Teknim TSD-701 User manual

TSD-701 /
Ceiling Type Gas Detector
Mounting and User Manual
Issue Date: 29/09/2016 R:01
IMPORTANT WARNINGS
GENERAL
Before using the device read this
manual carefully. Keep it just in case of
necessity.
Abide all the rules and precautions stated in the
manual. Follow all the instructions one by one.
Keep the devices away from water and moisture
CONDITIONS
Do not energize the device above or below the given
limits of extreme hot or cold conditions,
Temperature: Between 0C and +55C
Relative Moisture: %0- 95 concentrated
SERVICE
In case of any malfunction or below conditions contact
with your authorized service,
When Mains cable or the plug is harmed,
Contact of device with a fluid,
Exposure of rain and water,
Fell down of device or harmed outer cover,
Serious performance fall on the device,
Depending on the instructions stated in manual, if
your device not working properly, further usage or
possible wrong usage may cause other
malfunctions. Contact with your authorized service
in such terms.
INFORMATION RELATING TO USAGE ERRORS
Do not allow to change the opening or setting up your
device by unauthorized persons. As a result of such a
situation, your device can start working differently
compared to the first case.
SECURITY CHECK
Please ask your dealer to check that the service is
working properly and safe conditions.
.
TO BE CONSIDERED AND CONSUMER CAN DO
TO MAINTAIN, REPAIR AND CLEANING
- Do not attempt to repair the device yourself,
because if you open the oven door or tampering
can be exposed to possible electric shock or cause
a malfunction of the device.
- If a fault occurs, please contact your dealer or
authorized service center. Device technical
intervention must be carried out by authorized
service personnel qualified.
- The device should be cleaned with a damp cloth.
Never spray, polish, do not use any chemicals such
as detergents.
- Alcohol, thinner, cologne, sprays, lighter too
intense, pungent cleaning agents do not mislead
the device to false alarms and may cause
deterioration of the detector. In addition, gas
detection holes must be clean and dry.
TRANSPORTATION
Device must be carefully transported avoiding all
physical bump, stroke and possible fluid entry.
Malfunctions that caused by improper transportation is
not under warranty.
Model
TSD-701
Supply Voltage
Type
IP Rating
Compatible Standard
12-24 VDC
A
IPX2D
TS EN 50194-1
Contact Output
1 pcs, NC or NO
Startup Time
3 minutes
Normal Condition Led Color
Green
Error Condition Led Color
Yellow
Alarm Condition Led Color
Red
Alarm Level (Natural gas)
%10 LEL
Output Relay
30 V DC, 50mA
Alarm Output
Alarm Buzzer Sound Level
Solid State Relay +
Voice and flashing leds
85 dB
NO
NC

EQUIPMENT LOCATION SELECTION, INSTALLATION AND CONNECTION
1. To mount your device must be performed by authorized person.
2. Selecting the mounting location of the device:
- From any device powered by natural gas will be far away at least 1.5 meters from the projection of a place.
- In case of a gas leak it would be a likely place to be the most accumulation of gas.
- The detector will NOT be over direct cooked meals, sink and toilet bowl (which should be at least 1.5
meters away).
- The detector will NOT be adjacent Aspirator, fan and ventilation (which should be at least 1.5 meters
away).
3. Remove the head of the detector attached to base
by turning it counter clock wise until you reach the
short line on the base (1), then pull it off (2).
4. Use at least 2 opposite ones from 4 of the screw
holes on the base to fasten it.

5. Do the wiring according to schematic shown below
.
TSD-701 NO TSD-701 NC
6. Place the detector head back. Make sure the short line on head fits with long one on the base.
7. Energise the detector. If there is no alarm condition the LED on detector will be green color.
TEST
1. After mounting of detector is done and it’s operating, gas exposed by a lighter to the convection window.
2. Detector turns to alarm mode in 30-40 seconds. It shut down the output and beeps continuously. Also LED
turns green to red.
3. Gas alarm density has been adjusted due to TS EN 50194-1 criteria. Detector stops alarm condition and turns
normal operating mode when gas density is decreased.
4. If the gas test is applied frequently, it shorten the life of detector reduces the sensitivity.
5. Detector that passed the test can be integrated to the system.
NOTES ON USING OF DETECTOR
TSD-701 series detectors must be used for detecting the type of gas which is written on it.
Average life of the detector and sensor are 5 years. It’s recommended that all detectors be tested in every
year.
LED INFORMATION
Visual markings
Red LED
Gas Alarm
Yellow LED
Sensor Error
Green LED Continuous
Normal Operation
Green LED Flashing
Sensor Prepares
Audible Alerts
Continuous Beep
Gas Alarm
Cut Alert Sound
Sensor Error

WARNING –IN THE CASE OF GAS ALARM
Stay calm and act as follow
- do not operate any switch
- do not use any kind of phone in the location of the gas leakage
- open windows
- stop the gas leakage if possible or leave the place and call a fire company
Model
Alarm
Condition
Contact
Output
Supply
Standby Current / Alarm
Current
Operation
Temperature
(°C)
Startup
Time
Dimensio
ns (mm)
Body Material
TSD-701
%10 LEL
NC / NO
12 –24
VDC
12 VDC/ 100mA / 100mA
24 VDC/ 50mA / 50mA
-10 ~ +55
3 Mins
Ø110,
h50
White Color ABS
MANUFACTURER
Bilgi Elektronik San. Ve Tic. A.Ş.
Address :
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi No:1 Kat:2 No:32 Ümraniye/İstanbul
Tel: +90 216 455 88 46 Fax: +90 216 455 99 06 www.bilgielektronik.com.tr
Sales: sales@bilgielektronik.com.tr Technical Support: support@bilgielektronik.com.tr
Other Teknim Gas Detector manuals