TSC 7320 Transfer Switch Controller
PM180 REV 0 23/02/10 Thomson Power Systems
13
3.4. ATS OPERATION MODE DESCRIPTIONS
Mode Description ATS Mechanism
Control Outputs
Engine Start Output
AUTO ATS automatically transfers to Generator (Source 2) during a
Utility (Source 1) failure and automatically returns power to utility
once restored
Outputs automatically operate
ATS mechanism per automatic
sequence of operation
Output contact closes to start
engine during a utility (source
1) failure and opens to stop
engine once utility power has
transferred back to the load.
STOP MODE ATS will immediately start transferring to utility and stay there. The
ATS will not automatically operate during a utility power failure
Outputs momentarily energize to
move ATS mechanism to the
Utility position. If the mechanism
is moved away from Utility, the
controller will automatically move
it back to Utility.
Output is disabled - engine will
not start during a utility power
failure1
Engine will stop if it was
previously running
TEST MODE ATS will not automatically operate during a utility power failure,
and The ATS will transfer to utility if there is a gen power failure.
ATS cannot be operated manually as the controller will keep the
breaker on utility.
Outputs momentarily energize to
move ATS mechanism to the
Utility position. If the mechanism
is moved away from Utility, the
controller will automatically move
it back to Utility.
Output is enabled but engine
will not start during a utility
power failure1.
Engine will continue to run
unless there is a fault.
MANUAL ATS will not automatically operate during a utility power failure,
and The ATS will transfer to utility if there is a gen power failure.
ATS cannot be operated manually as the controller will keep the
breaker on utility.
Outputs momentarily energize to
move ATS mechanism to the
Utility position. If the mechanism
is moved away from Utility, the
controller will automatically move
it back to Utility.
Output is enabled but engine
will not start during a utility
power failure1.
Engine will continue to run
unless there is a fault.
SERVICE
DISCONNECT
(Service
Entrance
Only-US
Market ATS)
ATS transfers to neutral position to disconnect power to the load.
ATS will not automatically operate during a utility power failure.
Note:
When the Service Disconnect signal is removed, the transfer
switch will immediately return to the utility, and the controller will
remain in STOP mode. When required, put the controller back in
Outputs momentarily energize to
move ATS mechanism to the
neutral position.
Output is disabled - engine will
not start during a utility power
failure1. Engine will stop if it
was previously running
ON LOAD
TEST
When ONLOAD TEST mode is initiated, a utility power failure
condition will be simulated which will cause engine to start and
ATS will transfer to generator supply. When TEST mode is
terminated, ATS will transfer back to utility supply and engine will
stop
Outputs automatically operate
ATS mechanism per automatic
sequence of operation
Output contact closes to start
engine during the ONLOAD
TEST mode. Output
automatically opens when test
mode is terminated and ATS is
back on utility power
EXERCISE
ON LOAD
TEST
When ONLOAD TEST mode is initiated, a utility power failure
condition will be simulated which will cause engine to start and
ATS will transfer to generator supply. When TEST mode is
terminated, ATS will transfer back to utility supply and engine will
stop
Outputs automatically operate
ATS mechanism per automatic
sequence of operation
Output contact closes to start
engine during the ONLOAD
TEST mode. Output
automatically opens when test
mode is terminated and ATS is
back on utility power
MANUAL OFF
LOAD
TEST
When OFF LOAD TEST mode is manually initiated, engine will
start and run, but the ATS will not transfer to the generator. When
OFF LOAD TEST mode is terminated, engine will stop
Outputs do not change state
even if utility or generator supply
fails
Output automatically closes to
start engine during the OFF
LOAD test mode. Output
automatically opens when test
mode is terminated
EXERCISE
OFF LOAD
TEST
When OFF LOAD TEST mode is initiated, engine will start and
run, but the ATS will not transfer to the generator. When OFF
LOAD TEST mode is terminated, engine will stop
Outputs do not change state
unless utility or generator supply
fails in Off Load test mode
Output automatically closes to
start engine during the OFF
LOAD test mode. Output
automatically opens when test
mode is terminated
EXERCISE
SCHEDULE
When an EXERCISE SCHEDULE occurs, the ATS will perform an
exercise test on the pre-selected calendar date and time. The
Generator will operate on load or off load as selected and will
continue to run for the Exercise duration period as selected. If a
re-occurring Exercise mode is selected, ATS will repeat an
exercise test based on the calendar dates and times as selected.
Outputs operate ATS mechanism
per automatic sequence of
operation if programmed for ON
LOAD TEST operation.
Output contact closes to start
engine during the EXERCISE
test mode. Output
automatically opens when
exercise mode is terminated