), in a panel or on a wall.
2.1 Function
When the AHU starts, the return air fan (FF) is always started first;
then, supply air fan (TF) starts running. Both fans start on half
speed, no matter what speed has been chosen. If full speed has
been chosen, it is activated 30 seconds later than TF starts.
During the transition from full speed to half speed operation, both
fans are stopped for 10 seconds, then, FF is started before TF.

2:2 (2), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook The air handling controller TAC 2413
FF01
ST21
ST22
GT31
GT71
GP71
GT81
P01
SV21
LV01 LK01
P02
SV51
GP61
TF01
GT11
GT21
GT41
SN01
ST41
GX41
GX21
You can choose if you want room or supply air control by using
DIP switch 1. During room control, the control is done from the
sensor GT11, or possibly GT 41, which is chosen with DIP switch
2. The supply air temperature is controlled in cascade via the sen-
sor GT21 which has a minimum and maximum limitation function.
The control signal for the heating coil actuator SV21 is 2–10 V,
but you can set it to 0–10 V by using DIP switch 7. If the heating
coil temperature drops below a set value, SV21 is opened to prov-
ide a minimum limitation. If the temperature keeps dropping in
spite of this, the AHU is stopped and a freezing alarm is tripped. If
the AHU stops, the GT81 sensor helps hold the return temperature.
The control signal for heat recovery (HEX, or VVX in the pictu-
res) is 0–10 V. The efficiency is calculated using the sensors
GT31, GT41 and GT71. An alarm is tripped if it is too low.
During defrosting, the control signal for the VVX is controlled to
an optimum setting, and if the defrosting is not complete, TF is
stopped to quicken the process further. If the defrosting will run
for too long, the AHU stops and an alarm is tripped. The alarm is
reset in the controller.
The control signal to SV51 is 2–10 V, but you may set it to 0–10 V
by using DIP switch 7. The cooling coil actuator is allowed to
control the cooling valve only when the room temperature has
reached the cooling setpoint. Both SV21 and VVX have to be
closed, and the date has to be within the summer period, for this
to apply.
Flow diagram for TAC2413.
Flow diagram with:Plate HEX, SV heating, SV cooling, cooling recovery. Room control.
Flow diagram with: Rot.HEX, SV heating, SV cooling, cooling recovery. Room control.

TAC AB, 1998-10-23 0-004-7614-0 (GB), 3:1 (6)
TAC 2413 Handbook Using the operator’s panel
3 Using the operator’s panel
3.1 Introduction
This chapter will show you how to use the buttons of the
operator’s panel to read and set parameters, such as temperatures,
for example.
3.2 What is shown in the display window?
The display window provides you with information from the AHU
in the form of numbers and symbols.
Theinformation in thedisplaywindow
1
2
3
4
5
6
78910 121314151617
18
0
23
22
21
20
19
24
TF
TU WE TH FR SA
°C
12:00
P 00
MO
11
1
1
12
FF Dx
Pv Pk
!
++
%
SU
Parameter number 24 hour time bar Parameter value
cooling coil
supply air fan off timed operation manual pump,
control cooling coil
return air fan half speed full speed pump,
heating coil
electric
heat
DX
cooling
heating coil
heat
recovery
alarm

3:2 (6), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook Using the operator’s panel
3.2.1 Parameter numbers and parameter values
The controller has a list of 100 parameters ranging from 0 to 99.
Some of these parameters may be set, such as the room tempera-
ture setpoint; others, however, can only be read, such as the out-
door temperature. Some parameters are not shown if the cor-
responding function is disabled. For example, night cooling and
night heating are both disabled if there is no room sensor.
The parameter number and the parameter value constitute a
“window” for the list of parameters, see the figure below.
The and buttons are used to move the window up and
down on the list of parameters.
P 25 Night heating SP
P 26 Supply air, h.
control, min SP
P 20 Output signal,
Cool. valve (%)
P 21 Winter/
summer period
1
2
3
4
5
6
78910 121314151617
18
0
23
22
21
20
19
24
TF
TU WE TH FR SA
°C
19:0
P 24
MO
11
1
1
12
FF Dx
Pv Pk
!++
%
SU
List of parameters
display window
parameter
number
parameter
value
previous window
next window

TAC AB, 1998-10-23 0-004-7614-0 (GB), 3:3 (6)
TAC 2413 Handbook Using the operator’s panel
3.2.2 Operating modes
The different operating modes of the controller are shown in the
display window by means of the symbols below.
The symbols of the operating modes of the controller
The symbols are interpreted as follows:
Off
12
Timed one speed operation/halv speed operation
11Timed full speed operation
12
Manual control, one speed operation/half speed operation
Manual control, full speed operation
A flashing hand and the 1/2 speed or 1/1 speed symbol denotes
manual control by means of an external contact (X1, X2).
You may find information on how to set the operating mode in
Chapter 4, in the section Setting the weekly program for timed
operation. For a more detailed explanation of the operating mo-
des, please refer to Chapter 7, and more specifically the section
Operating modes of the controller.
11
1
1
12
1
2
3
4
5
6
78910 121314151617
18
0
23
22
21
20
19
24
TF
TU WE TH FR SA
°C
12:00
P 00
MO
11
FF Dx
Pv Pk
!
++
%
SU
Operating mode

3:4 (6), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook Using the operator’s panel
3.2.3 Weekly program
The weekly program is shown as a 24 hour time bar from 00:00 to
24:00 for each day of the week. The part of the bar that is filled
shows when daytime operation applies.
The symbols of the weekly program
Each field in the time bar represents 30 minutes. If the field is fil-
led, the AHU is in operation. An empty field means that the AHU
is not running.
Below the time bar, you will find the days of the week. They
show which day of the week the time bar applies to.
• MO: Monday
• TU : Tuesday
• WE: Wednesday
• TH : Thursday
• FR : Friday
• SA : Saturday
• SU : Sunday
How to set a weekly program is described in Chapter 4, in the sec-
tion Setting weekly programs for timed operation. For more in-
formation on time schedules, please refer to the section Time
schedules in Chapter 7.
1
1
12
1
2
3
4
5
6
78910 121314151617
18
0
23
22
21
20
19
24
TF
TU WE TH FR SA
°C
12:00
P 00
MO
11
FF Dx
Pv Pk
!
++
%
SU
24 hour time bar days of the week

TAC AB, 1998-10-23 0-004-7614-0 (GB), 3:5 (6)
TAC 2413 Handbook Using the operator’s panel
3.2.4 Outputs of the controller
The controller has a number of outputs for control, such as for the
heating coil, and for controlling external units, such as the heating
coil pump. When an output is active, its symbol is shown in the
display window.
The symbols for the outputs of the controller
3.2.5 Alarms
When there is an alarm, an alarm symbol will flash in the display
window together with the symbol of the part of the installation
that the alarm is referring to. For example, when the frost protec-
tion guard has been triggered, the alarm symbol and the heating
coil symbol will flash.
Thealarm symbol
Chapter 4 describes how to read alarms in the section Reading
alarms. There is further information on the alarms of the control-
ler in the Alarms section in Chapter 7.
1
1
12
1
2
3
4
5
6
78910 121314151617
18
0
23
22
21
20
19
24
TF
TU WE TH FR SA
°C
12:00
P 00
MO
11
FF Dx
Pv Pk
+
%
SU
!+
1
2
3
4
5
6
8 9 10 12 13 14 15 16 17
18
0
23
22
21
20
19
24
TF
TU WE TH FR SA
°C
12:00
P 00
MO
11
1
1
12
FF Dx
Pv Pk
!
+
%
SU
+
7
supply air fan
return air fan cooling coil pump, cooling coil
heating coil heat recovery pump, heating coil
DX cooling
alarm
electric heat

3:6 (6), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook Using the operator’s panel
3.3 How are the buttons used?
The controller has five buttons located below the display window.
Thebuttons on theoperator’s panel
The and buttons are used to choose a parameter.
The and buttons are used to change a parameter value.
The button is used as an enter button. Each change made to
a parameter must be confirmed with this button if it is to be regis-
tered in the controller. A flashing “P” in the display window will
give you confirmation that you have pressed .
The button is also used to alternate between a full and empty
field in the 24 hour time bar.
Enter
button
Choose
parameter
Increase/decrease
parameter value

TAC AB, 1998-10-23 0-004-7614-0 (GB), 4:1 (6)
TAC 2413 Handbook Day-to-day usage
4 Day-to-day usage
4.1 Introduction
This chapter provides enough information for you to be able to
read and set temperatures and other parameters during normal
operation. All parameters and functions are explained in detail in
Chapter 7, Functional description.
If you want to switch between the parameter groups P 00–P 17
and P 18–P 99, press and at the same time.
4.2 Reading temperatures
Procedure for reading a temperature:
1 Choose the parameter number (P No.) using or
according to the list below. You can increase the number by
pressing and decrease it by pressing .
2 Hold the button down for fast increase/decrease.
3 Read the value.
Temperature P No.
Supply air temperature P 01
Calculated SP for supply air temperature P 02
Room temperature P 03
Calculated SP for room/return air temp. P 04
Return air temperature P 05
Exhaust air temperature P 08
Outdoor temperature P 09
0
1
2
3
4
5
678910 11 12 13 14 15 16 17 18
19
20
21
22
23
24
12
P:01 14.7 °C

4:2 (6), 0-004-7614-0 (SE) TAC AB, 1998-10-23
TAC 2413 Handbook Day-to-day usage
4.3 Setting temperatures
Procedure for setting a temperature:
1 Choose the parameter number (P No.) by using or . You
can increase the number by pressing and decrease it by
pressing .
2 Change the temperature by using or .
3 Confirm by using .
Parameter P No.
Heating setpoint P 10
Cooling setpoint P 11
4.4 Setting weekly programs for timed operation
4.4.1 Weekly program one speed operation, 1/2 speed operation
The controller is factory set so that the AHU is in operation
07.00–17.00 on Monday to Friday according to this weekly pro-
gram. For an explanation in detail of time schedules, please refer
to the section Time schedules in Chapter 7.
Procedure for changing the weekly program:
1 Choose parameter number P 12 by using or . Increase
the number by using and decrease it by using .
2 When the parameter number has been chosen, the 24-hour
time bar is shown along with MO for Monday.
3 Move forward on the time bar with and backward with
to the segment which is to be changed. The segment will flash.
4 Change the half-hour segments by using . A filled
segment means that the AHU is in operation. When one
segment has been changed, the next segment starts to flash.
5 Move on by using until TU for Tuesday is shown.
6 Change the half-hour segments for Tuesday by using .
7 Repeat steps 5 and 6 for the rest of the days of the week.
0
1
2
3
4
5
678910 11 12 13 14 15 16 17 18
19
20
21
22
23
24
12
P:10 20.0 °C
0
1
2
3
4
5
678910 11 12 13 14 15 16 17 18
19
20
21
22
23
24
12
P:12 07-17
mo

TAC AB, 1998-10-23 0-004-7614-0 (GB), 4:3 (6)
TAC 2413 Handbook Day-to-day usage
Parameter P No.
Weekly program 1/2 speed P 12
4.4.2 Weekly program 1/1 speed
For 1/1 speed to take effect, the weekly programs for both 1/2
speed and 1/1 speed operation have to be active. The 1/1 speed
program is not set on delivery.
Procedure for setting the weekly program:
1 Make sure that the weekly program for half speed operation
(P12) is set.
2 Choose parameter number P 13 by using or . The
parameter number is increased by using and decreased by
using .
3 When the parameter number has been chosen, the 24-hour
time bar is shown along with MO for Monday.
4 Move forward on the time bar by using and backward by
using to the segment which you wish to change. The
segment will flash.
5 Change the half-hour segments by using . A filled segment
means that 1/1 speed operation will be active. When a
segment has been changed, the next segment will start to flash.
6 Move on by using until TU for Tuesday is shown.
7 Change the half-hour segments for Tuesday by using .
8 Repeat steps 5 and 6 for the rest of the days of the week.
Parameter P No.
Weekly program 1/1 speed P 13
4.4.3 Yearly program for holidays
You may use the yearly program to shut down the AHU during
longer periods of time. There are six holiday periods that may be
programmed up to a year in advance. Each holiday period is limi-
ted by a start and stop date, and the 24 hours of the day are affec-
ted. There are no holidays programmed on delivery. For an ex-
planation in detail of time schedules, please refer to the section
Time schedules in Chapter 7.
0
1
2
3
4
5
678910 11 12 13 14 15 16 17 18
19
20
21
22
23
24
12
P:13 07-17
mo

4:4 (6), 0-004-7614-0 (SE) TAC AB, 1998-10-23
TAC 2413 Handbook Day-to-day usage
Procedure for setting a holiday period:
1 Choose parameter number P 15 by using or . The
parameter number is increased by using and decreased by
using .
2 Choose a holiday period (1–6) by using or .
3 Confirm by using .
4 Go to P 16 by using .
5 Set the start date (month.day) by using or . Hold the
button down for fast increase/decrease.
6 Confirm by using .
7 Go to P 17 by using .
8 Set the stop date (month.day) by using or .
9 Confirm by using .
Procedure for deleting a holiday period:
1 Choose parameter number P 15 by using or . The
parameter number is increased by using and decreased by
using .
2 Choose a holiday period (1–6) by using or .
3 Go to P 16 by using .
4 Change the start date to day 0 of the month (month.00) by
using or . Hold the button down for fast increase/
decrease.
5 Confirm by using .
You may also set the stop date to day 0 if you wish to delete a
holiday period.
Parameter P No.
Yearly program, choice of holiday period 1–6
P 15
Start of holiday. Start date of holiday period
as per above. P 16
End of holiday. Stop date of holiday period
as per above. P 17
0
1
2
3
4
5
678910 11 12 13 14 15 16 17 18
19
20
21
22
23
24
12
P:15 1
0
1
2
3
4
5
678910 11 12 13 14 15 16 17 18
19
20
21
22
23
24
12
P:16 01:00
Table of contents
Other TAC Controllers manuals
Popular Controllers manuals by other brands

DINGSONG
DINGSONG DS822-A8KTF operation instruction

Mircom
Mircom TX3 Series Installation quick reference

Philio Technology Corporation
Philio Technology Corporation PAN34 manual

BB&S
BB&S Pipeline 4 Way Controller manual

AMX
AMX AXB-REL8 instruction manual

Grundfos
Grundfos EPC 300 Installation and operating instructions

RealSimulator
RealSimulator FSSB-R3 Lighting user guide

Moeller
Moeller Xcomfort CAAE-01/01 Assembly instructions

Viconics
Viconics VT8000 Series installation guide

emz
emz smart Sol operating instructions

Omron
Omron E5EC instruction manual

BIFFI
BIFFI ICON3000 Series Installation, operation and maintenance manual