Tools Required
Receiving, Storing and Handling
1. Inspect materials for damage incurred during shipping.
2. Report damages to the carrier for selement.
3. Idenfy parts against the packing list to ensure the proper
type and quanty has been received.
Dimensions
Installaon Precauons
• To minimize the potenal for arcing and re caused by product
damage or improper installaon use ground-fault protecon.
The Naonal Electrical Code (NEC) and Canadian Electrical
Code (CEC) require ground-fault protecon of equipment for
each branch circuit supplying electric heat tracing.
• Installaon must comply with Thermon requirements and
be installed in accordance with the NEC, CEC, or any other
applicable naonal and local codes.
• Component approvals and performance rangs are based on
the use of Thermon specied parts only. User supplied power
connecon ngs must be listed or cered for intended use.
• De-energize all power sources before opening enclosure.
• Keep ends of heang cable and kit components dry before and
during installaon.
• Individuals installing these products are responsible for
complying with all applicable safety and health guidelines.
Proper personal protecve equipment, or PPE, should be
ulized during installaon. Contact Thermon if you have any
addional quesons.
IP66/Type 4X -60°C ≤ Ta ≤ +55°C
Listed Heat Tracing Cable System 137M
Ordinary & Hazardous Locaons
Class I, Division 2, Groups A, B, C, & D
Class II, Division 2, Groups F & G, Class III
Cercaons/Approvals
Kit Contents
Item Quanty Descripon
1 1
Expediter Assembly
Support Cap with O-Ring
Threaded Grommet Compressor
Grommet
Support Base with O-Ring
2 1 Juncon Box Lid
3 1 Juncon Box Base with O-Ring
41Nut
51Banding
6 1 Banding Guide
71
Terminal Blocks with DIN Rail
(Refer to terminal block specicaons for
maximum allowable wire size)
8 1 Juncon Box Cord
9 1 Terminal Block Jumper
Terminator DP-M
9
1 2
6
4
3
8
5
7