2
Tools Required
Terminator-LN-Tool
(order separately)
3 mm
8 mm 28 mm
29 mm
33 mm
Item Quanty Descripon
1 1
Expediter Assembly
Grommet Compressor
Grommet
Support Base with O-Ring
2 1 Splice Cap
3 1 Banding Guide
4 1 Banding
TerminatorTM ZS/ZE INSTALLATION PROCEDURES
Kit Contents
Order Separately for End Terminaon
PETK Power and End Terminaon Kits (per cable)
PETK-1 for BSX, RSX, VSX, VSX-HT
PETK-2 for KSX, HTSX,
PETK-3 for FP, HPT
Item Quanty Descripon
1 1 RTV Tube
2 1 Power Connecon Boot
3 1 End Cap
4 1 Tape Strip Teon 6" (PETK-3 only)
5 1 End Terminaon Cauon Label
61GRW-G Grommet (PETK-3 only)
Order Separately for Inline Splice
SCTK Splice Connecon Terminaon Kits (per cable)
SCTK-1 for BSX, RSX, VSX, VSX-HT
SCTK-2 for KSX, HTSX,
SCTK-3 for FP, HPT
Item Quanty Descripon
1 3 Splice Connecon Boots
2 2 Small Crimps
3 1 Large Crimp
4 2 Small Crimp Insulators
5 2 Silicone Caps
63Ground Sleeves
7 1 RTV Tube
Cercaons/Approvals
1725 II 2 GD Ex eb IIC T6...T4, Ex tb IIIC T85°C...T135°C
FM 10ATEX0058X
IP66 -60°C ≤ Ta ≤ +55°C
Ordinary & Hazardous Locaons
FMG 10.0022X Ex eb IIC T6...T4
Ex tb IIIC T85°C...T135°C
Warnings
• Due to the risk of electrical shock, arcing and re caused
by product damage or improper usage, installation or
maintenance, a ground-fault protecon device is required.
• Installaon must comply with Thermon requirements and be
installed in accordance with the regulaons as per the norm
EN IEC 60079-14 for hazardous areas (where applicable), or
any other applicable naonal and local codes.
• Component approvals and performance rangs are based on
the use of Thermon specied parts only.
• De-energize all power sources before opening enclosure.
• Avoid electrostac charge. Clean only with a damp cloth.
• Keep ends of heang cable and kit components dry before
and during installaon.
• Minimum bending radius of heang cable is 32 mm (except
HPT is 57 mm and FP is 19 mm).
• Individuals installing these products are responsible for
complying with all applicable safety and health guidelines.
Proper Personal Protective Equipment (PPE) should be
ulized during installaon. Contact Thermon if you have any
addional quesons.
Tcode Instrucons
Temperature code is based on the rang of the electrical heat
tracing cables for which the connecon kits are intended to
be used.
Dimensions
A
inch (mm)
B
inch (mm)
C
inch (mm)
D
inch (mm)
Terminator
ZS/ZE 3” (75 mm) 3” (75 mm) 3-1/2”
(90 mm)
7-3/4”
(200 mm)
D
B
C
A
Terminator has addional hazardous area approvals including:
• GGTN • Kazakhstan
The following installaon procedures are guidelines for the
installation of the In Line Splice/End Termination Kit. For
translaons other than English and local language translaon
provided here, please contact Thermon. The English language
installaon procedure shall govern.
1 2
4
3
2 43 51 6
2 43 5 61 7