
__
Model 391l/39
Dehumidify
Switch and Indicator (Figure 3-3)
H
Ihe
dehumidify switch will enable the refrigeration
system
if
the refrigeration switch is currently off. When
controlling humidity, the dehumidification switch should be in
the
ON
position for most applications. The dehumidification
light will cycle on and
off
as
the humidity controller toggles
between umidify and dehumidify. The dehumidify light will be
de-energized when the system
is
in Defrost mode.
Humidity is removed from the cabinet by the refrigeration
evaporator coiL Moisture accumulates on the coil and is collect-
ed into
the
evaporator pan. The accumulated moisture
is
then
plumbed
to
the back
of
the cabinet, which can be emptied to a
floor drain, or an evaporative device.
Audible
Humidity
Alarm
and
Indicator
Display (Figure 3-3)
I The humidity alarm is a function
of
the humidity
con
troller, Figure 3-4. When the cabinet humidity goes outside
the set parameters
of
the controller, L3 indicator on the con-
troller lights, the audible alatm sounds, and the humidity alarm
indicator (Figure 3-3, Item I) on the control panel lights.
HoldlRun
Key
J Pressing the HoldlRun key
(Figure 3-4) on the controller
silences the audible alarm and
extinguishes the humidity alarm
ind~
cator and
the
L3
indicator on the con-
troller. A3HIJA3LO flashes on the
lower display until the cabinet humid-
ityretums
tottle
system setpoint.
Note: The humidity controller's high
and low limits are set by the factory
at 100% and 0%. Therefore, the sys-
tem will go into the alarm state when
--WATLOW
rr
B5~
ll=
PROCESS
~J
LB5]
l1
l2 l3
l4
DEV
%OUl
~.+~
I~
Figure
3-4
the humidity exceeds these percentages by one percent. When
operating the incubator near these high or low humidity levels,
frequent alarms
may
occur. This will require that
the
con-
troller's
high
or low limit be reset to three or four percent over
the
high
limit, or three or four percent under the low limit.
Refer to the Watlow
User's
guide provided. Refer also to the
__
~
factory configuration records lqgated at the (;llclof
Sect!Ql'l-"-2,--,0"",f
this manual.
and Operation
3.2
Setting the Incubator's Operating Temperature
(Figure 3-5)
K L The Watlow temperature
WAllOW
controller's upper numerical ®
~cz~qJ
display shows the actual temperature
inside the incubator chamber. The
lower display shows the temperature
setpoint.
Changing the Setpoint
M
To
raise or lower the set-
point, press the up
or
down
arrow. Temperatures are set in
.IOC
increments.
(b)-+--'3I~.D-.
l1
l2
l3
L4
DEV
%OUT
ELAyj
[HOLD]
~
RUNJ
~
SF.RIES982
Figure 3-5
3.3
Setting the
Incubator's
Operating Humidity
(Figure
3-6)
-~E/~l
N 0 The Watlow humidity ®
controller's upper numerical
PROCESS~
display shows the actual humidity inside
@-t--t
DEY
85
the incubator. The lower display shows
the humidity setpoint.
P
To
raise the setpoint, press the
up or down arrows. Humidity is set
in one percent increments. ®
3.4
Programming the
controllers
L1
L2 L3
L4
The Watlow temperature and humidity controllers have
been set at the factory to operate the incubator within the
sped
fications listed in Section 6
of
this manual. Reference copies
of
the Watlow configuration records are included at the end
of
Section 2
of
this manual.
To
prevent tampering, mechanical and software lockouts
are employed in the system. These lockouts must only be
removed by persons skilled in configuring controller software.
~
..
__
......
_________________
_
& Makingprogram changes to either tile tempera-
, ture or humidity controllers will seriously alter tile
• performance
of
the
incubator andtherefore must
be made only by qualifle(/persons. The con-
trollers should
not
be re-configured withoutfirst
consulting Thermo Forma Service Department, at
1-888-213-1790.
3-2
-I