manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. TESTO
  6. •
  7. Measuring Instrument
  8. •
  9. TESTO 0590 0003 User manual

TESTO 0590 0003 User manual

testo clamp meter adapter 0590 0003
Instruction manual [en]
0970 0702 en 02 V01.00
Overview
Instrument
1 Button for offset compensation
2 Clamp opener
3 Clamp meter
4 Battery compartment (at rear)
5 LED
6 ON/OFF button
7 Measuring cable to testo 760
Explanation of icons
Observe prior to use!
• The instruction manual contains information and instructions which are necessary for
operating and using the instrument safely. Before using the instrument, read the instruction
manual carefully and comply with all aspects of it. Keep this document to hand so that you
can refer to it when necessary. Forward this documentation to any subsequent users of the
instrument.
• If the manual is not followed, or if you fail to observe the warnings and instructions, there is
a risk of fatal injury to the user and damage to the instrument.
Safety instructions
The instrument may only be used by trained personnel. During all operations, please observe
the Employers' Liability Insurance Association provisions for health and safety at work.
• In order to prevent electric shock, take safety precautions when working with voltages
greater than 120 V (60 V) DC or 50 V (25 V) rms. AC. These values are the limits for contact
voltages in accordance with DIN VDE (values in brackets apply to restricted areas, for
example agricultural sectors).
• The measuring instrument is only to be used in electrical circuits with up to 600 V nominal
voltage.
• Measurements may only be taken near electrical installations under the direction of an
authorised qualified electrician - never alone.
• The instrument may only be touched at the designated grip areas, the display elements
must not be covered. If the instrument is not held by the designated grip areas, or outside
the limits of the grips, the operator will be at risk of electric shock.
• If operator safety can no longer be guaranteed, the instrument is to be taken out of service
and prevented from being inadvertently used. This is the case if the instrument:
- Is obviously damaged. e.g.
- Housing breakages
- Defective measurement cables
- Leaking batteries
- Does not carry out the required measurements
- Has been stored too long in unfavourable conditions
- Has been exposed to mechanical stresses during transit.
• Protect from direct solar radiation to prevent the instrument from heating up. This is the
only way to guarantee the instrument will function perfectly and have a long service life.
• If the instrument needs to be opened, this may only be carried out by a qualified specialist.
Prior to opening, the instrument is to be switched off and disconnected from all electrical
circuits.
• Maintenance work that is not described in this documentation must only be carried out by
trained service technicians.
• If the instrument is modified in any way, operational safety cannot be guaranteed.
• Modifications to the instrument will completely void any right to claims under the manufac-
turer’s guarantee and warranty.
• The clamp meter adapter must not be used when the battery compartment is open.
• Check and replace batteries, if necessary, before use.
• Always store in a dry place.
• The instrument must not be used in explosive environments.
• Always check the instrument is in perfect working order prior to and after use. Test the
instrument on a known current source.
• If there is any battery leakage, the instrument must not be used until it has been checked by
our Customer Service.
• The battery acid (electrolyte) is highly alkaline and electrically conductive. Risk of acid burn!
If the battery acid comes into contact with your skin or clothing, thoroughly rinse the areas
affected immediately with plenty of water. If battery acid gets into your eyes, rinse them
immediately with plenty of water and seek medical advice.
Intended use
The instrument may only be used under the conditions and for the purpose for which it was
designed:
• The instrument complies with the CAT IV measurement category and rated voltage of 600 V
to earth.
The CAT IV measurement category is used at the source of low voltage installations, e.g. build-
ing connection, main fuse, and meter.
The instrument may only be used in the fields of application defined in the instruction manual.
Any application deviating from this is considered to be improper and unchecked use and may
result in accidents or instrument damage. Any improper use will completely void any right to
claims under Testo’s guarantee and warranty.
The manufacturer is not responsible for damage to property or personal injury caused by the
following:
• Failure to comply with the instruction manual
• Modifications to the instrument not approved by the manufacturer
• The use of spare parts not approved by the manufacturer
• Use when under the influence of alcohol, drugs, or medication
The instrument must not be used for the following purposes:
• In potentially explosive atmospheres: the instrument is not explosion-proof!
• When it rains: risk of electric shock!
Technical data
Specifications valid at 23 °C ± 5 °C, <80% relative humidity:
Feature Value
Measuring range 1.0-400 A AC RMS, 1-400 A DC
DC accuracy (offset-com-
pensated and conduc-
tor-centred)
± (2% + 0.5 A) at +23 °C; ± 5 °C at <80% RH
AC accuracy ± (2% + 0.5 A), 45-400 Hz, Crest Factor 3
at +23 °C; ± 5 °C at < 80% RH
Temperature coefficient ± (0.05 x specified accuracy per 1 °C (0-18 °C; 28-50 °C)
Transfer function 1 mV per 1 A
Height To 2000 m
Measurement category CAT IV/600 V
Level of contamination 2
Protection class IP 40
Power supply 3 x 1.5 V (AAA/IEC LR03)
Battery life approx. 100 h (continuous operation with alkaline batteries)
Output signal 1 mV per 1 A DC or AC
Max. permitted
conductor current
600 V
Max. conductor size Ø 30 mm (1.18 in.)
Load impedance > 1 M; 100 pF
Automatic power off func-
tion (APO)
after approx. 15 min.
Dimensions (WxHxD) 210 mm x 100 mm x 42 mm
Temperature range Operation: 0 to 50 °C
Storage: -15 to 60 °C
Humidity 0 to 95% (0-30 °C)
0 to 75% (30-40 °C)
0 to 45% (40-50 °C)
Weight Approx. 370 g
Standards WEEE 2012/16/EU, EMV 2014/30/EU, EN 61326-1, Low Voltage
Directive 2014/35/EU with the standard EN 61010-2-032, and
insulation complying with class II IEC 536/DIN EN 61140
Certifications TÜV GS, CE, CSA
Warranty Duration: 2 years
Warranty terms: see website www.testo.com/warranty
Operating the instrument
Switching the instrument on
> Press the on/off button briefly.
- The instrument switches on
Switching the instrument off
> Press the on/off button briefly.
Automatic switch-off: after approx. 15 minutes of no button being pressed.
Carrying out a test
The contents of the testo 760 documentation must have first been read and understood.
Measuring direct currents (DC)
1. Connect the testo 760 and clamp meter adapter to the measurement cables: black cable to
the COM jack; red cable to jack V//diode/capacity.
2. Switch on the testo 760.
3. Activate DC mV measuring mode for current measurement: press key V 4 x.
4. Switch on the clamp meter adapter.
- A green or red LED indicates readiness for operation.
5. Close the clamp jaws of the clamp meter adapter. Make sure that no conductor is enclosed.
> Compensate the direct current offset: press ZERO < 1 second.
6. Place the cables being measured centrally within the clamp.
- The measured value is shown on the LC display.
Measuring alternating currents (AC)
1. Connect the testo 760 and clamp meter adapter to the measurement cables: black cable to
the COM jack; red cable to jack V//diode/capacity.
2. Switch on the testo 760.
3. Activate AC mV measuring mode for current measurement: Press button V3 x.
4. Switch on the clamp meter adapter.
- A green or red LED indicates readiness for operation.
5. Place the cables being measured centrally within the clamp.
- The measured value is shown on the LC display.
- The displayed mV value indicates the measured current in amperes.
www.testo-international.com
Attention! Warning about a
danger spot, refer to instruction
manual
Caution! Dangerous voltage,
risk of electric shock
The product is certified for the
USA and Canada markets to
applicable American and Cana-
dian standards.
Continuous double or rein-
forced insulation in accordance
with category II DIN EN 61140/
IEC 536
This product has been tested to
the requirements of CAN/CSA-
C22.2 No. 61010-1, second
edition, including Amendment
1, or a later version of the same
standard incorporating the
same level of testing require-
ments.
Conformity mark, verifies
compliance with the valid
EU Directives: EMC Directive
(2014/30/EU) with the stand-
ard EN 61326-1, Low Voltage
Directive (2014/35/EU) with the
standard EN 61010 2-032
Certified safety (verified by TÜV
Rheinland)
The instrument complies with
the WEEE Directive (2012/16/
EU)
Application around and removal
from HAZARDOUS LIVE con-
ductors is permitted.
Service and maintenance
Replacing the batteries
If the battery voltage is high enough, the LED lights up green. When batteries start running out,
the LED lights up red, which means the batteries need changing soon.
1. Switch the instrument off.
2. Fully disconnect the instrument from all measurement circuits.
3. Open the battery compartment: undo the screw and remove the battery compartment cap.
4. Remove the spent batteries.
5. Insert new batteries in accordance with the battery icon.
6. Close the battery compartment: put the battery compartment cap on and tighten the screw.
Maintenance
When operated in accordance with the instruction manual, the instrument does not require any
particular maintenance. If a malfunction occurs during operation, the ongoing measurement
should be stopped immediately. Send the instrument to Testo Service for checking.
Storage
- Make sure the instrument is stored in a dry place.
- If the instrument is not in use for a significant period of time: remove the batteries in order to
prevent any danger or damage due to any potential leaking of the batteries.
Cleaning
- Always switch off the instrument prior to cleaning and disconnect it from external voltage,
other connected instruments (e.g. test piece, and control devices, etc.), or a clamped con-
ductor.
> Wipe the instrument with a damp cloth and a small amount of mild household detergent.
Never use any harsh cleaning agents or solvents to clean the instrument! After being cleaned,
the instrument must not be used until it has completely dried.
Protecting the environment
> Dispose of faulty rechargeable batteries/spent batteries in accordance with the valid legal
specifications.
> At the end of its useful life, send the product to the separate collection for electric and elec-
tronic devices (observe local regulations) or return the product to Testo for disposal.
www.testo-international.com

Other manuals for 0590 0003

1

Other TESTO Measuring Instrument manuals

TESTO 515 User manual

TESTO

TESTO 515 User manual

TESTO 405-V1 User manual

TESTO

TESTO 405-V1 User manual

TESTO 0636.9835 User guide

TESTO

TESTO 0636.9835 User guide

TESTO 320 User manual

TESTO

TESTO 320 User manual

TESTO 606-1 User manual

TESTO

TESTO 606-1 User manual

TESTO Saveris T1 User manual

TESTO

TESTO Saveris T1 User manual

TESTO 810 User manual

TESTO

TESTO 810 User manual

TESTO 511 User manual

TESTO

TESTO 511 User manual

TESTO 0519.0816 User manual

TESTO

TESTO 0519.0816 User manual

TESTO Smart Probes 805i Installation manual

TESTO

TESTO Smart Probes 805i Installation manual

TESTO 545 User manual

TESTO

TESTO 545 User manual

TESTO 316-2-EX User manual

TESTO

TESTO 316-2-EX User manual

TESTO 300 User manual

TESTO

TESTO 300 User manual

TESTO 327 User manual

TESTO

TESTO 327 User manual

TESTO 206 User manual

TESTO

TESTO 206 User manual

TESTO 6381 User manual

TESTO

TESTO 6381 User manual

TESTO Saveris User manual

TESTO

TESTO Saveris User manual

TESTO 915i User manual

TESTO

TESTO 915i User manual

TESTO 440 User manual

TESTO

TESTO 440 User manual

TESTO 608 - H1 User manual

TESTO

TESTO 608 - H1 User manual

TESTO 556 User manual

TESTO

TESTO 556 User manual

TESTO 440 User manual

TESTO

TESTO 440 User manual

TESTO 0564 2552 01 User manual

TESTO

TESTO 0564 2552 01 User manual

TESTO 300 XXL User manual

TESTO

TESTO 300 XXL User manual

Popular Measuring Instrument manuals by other brands

Precision Digital Corporation Survivor PD662 instruction manual

Precision Digital Corporation

Precision Digital Corporation Survivor PD662 instruction manual

Vega VEGAPULS WL 61 operating instructions

Vega

Vega VEGAPULS WL 61 operating instructions

Fluke 16 Calibration information

Fluke

Fluke 16 Calibration information

Anritsu MG9637A Operation manual

Anritsu

Anritsu MG9637A Operation manual

Extech Instruments CO240 user manual

Extech Instruments

Extech Instruments CO240 user manual

Alf Noyes OLS Series user guide

Alf

Alf Noyes OLS Series user guide

UEi C255 instruction manual

UEi

UEi C255 instruction manual

Kewtech KEW337 instruction manual

Kewtech

Kewtech KEW337 instruction manual

SDT International SDT340 user manual

SDT International

SDT International SDT340 user manual

Hanna Instruments HI96786 user manual

Hanna Instruments

Hanna Instruments HI96786 user manual

Burster Resistomat 2323 manual

Burster

Burster Resistomat 2323 manual

Rion NL-62 Quick instruction manual

Rion

Rion NL-62 Quick instruction manual

Extech Instruments 451212 instruction manual

Extech Instruments

Extech Instruments 451212 instruction manual

MSA Chillgard RT instruction manual

MSA

MSA Chillgard RT instruction manual

G.R.A.S. 40HH instruction manual

G.R.A.S.

G.R.A.S. 40HH instruction manual

Laser Technology TruPulse 200X Quick reference guide

Laser Technology

Laser Technology TruPulse 200X Quick reference guide

Dash SMARTSTORE DSMS400 instruction manual

Dash

Dash SMARTSTORE DSMS400 instruction manual

Endress+Hauser DipFit W CPA 111 operating instructions

Endress+Hauser

Endress+Hauser DipFit W CPA 111 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.