Teknim TWS-1815 Instruction Manual

Release Date: 19/04/2021
Rev:00
TWS-1815
Wireless Fire Siren and Flasher
Installation & User Manual
Critical Warnings
General
✓Read this manual with care before operating the device and keep it for further reference.
✓Comply with all warnings and measures provided in the manual. Follow all respective operation and usage
instructions.
✓Keep the devices away from water and humidity.
Service
Do not attempt to repair the device on your own, you may be exposed to electric shock in case you open the
device housing.
Contact your dealer or authorized service in case of a failure. Technical interventions to the device must be
carried out by qualified personel of authorized service.
Failures That Require Service Intervention
Contact your authorized service or dealer in case of a failure or in following cases.
✓If the power line or plug is damaged,
✓If any liquid has leaked or a substance has fallen into the device,
✓If the device is exposed to water or rain,
✓If the device is dropped or the housing is damaged,
✓If there is significant performance change in the device,
✓If the device is not operating normally according to the operating instructions in the user manual
Call the service since erroneous operations may cause further failures.
What You Can Do On Your Own
Do not attempt to repair the device on your own since you may be exposed to electric shock in case you
open the device housing. Contact your dealer or authorized service in case of a failure. Technical
interventions to the device must be carried out by qualified personel of authorized service. The device must
be cleaned with a dry cloth. No chemical substances must be used for cleaning purposes .
Handling and Transportation
The device must be handled with care in manner that it does not get exposed to impacts and liquid influx.
The damages that may occur during improper handling are out of guarantee.
Human and Environment Health
This device does not contain any chemical or biological substance that may harm human health.
*The consumer may apply to the Consumer Arbitration Board or Consumer Court of the place of residance or
of the consumer transactions in case of disputes arising from exercising the rights granted by the guarantee.
Technical Specifications
Communication Distance
(via Coordinator or Router)
500 m (open area)
Operating Frequency
868 MHz
Operating Frequency Channels
10
Output Power
14 dBm (25 mW)
Average (Quiescent) Current Consumption
20uA (@12V)
Battery
4xCR123A (3 Vdc)
Battery Life
6 years
Area of Use
Closed Area
Operating Temperature Range
-10C ~ 55C (14F ~ 131F)
Humidity
@ +40°C between 0% and 95%
Alarm State Current Consmp. (Default tone)
~Min.=6.74mA, Nom.=11.06Ma, Max.=15.1mA.(12VDC )
Volume
88.4 / 90.3 / 95 dB±2 dB (@12VDC, within 1 meter)
Number of Siren Tones
42 tone types (Default tone :1)
Flash speed mode
3 (Slow, Normal, Fast)
Protection Class
IP21C
Heart Led
White, flashes with 20 sec
periods
Red, flashes with 20 sec
periods
Size (mm)
Ø:110mm, h:55mm (Incl. Base)
Housing Material
Red, UL94 non-combustible Polycarbonate
Weight (Incl. base / Excl. base)
190 gr / 147 gr (Batteries not included)
Leds
Wide Angle 8 pcs bright LED
Heart Led
1815R=White 1815W=Red flashes with 20s periods
Piezo
Piezzo w/ impermeable gasket
Coverage Area
W-2,4-4
Area of Use
Interior Use / Siren type: Type A device
Supported Flasher Modes and Descriptions
Warning: Do not attempt to take the card out of its plastic protection. It is sealed solely for your safety.
Users must avoid intervention.
Connection/Test Button
CR123A Battery
Compartment
Tamper Key
Programming Connector
Tone Modes Tone Type Tone Description
TONE 1 (default)
Default tone 1754Hz ~ 2380Hz sinus signal
11 HZ 600 us
TONE 2
Specific tone 1754Hz ~ 2380Hz sinus signal
5 HZ 1333 us
TONE 3
Specific tone 1754Hz ~ 2380Hz sinus signal
1 HZ 6666 us
TONE 4
Specific tone 500Hz ~ 1200Hz sinus signal
0.33 HZ 2594 us
TONE 5
Specific tone 2400Hz ~ 2850Hz sawtooth signal
7 HZ 2197 us
TONE 6
Specific tone 2400Hz ~ 2850Hz sawtooth signal
1 HZ 15384 us
TONE 7
Specific tone 2400Hz ~ 2850Hz sawtooth signal
50 HZ 307 us
TONE 8
Specific tone 300Hz ~ 1200Hz sawtooth signal
1 HZ 400 us
TONE 9
Specific tone 500Hz ~ 1200Hz sawtooths signal
1 HZ 856 us
TONE 10
Specific tone 800Hz ~ 970Hz sawtooth signal
7 HZ 646 us
TONE 11
Specific tone 800Hz ~ 970Hz sawtooth signal
1 HZ 4524 us
TONE12
Specific tone 800Hz ~ 970Hz sawtooth signal
50 HZ 90 us
TONE 13
Specific tone 800Hz ~ 970Hz sawtooth signal
2 HZ 2262 us
TONE14
Specific tone 800Hz ~ 970Hz sawtooth signal
9 HZ 502 us
TONE 15
Specific tone 800Hz ~ 970Hz sawtooth signal
100 HZ 45 us
TONE 16
Specific tone 500Hz ~ 988Hz sawtooths-square signal
321 us 250000 us
TONE 17
Specific tone 500Hz ~ 1200Hz sawtooths-square signal
299 us 500000 us
TONE 18
Specific tone 500Hz ~ 1200Hz sawtooths-square signal
600 us 500000 us
TONE 19
Specific tone 1200Hz ~ 500Hz sawtooths-square signal
600 us 500000 us
TONE 20
Specific tone 2850Hz - 2400Hz square signal (ISO8201)
250000 us 250000 us
TONE 21
Specific tone 1200Hz - 500Hz square signal
500000 us 500000 us
TONE 21
Specific tone 1200Hz - 500Hz square signal
500000 us 500000 us
TONE 22
Specific tone 800Hz ~ 970Hz square signal
500000 us 500000 us
TONE 23
Specific tone 628Hz - 925Hz square signal
250000 us 250000 us
TONE 24
Specific tone 554Hz - 440square signal
100000 us 400000 us
TONE 25
Specific tone 670Hz - 845Hz square signal
250000 us 350000 us
TONE 26
Specific tone 440Hz - 554Hz square signal (French)
100000 us 400000 us
TONE 27
Specific tone 2850Hz - 0 square signal
500000 us 500000 us
TONE 28
Specific tone 970Hz - 0square signal (ISO8201)
250000 us 250000 us
TONE 29
Specific tone 925Hz - 0square signal
150000 us 600000 us
TONE 30
Specific tone 925Hz - 0square signal
250000 us 1000000 us
TONE 31
Specific tone 800Hz - 0square signal (ISO8201)
250000 us 1000000 us
TONE 32
Specific tone 660Hz - 0square signal (Swedish)
150000 us 150000 us
TONE 33
Specific tone 660Hz - 0square signal
6500000 us 13000000 us
TONE 34
Specific tone 554Hz - 0square signal
100000 us 400000 us
TONE 35
Specific tone 400Hz continuous
signal
TONE 36
Specific tone 628HZ
continuous signal
TONE 37
Specific tone 660HZ
continuous signal
TONE 38
Specific tone 750HZ
continuous signal
TONE 39
Specific tone 925HZ
continuous signal
TONE 40
Specific tone 970HZ
continuous signal
TONE 41
Specific tone 2400HZ continuous
signal
TONE 42
Specific tone 2850HZ continuous
signal
Supported Tone Types and Descriptions
General Features
✓TLPWAN low power consumption, two-way safe and stable wireless communication protocol
✓Standard, low cost lithium battery
✓6 years battery life thanks to advanced communication protocol
✓EN54-3, EN54-23, EN54-25
Indicator LEDs
LED Signal Meaning
LED Signal Pattern
Any error situation
(Tamper etc.)
Heart LED blinks once in every 10 seconds
Device in normal operation mode
Heart LED blinks once in every 20 seconds
Low battery warning
Heart Led blinks once in every 10 seconds
Network connection-disconnection
operation
Result of operation
Heart Led blinks twice in every 2 seconds
Positive, Heart Led on for 3 seconds
Negative, Heart Led off
Connection quality
Good connection; Heart LED blinks 3 times
Moderate connection; Heart LED blinks 2 times
Poor connection; Heart LED blinks once
No connectiob; Heart Led off
Link Testi
It is possible to measure the link quality between the device and the connected coordinator or router. For
this, press shortly on the button under the device. If the device is connected to a network, the LEDs will light
as noted below at the end of the procedure:
Changing/Testing Siren and Flasher Modes
Connection /Test Button
Flasher Turns On/Off when pressed long
Connection /Test Button
Flasher Mode changes when pressed shortly
Tamper+ Connection /Test Button
Siren Turns On/Off when both of them pressed
simultaneously
Tamper Key
Siren mode changes when pressed shortly
Network Connection Procedure
For a device to connect a network, such device must not be connected to any network. The connection status
of a device can be found out by means of the link test. Follow the steps below for connecting the device to a
network.
1. The connection permission on the coordinator or on the router must be on before the device is
connected to a network. Turn on the connection permission on the coordinator or on the router.
2. Press long (for 5 minutes) on the “Connection/Link” button under the device.
3. The device will start the connection procedure automatically. This procedure takes a about 20 to 60
seconds. The green LED will blink twice every 2 seconds during the procedure.
4. At the end of the procedure, the green LED will light for 3 seconds if the connection procedure is
successful, and the red LED will light for 3 seconds if the connection procedure is not successful.
Disconnection procedure
1. Press long (for 5 seconds) on the “Connection/Link” button under the device.
2. The device will start the disconnection procedure automatically. The green LED will light for 3
seconds at the end of the procedure.
EN 54-23 Visual Alarm Devices A –Intensive Volume Level Figure (max.)
Manufacturer Company and Main Service
*In compliance with AEEE regulations. This product is manufactured from recyclable and reusable high
quality parts and materials. Therefore, do not dispose of the product together with domestic or other wastes
at the end of its service lifetime. Take it to a drop-off point for the recycling of electrical and electronic
devices.
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul / Türkiye
Phone: +90 216 455 88 46 Facsimile: +90 216 455 99 06
www.bilgielektronik.com.tr
satis@bilgielektronik.com.tr
destek@bilgielektronik.com.tr
Warning: The products works only with Teknim TFP-121x, TFP-122x and TFP-123x Analogue
Addressed Fire Alarm panels.
Warning: Once the device is connected to the network, carry out the link test from the point where the
device will operate. The system will not operate properly if there is no connection at the link test. Change
the device’s location in such case.
Warning: If no LED lights at the end of the Link Test, this means the device is not connected to any
coordinator or router.

Other Teknim Fire Alarm manuals

Teknim TFS-1183R User manual

Teknim

Teknim TFS-1183R User manual

Teknim TFS-3191 Troubleshooting guide

Teknim

Teknim TFS-3191 Troubleshooting guide

Teknim TFS-1182R User manual

Teknim

Teknim TFS-1182R User manual

Teknim TFB-1166 v2 User manual

Teknim

Teknim TFB-1166 v2 User manual

Teknim TFA-1196 User manual

Teknim

Teknim TFA-1196 User manual

Teknim TFS-3191R Troubleshooting guide

Teknim

Teknim TFS-3191R Troubleshooting guide

Teknim TFB-1166 Instruction Manual

Teknim

Teknim TFB-1166 Instruction Manual

Teknim TFP3304 User manual

Teknim

Teknim TFP3304 User manual

Teknim TFS-3193 Series Troubleshooting guide

Teknim

Teknim TFS-3193 Series Troubleshooting guide

Teknim TFD-1260 Troubleshooting guide

Teknim

Teknim TFD-1260 Troubleshooting guide

Teknim TFS-3192R Troubleshooting guide

Teknim

Teknim TFS-3192R Troubleshooting guide

Popular Fire Alarm manuals by other brands

GST DC-9102E user guide

GST

GST DC-9102E user guide

LST SIM216-1 Specification sheet

LST

LST SIM216-1 Specification sheet

Simplex 4099-9032 installation instructions

Simplex

Simplex 4099-9032 installation instructions

INIM Electronics PREVIDIA-CS Series instruction manual

INIM Electronics

INIM Electronics PREVIDIA-CS Series instruction manual

Smartswitch FR-4000 installation manual

Smartswitch

Smartswitch FR-4000 installation manual

Electronics Ei407 manual

Electronics

Electronics Ei407 manual

Kidde Gemini II Design, Installation, Operation, and Maintenance Manual

Kidde

Kidde Gemini II Design, Installation, Operation, and Maintenance Manual

Autronica AutroGuard Multicriteria Protector V-430... Technical handbook

Autronica

Autronica AutroGuard Multicriteria Protector V-430... Technical handbook

Ziton zp1-f Series Quick operation guide

Ziton

Ziton zp1-f Series Quick operation guide

DSC WS4916 Series Installation and operation instruction manual

DSC

DSC WS4916 Series Installation and operation instruction manual

Apollo 45681-265 installation guide

Apollo

Apollo 45681-265 installation guide

Teletek electronics SensoIRIS BSOU Installation instruction

Teletek electronics

Teletek electronics SensoIRIS BSOU Installation instruction

Honeywell ESSER 804902 Installation instruction

Honeywell

Honeywell ESSER 804902 Installation instruction

Honeywell HW-TG7LAF02 Installation and operating guide

Honeywell

Honeywell HW-TG7LAF02 Installation and operating guide

Bosch FMC-300RW-GSRRD installation guide

Bosch

Bosch FMC-300RW-GSRRD installation guide

Pittway NOTIFIER LED-10N manual

Pittway

Pittway NOTIFIER LED-10N manual

Awex ROP 21 Assembly instructions

Awex

Awex ROP 21 Assembly instructions

Jade Bird JBE-2100 manual

Jade Bird

Jade Bird JBE-2100 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.