Titon aurastat V User manual

ventilation systems
aurastat® V
TP526
HRV ControllerProduct Manual
EN

Contents
When this document
is viewed as a PDF the
headings & sub headings on
this page are hyperlinks to the content.
Additionally the page numbers in this
document are hyperlinks back to this
contents page.
Warnings, Safety Information and Guidance
Important Information . . . . . . . . . . . . . . . . . . . . . . 3
Product Overview
Product Description. . . . . . . . . . . . . . . . . . . . . . . . . 5
Packaging Contents. . . . . . . . . . . . . . . . . . . . 5
Feature Descriptions . . . . . . . . . . . . . . . . . . . . . . . . 5
24 Hour Clock . . . . . . . . . . . . . . . . . . . . . . . . . 5
Day of Week Display . . . . . . . . . . . . . . . . . . . 5
Backlight Brightness . . . . . . . . . . . . . . . . . . . 5
Boost Overrun Timer . . . . . . . . . . . . . . . . . . . 5
Boost Delay Timer . . . . . . . . . . . . . . . . . . . . . 5
Boost Inhibit. . . . . . . . . . . . . . . . . . . . . . . . . . 5
Internal Humidity Sensor . . . . . . . . . . . . . . . 5
Filter Change Alert. . . . . . . . . . . . . . . . . . . . . 6
4 x Fan Speeds. . . . . . . . . . . . . . . . . . . . . . . . 6
Fan Speed Display . . . . . . . . . . . . . . . . . . . . . 6
Boost Alert . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Summer Mode . . . . . . . . . . . . . . . . . . . . . . . . 6
SUMMERboost® . . . . . . . . . . . . . . . . . . . . . . . 6
Summer By Pass. . . . . . . . . . . . . . . . . . . . . . . 6
Duct Heater Control . . . . . . . . . . . . . . . . . . . . 6
2 x Proportional Sensor Inputs. . . . . . . . . . . 6
3 x Volt Free Inputs . . . . . . . . . . . . . . . . . . . . 6
2 x Live Switch Inputs . . . . . . . . . . . . . . . . . . 6
Frost Protection Program . . . . . . . . . . . . . . . 6
HRV Run Timer . . . . . . . . . . . . . . . . . . . . . . . . 6
Holiday Mode. . . . . . . . . . . . . . . . . . . . . . . . . 6
Multiple InternalTemperature Sensors. . . . 6
Installation
Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
aurastat® V . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Connections Access. . . . . . . . . . . . . . . . . . . 7
aurastat® V . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
HRV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
User Interface
Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Display Icons. . . . . . . . . . . . . . . . . . . . . . . . . . 9
Menu System . . . . . . . . . . . . . . . . . . . . . . . . . 9
Menu Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Commisioning
Quick Start Guide. . . . . . . . . . . . . . . . . . . . . . . . . . 11
Setup
Menu Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SETUP1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SETUP2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SETUP3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
RESET4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Installed Conguration. . . . . . . . . . . . . . . . . . . . . 21
SETUP1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SETUP2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SETUP3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Menu Maps
SETUP1 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . 22
SETUP1 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . 24
SETUP2 1 of 4 . . . . . . . . . . . . . . . . . . . . . . . . 26
SETUP2 2 of 4 . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP2 3 of 4 . . . . . . . . . . . . . . . . . . . . . . . . 30
SETUP2 4 of 4. . . . . . . . . . . . . . . . . . . . . . . . 32
SETUP3 1 of 2. . . . . . . . . . . . . . . . . . . . . . . . 34
SETUP3 2 of 2. . . . . . . . . . . . . . . . . . . . . . . . 36
RESET4 1 of 1. . . . . . . . . . . . . . . . . . . . . . . . 38
Routine Maintenance
Cleaning Exterior . . . . . . . . . . . . . . . . . . . . . 39
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2

Warnings, Safety Information and Guidance
Important Information
Important: read these instructions fully before the installation of this appliance
1. This manual covers the operation of the HRV control system only, it must therefore be read
in conjunction with the relevant heat recovery unit Product Manual.
2. Installation of the appliance and accessories must be carried out by a qualied and suitable
competent person and be carried out in clean, dry conditions where dust and humidity are
at minimal levels.
3. All wiring must conform to current I.E.E. Wiring Regulations and all applicable standards
and Building Regulations.
4. aurastat®, control & communication cable access to the HRV is via the tted cable gland(s)
which are suitable for Ø3- 6mm cable.
5. aurastat® control & communication cable - Unshielded 4 Core 18-24AWG Stranded, Tinned
Copper.
6. Control & communication cables should not be placed within 50mm or on the same metal
cable tray as any 230V lighting or power cables.
7. Ensure all cable glands are fully tightened.
8. The unit must be stored in a clean and dry environment. Do not install the appliance in
areas where the following may be present or occur;
• Excessive oil or a grease laden atmosphere,
• Corrosive or ammable gases, liquids or vapours,
• Ambient temperatures above 40°C or below -5°C,
• Humidity levels above 90% or is a wet environment.
9. The appliance is not suitable for installation to the exterior of the dwelling.
10. This appliance can be used by children aged from 8 years and above and persons with re-
duced physical, sensory or mental capabilities or lack of experience and knowledge if they
have been given supervision or instruction concerning use of the appliance in a safe way
and understand the hazards involved.
11. Children should be supervised to ensure that they do not play with the appliance.
3

Product Overview
Product Description
The aurastat®V is a programmable controller and display for commissioning and monitoring a Titon HRV. The aurastat®V
is connected to the HRV via a wired connection.
Dimensions
Packaging Contents
Inspect the unit when taking delivery. Check the unit for damage and that all accessories have been supplied. Package
supplied with:-
1 x aurastat®V controller.
1 x cable tie.
1 x Product Manual.
Any shortages or damage must be immediately reported to the supplier.
Feature Descriptions
The following gives an outline description for each of the product features.
24 Hour Clock
The aurastat®V has a twenty four hour
clock with a battery backup.
Day of Week Display
The aurastat®V displays the days of
the week as numbers.
Backlight Brightness
The aurastat®V display backlight
brightness can be adjusted or turned
o.
Boost Overrun Timer
A programmable timer that controls
the time the HRV remains at Boost
Speed after all boost switches have
been released.
Boost Delay Timer
A programmable timer which can be
used to delay the HRV running at Boost
Speed after a boost switch has been
activated.
Boost Inhibit
A programmed time period that
prevents the HRV switching into Boost
Speed or SUMMERboost®. Fan speed
controlled by proportional inputs are
not eected by Boost Inhibit.
Internal Humidity Sensor
The HRV has a relative humidity (RH)
sensor, the RH can be displayed on the
aurastat®V LCD screen. The RH sensor
can be programmed to switch the HRV
into Boost Speed.
106 25
141
Wiring Access
Knockout
aurastat®V
5

Filter Change Alert
The aurastat®V will display an alert
after a specied time when the HRV
lters require changing.
4 x Fan Speeds
The units have 4 programmable
speed settings, all speeds are
variable between 14-100% and allow
independent speed setting of both
supply and extract ventilation rates
1. Setback Speed.
Reduced ventilation.
2. Continuous Speed.
Normal ventilation.
3. Boost Speed.
Increased ventilation
4. SUMMERboost® Speed.
Very high ventilation, only
available during Summer
By Pass operation.
Fan Speed Display
The aurastat®V screen displays the
selected fan speed using the 1-4
stepped icons.
Boost Alert
A programmable timer which displays
a warning message on the aurastat®V
LCD screen after the HRV has been left
in Boost Speed for the specied time.
Summer Mode
Summer Mode operates by slowing or
stopping the supply fan. This reduces
the supply of From Atmosphere air
to the dwelling. Summer Mode is
triggered automatically or via a Volt
Free input. Summer Mode must not be
enabled or installed in dwellings where
open ue combustion appliances are
used.
SUMMERboost®
SUMMERboost® allows both the supply
and extract fans to run at full speed
whenever the Summer Bypass is
activated. By default SUMMERboost®
is enabled. When SUMMERboost®
is triggered by Summer Bypass the
increased fan speed can be prevented
either Manually or Automatically.
Manual - This is by means of a volt-free
switch wired directly into the controller
PCB.
Automatic - This is by means of
a dedicated wall mounted room
thermostat. SUMMERboost® will only
operate when the temperature has
exceeded the thermostat setting.
Should the room temperature fall
below the thermostat setting, then
SUMMERboost® will not operate.
Summer By Pass
Summer Bypass is designed to operate
during hot periods where fresh air can
be vented straight into the property
without being preheated by the
extracted stale air. Summer Bypass
operation is automatically controlled.
The Summer Bypass mechanism diverts
the stale air being extracted from the
dwelling around the heat cell so that
its heat energy is not transferred to
the fresh air being supplied to the
dwelling.
Duct Heater Control
To maintain ventilation ow rates
where prolonged periods of very low
temperatures occur, the facility for the
control of an electrically powered Duct
Heater is provided, MAX 1800W. The
Duct Heater is placed in-line between
the outside supply vent and the From
Atmosphere terminal on the HRV. In
these applications, the heater is used
to pre-warm the outside fresh air
supply before it enters the HRV.
2 x Proportional Sensor
Inputs
Enables connection of environmental
sensors to the HRV which can be used
to proportionally control HRV fan
speeds.
3 x Volt Free Inputs
Enables the connection of single pole
momentary switches, latching switches
or normally open relay contacts
to the HRV. These can be used to
switch between fan speeds or control
SUMMERboost® and Summer Mode.
2 x Live Switch Inputs
These inputs are used to switch the
HRV to Boost Speed via a switched live
input.
Frost Protection Program
During very cold weather, the Frost
Protection Program will detect
temperatures that could cause ice to
form inside the unit. It will reduce
or stop the supply ventilation rate,
thus allowing the warmer stale air to
raise the temperature within the unit
cell to such a level that prevents the
formation of ice. As temperatures
rise the Frost Protection Program
will increase the supply ventilation
ow rate back to the commissioned
settings.
HRV Run Timer
The aurastat®V displays the total run
time of the unit in hours.
Holiday Mode
The aurastat®V can set the HRV to
Holiday Mode. Holiday Mode sets the
HRV to speed 1 Setback Speed, Boost
Inhibit is enabled.
Multiple Internal
Temperature Sensors
The aurastat®V LCD can display the
From Atmosphere and To Atmosphere
air temperatures in real-time.
Additionally the temperature of the
heat cell is monitored.
6

Installation
Fitting
aurastat® V
The unit is designed to be wall mounted or tted over a UK standard single gang recessed metal box. It should be sited in
a place that is visible and convenient for the householder. To t the unit, rst remove the front of the unit; The front of the
unit is removed by loosening a single screw on the bottom face to the unit, lifting the bottom of the front away from the
base and unhooking the top of the front from the base. Fix base to the wall (always use a xing suited to the wall type) or if
using a metal box using M3.5 raised countersunk machine screws.
Wiring Connections Access
aurastat® V
The front of the unit is removed by loosening a single screw on the bottom face to the unit, lifting the bottom of the
front away from the base and unhooking the top of the front from the base. The base has a cable access knockout.
Communication Cable - Unshielded 4 Core 18-24AWG Stranded, Tinned Copper must be zip tied to the loop provided on
the front cover. The wiring connections are mounted on the circuit board in the front of the unit.
HRV
Refer to the Product Manual for the specic unit for information.
Wiring Diagram
aurastat®V to HRV connection wiring
aurastat
®
HRV
7

User Interface
The aurastat®V provides the user interface for commissioning and monitoring of a Titon HRV.
Buttons
The aurastat®V has seven buttons which control, congure and monitor the HRV. The Buttons on the units have dierent
function depending on which menu is active.
Display
The display is a 90mm liquid crystal display (LCD) screen. The display has a back light. The display uses a mixture of icons
text and gures grouped into regions to communicate information to the user.
SETUP key
ARROW keys
+/- keys
HOME key
FAN key
Enter menu item
Enter parameter setting
Previous / Next menu item
Navigation
Increase / Decrease parameter
Back to Setup Menu
Enter setup
Switch between Fan Speed % display
& Temprature monitoring
Cycle though Clock,
RH% & Room Sensor(s)
Long Press engage Holiday Mode
Switch HRV into Speed 3 Boost Speed
RUN Menu SETUP Menus
Status Icons
Week Days
Mode
Clock, %RH & PPM
& Holiday Mode
Fan Speed %
Air Tempratures
Fan Speed & Status
8

Display Icons
Icon denitions
Menu System
The aurastat®V menu system is divided into ve sections. This is to make the display user friendly for both the end user
(householder) and the service / installation engineer.
Menu Monitor & Control
RUN Menu
User setup Service & Setup Commissioning &
Installation
Reset
Name displayed SETUP 1 SETUP 2 SETUP 3 RESET 4
Description Gives access
to the control
and monitoring
functions.
Gives access to
settings likely
to be routinely
used by the
householder.
Gives access to
settings likely
to be used by
Maintenance or
Service Engineers.
Gives access to
advanced settings
required during
installation and
commissioning.
Pass code
protected.
Gives access to
the reset function.
Pass code
protected.
Status
Alert
Duct Heater
Frost Program active
Summer Mode active
Boost Timer
Fan
Supply
Extract
Summer By Pass active
Filter Alert
Set Up
Holiday Mode active
CO2 Sensor
Demand Control Ventilation
Kitchen
Wet Room
9

Menu Sections
The table below gives an overview of which item and settings are in which menu section.
Menu item User setup Service & Setup Commissioning &
Installation
Reset
SETUP 1 SETUP 2 SETUP 3 RESET 4
Time o
Day of Week o
Backlight Brightness o
Boost Overrun Timer ooo
Boost Delay Timer ooo
Boost Inhibit On/O o
Boost Inhibit Times o
Internal Humidity Boost (Set Point) o
Run Timer o
Filter Change Reset o
Filter Change Interval o
Speed 4 SUMMERboost® o o
Boost Alert On/O o
Boost Alert Timer o
Summer Mode Enable/Disable o
Summer Mode o
Summer By Pass Enable/Disable o
Summer By Pass o
Duct Heater Enable/Disable o
Duct Heater o
Room Sensor 1 - Set Points o
Room Sensor 2 - Set Points o
Internal Humidity Boost On/O o
Internal Humidity Boost (Full) o
Contious SPEED2 o
Boost SPEED3 o
Setback SPEED4 o
Frost Protection o
Room Sensor 1 Enable/Disable o
Room Senor 1 - Conguration o
Room Sensor 2 Enable/Disable o
Room Senor 2 - Conguration o
Switch input 1 o
Switch input 2 o
Switch input 3 o
Live Switch 1 (LS1) o
Live Switch 2 (LS2) o
Reset o
10

Commisioning
Quick Start Guide
Titon recommend that every installer start with the with the Quick Start Guide as a menu familiarization exercise. Using the
Quick Start Guide installers can setup the HRV quickly. With the minimum of conguration changes the system will be up
and running. All other settings are set at the default settings, ne tuning can be carried out at any time.
The Quick Start Guide explains step by step how to set up.
1. Time.
2. Day.
3. Continuous Speed 1.
4. Boost Speed 3.
Step Action Button Press(es) Screen(s)
1 Power up the HRV
Run Mode
2 Enter SETUP
Press key
3 Enter SETUP1 menu
Press key
SETUP key
ARROW keys
+/- keys
HOME key
FAN key
Enter menu item
Enter parameter setting
Previous / Next menu item
Navigation
Increase / Decrease parameter
Back to Setup Menu
Enter setup
Switch between Fan Speed % display
& Temprature monitoring
Cycle though Clock,
RH% & Room Sensor(s)
Long Press engage Holiday Mode
Switch HRV into Speed 3 Boost Speed
RUN Menu
SETUP Menus
11

Step Action Button Press(es) Screen(s)
4 Enter Clock setup
Press key, to enter clock edit
5 Edit minutes
Using / keys to edit mins value
Press key, to enter mins and move to
next menu item
6 Edit Hours
Using / edit hours value
Press key, to enter hours and move to
next menu item
7 Enter Day setup
Press key, to enter day setup
8 Change Day
Using / edit day
Press key, to enter Day and move to next
menu item
9 Exit SETUP1 menu
Press key, to return to SETUP1 menu
10 Enter SETUP3 menu
Move to SETUP3 menu by pressing key
twice
Press key to enter SETUP3 menu
11 Enter Pass Code
Using / edit the individual digits.
Use / to move digits.
Press key,
Enter Pass Code 3333
12

Step Action Button Press(es) Screen(s)
12 Enter Continous SPEED2
setup Press key to enter edit
13 Edit Continous Supply
Rate Using / edit supply rate
Press and release to modify the decimal
Press and hold to modify the integer
Press key, to enter value and move to
next menu item
14 Edit Continous Extract
Rate Using / edit extract rate
Press and release to modify the decimal
Press and hold to modify the integer
Press key, to enter value and move to
DONE
15 Finish Continous SPEED2
setup Press key to enter values and move to
the next menu item
SETUP key
ARROW keys
+/- keys
HOME key
FAN key
Enter menu item
Enter parameter setting
Previous / Next menu item
Navigation
Increase / Decrease parameter
Back to Setup Menu
Enter setup
Switch between Fan Speed % display
& Temprature monitoring
Cycle though Clock,
RH% & Room Sensor(s)
Long Press engage Holiday Mode
Switch HRV into Speed 3 Boost Speed
RUN Menu
SETUP Menus
13

Step Action Button Press(es) Screen(s)
16 Enter Boost SPEED3
setup Press key to enter edit
17 Edit Boost Supply Rate
Using / edit supply rate
Press and release to modify the decimal
Press and hold to modify the integer
Press key, to enter value and move to
next menu item
18 Edit Boost Extract Rate
Using / edit extract rate
Press and release to modify the decimal
Press and hold to modify the integer
Press key, to enter value and move to
DONE
19 Exit SETUP3
Press key to enter values and move to
the next menu item.
Press key twice to exit SETUP3 menu
and return to Run Mode
20 Run Mode
14

Setup
Menu Defaults
The tables below detail the default values and the range of available settings, plus any additional information about the
unit's conguable settings.
SETUP1
Congurable Item Range Default Additional information
Min Max
Time Any Time 00:00 24 hour clock.
Day of Week 1 7 1 Two groups, ve week days & two
weekend days.
Backlight Brightness O 4 1 O, 25%, 50%, 75% & 100%
Boost Overrun Kitchen 0 mins 60 mins 15 mins
Wet Room 0 mins 60 mins 15 mins
Boost Overrun timers are set independently for Kitchen and Wet Room inputs.
Boost Overrun timers must be set greater than zero for any momentary switch or the aurastat's fan button to trigger boost.
The aurastat's fan button uses the Kitchen Boost Overrun timer.
When using latching switches to initiate Boost SPEED 3 the Overrun timer will start when the latching switch is disengaged.
Boost Delay Timer 0 mins 60 mins 0 mins
If the Boost Delay Timer is set greater than zero momentary switches or the aurastat's fan button will not switch the HRV into
Boost SPEED 3. When using latching switches, if the Boost switch is turned of before the Boost Delay Timer has elapsed the
HRV will not Boost.
Boost Inhibit On/O On O O
Boost Inhibit Times Start 00:00 23:59 23:00
End 00:00 23:59 05:00
Internal Humidity Boost
(Setpoint)
30% 89% 70%
SETUP2
Congurable Item Range Default Additional information
Min Max
Filter Change Interval 3 months 24 months 12 months
Boost Overrun Timer Kitchen 0 mins 60 mins 15 mins
Wet Room 0 mins 60 mins 15 mins
Boost Overrun timers are set independently for Kitchen and Wet Room inputs.
Boost Overrun timers must be set greater than zero for any momentary switch or the aurastat's fan button to trigger boost.
The aurastat's fan button uses the Kitchen Boost Overrun timer.
When using latching switches to initiate Boost SPEED 3 the Overrun timer will start when the latching switch is disengaged.
Boost Delay Timer 0 mins 60 mins 0 mins
If the Boost Delay Timer is set greater than zero momentary switches or the aurastat's fan button will not switch the HRV into
Boost SPEED 3. When using latching switches, if the Boost switch is turned of before the Boost Delay Timer has elapsed the
HRV will not Boost.
Speed 4 SUMMERboost® 14% 100% 100% SUMMERboost® is only available on
models with Summer. SUMMERboost®
is disabled by default.
Press and release the + / - key to modify the mantissa(decimal). Press and hold the + / - key to modify the characteristic
(interger). HRV fan speed will change to reect the displayed setting when the button is released. Changes in fan speed
will take time to be reected as changes to the ventilation system airow rates. Fan speed will not change while in this
conguration menu.
Boost Alert On/O On O On
Boost Alert Timer 1 hour 10 hours 2 hours
15

Congurable Item Range Default Additional information
Min Max
Summer Mode Enable/
Disable
Enabled Disabled Enabled Disabled in By Pass unit.
Summer Mode Extract
from
dwelling
17°C 35°C 22°C
Supply to
dwelling
15°C 20°C 18°C
Supply Fan
Speed
0% 100% 0%
The Summer Mode fan speed is a % of Continuous SPEED 2. Therefore care must be taken to set the Summer Mode fan speed
at a value that makes the actual fan speed greater than 14%.
e.g. Continuous SPEED 2 x Summer Mode fan speed = Actual fan speed. 50% x 50% = 25%, 50%x28%=14%.
If the actual fan speed between 1% & 14% the fan may not run and an Error will be shown.
Summer By Pass Enable/
Disable
Enabled Disabled Enabled Enabled in By Pass unit
Summer By Pass Extract
from
dwelling
17°C 35°C 25°CIn order for the Summer By Pass to
operate the temperatures of both
the air being extracted from and
supplied to the property must be
above their individual thresholds. If the
temperature of the Supply air exceeds
that of the Extracted air the Summer
By Pass switches o to prevent the
warmer air being supplied directly to
the property.
Supply to
dwelling
10°C 20°C 18°C
SUMMERboost® Enabled Disabled Enabled
Duct Heater Enable/
Disable
Enabled Disabled Disabled
Duct Heater Frost User Frost Selects sensor that controls Duct Heater
activity.
Frost (FRST) = Uses sensor on the to
atmosphere side of the heat cell and the
Frost Protection Threshold temperature
congured in SETUP3.
User = Uses sensor in the From
Atmosphere (OUTSIDE) airstream and
user congured Duct Heater threshold
temperature.
Hyst 1°C 10°C 1°C Hysteresis value used during rising
temperature scenarios to prevent rapid
switching of the Duct Heater.
Duct Heater threshold -4°C 16°C 4°C Temperature at which duct heater will
turn on. This setting is only used in User
mode.
Frost mode:
During falling temperature scenarios duct heater will switch on at Frost threshold + 2°C switch o at the Frost Threshold.
During rising temperature scenarios duct heater will remain switched on between
Frost threshold and Frost threshold + 2°C + Hysteresis °C.
User mode:
During falling temperature scenarios duct heater will switch on below Duct Heater threshold.
During rising temperature scenarios duct heater will switch o above Duct Heater threshold + Hysteresis°C.
If the supply fan is set to run at a speed less than 25% Duct Heater will not turn on. This can be either by a congured speed eg
Setback SPEED1, holiday mode or Frost protection being active).
16

Congurable Item Range Default Additional information
Min Max
Room Sensor 1 na na %RH
These settings are only available when
Room Sensor1 is enabled in SETUP3
menu.
Room Sensor 1 is setup by default for use
with an %RH sensor.
Room sensor can be congured to also
operate with;
o Air Quality (AQ) Sensor - PPM,
o CO2 Sensor - PPM CO₂,
o Temperature Sensor - °C.
0000 9999
Continous SPEED 2
Proportional Increase
20
Sensor
Min Point
0V
90
Sensor
Max Point
10V
60
Set Point
Low
70
Set Point
High
Boost SPEED 3
Set point Low Dynamic Dynamic 60% Sensor Min & Max values are setup in
SETUP3 menu
Recommended Default High & Low
Values for sensors
Sensor
Type
Titon
Part №
SP
Low
SP
high
°C TP543 0017 0027
CO₂ PPM TP541 0800 1400
AQ PPM TP540 0800 1400
%RH TP542 0060 0070
Set point High Dynamic Dynamic 70%
Room Sensor 2 na na CO₂
These settings are only available when
Room Sensor2 is enabled in SETUP3
menu.
Room Sensor 2 is setup by default for use
with an CO₂ sensor.
Room sensor can be congured to also
operate with;
o Temperature Sensor - °C.
o Air Quality (AQ) Sensor - PPM,
o Humidity Sensor - %RH
0000 9999
Continous SPEED 2
Proportional Increase
450
Sensor
Min Point
0V
1850
Sensor
Max Point
10V
800
Set Point
Low
1400
Set Point
High
Boost SPEED 3
17

Congurable Item Range Default Additional information
Min Max
Set point Low Dynamic Dynamic 800PPM Sensor Min & Max values are setup in
SETUP3 menu
Recommended Default High & Low
Values for sensors
Sensor
Type
Titon
Part №
SP
Low
SP
high
°C TP543 0017 0027
CO₂ PPM TP541 0800 1400
AQ PPM TP540 0800 1400
%RH TP542 0060 0070
Set point High Dynamic Dynamic 1400PPM
Internal Humidity Boost On O O
Internal Humidity %RH
Boost FULL
%RH Boost Set point 30% 89% 70% HRV will switch to Boost SPEED 3 when
%RH is greater than set point value.
%RH Boost Overrun
timer
1 min 60 mins 15 mins The timer is engaged when the %RH
has decreased to the %RH set point
less the %RH Boost Hysteresis.
%RH Boost Hysteresis 1% 10% 1%
During falling humidity scenarios the HRV will remain in Boost SPEED 3 until the %RH has decreased to below %RH set point
less %RH Boost Hysteresis and the % RH Boost Overrun timer has elapsed.
When the timer is in operation the hour glass symbol is displayed.
SETUP3
Congurable Item Range Default Additional information
Min Max
SETUP3 pass code na na 3333 Pass code needs to be entered to
congure settings in the SETUP3 menu
Continuous SPEED2 Supply 14% 100% 40%
Extract 14% 100% 40%
Boost SPEED3 Supply 14% 100% 70%
Extract 14% 100% 70%
Setback SPEED1 Supply 14% 100% 18%
Extract 14% 100% 18%
Press and release the + / - key to modify the mantissa (decimal).
Press and hold the + / - key to modify the characteristic (integer)
HRV fan speed will change to reect the displayed setting when the button is released. Changes in fan speed will take time
to be reected as changes to the ventilation system airow rates.
Boost Overrun Kitchen 0 mins 60 mins 15 mins
Wet Room 0 mins 60 mins 15 mins
Boost Overrun timers are set independently for Kitchen and Wet Room inputs.
Boost Overrun timers must be set greater than zero for any momentary switch or the aurastat fan button to trigger boost.
The aurastat's fan button uses the Kitchen Boost Overrun timer. When using latching switches to initiate Boost SPEED 3 the
Overrun timer will start when the latching switch is disengaged.
Boost Delay Timer 0 mins 60 mins 0 mins
If the Boost Delay Timer is set greater than zero momentary switches of the aurastat's fan button will not switch the HRV into
Boost SPEED 3. When using latching switches, if the Boost switch is turned of before the Boost Delay Timer has elapsed the
HRV will not Boost.
18

Congurable Item Range Default Additional information
Min Max
SPEED4 SUMMERboost® 14% 100% 100% SUMMERboost® is only available
on models with Summer By Pass.
SUMMERboost® is enabled by default.
Press and release the + / - key to modify the mantissa. Press and hold the + / - key to modify the characteristic (integer).
HRV fan speed will change to reect the displayed setting when the button is released. Changes in fan speed will take time
to be reected as changes to the ventilation system airow rates.
Frost set point -2°C 11.5°C 2°C
Press and release the + / - key to modify the mantissa. Press and hold the + / - key to modify the characteristic (integer)
Frost Protection Mode O Reduce O
O = When temperature detected is below Frost set point Frost Protection activates turning o the Supply fan.
Reduce = When temperature detected is below Frost set point Frost Protection activates, progressively reducing the speed of
the Supply fan until the temperature reaches 4°C below Frost set point at which point the Supply fan is stopped.
Room Sensor 1 Enable/
Disable
Enable Disable Disable Activates Setup Room Sensor 1 in SETUP2
menu.
Room Sensor Type %RH Options are;
Temperature Sensor - °C,
CO₂ Sensor - PPM,
Air Quality Sensor - PPM,
Humidity Sensor - %RH.
Settings required for Titon supplied
sensors:
Sensor
Type
Titon
Part №
Min
0V
Max
10V
°C TP543 0000 0040
CO₂ PPM TP541 0450 1850
AQ PPM TP540 0450 1850
%RH TP542 0020 0090
Consult manufactures data sheets for
details.
Sensor Min Point 0V 0 9999 20%
Sensor Max Point 10V 0 9999 90%
0000 9999
Continous SPEED 2
Proportional Increase
20
Sensor
Min Point
0V
90
Sensor
Max Point
10V
60
Set Point
Low
70
Set Point
High
Boost SPEED 3
19

Congurable Item Range Default Additional information
Min Max
Room Sensor 2 Enable/
Disable
Enable Disable Disable Activates Setup Room Sensor 1 in SETUP2
menu.
Room Sensor Type CO₂ Options are;
Temperature Sensor - °C,
CO₂ Sensor - PPM,
Air Quality Sensor - PPM,
Humidity Sensor - %RH.
Settings required for Titon supplied
sensors:
Sensor
Type
Titon
Part №
Min
0V
Max
10V
°C TP543 0000 0040
CO₂ PPM TP541 0450 1850
AQ PPM TP540 0450 1850
%RH TP542 0020 0090
Consult manufactures data sheets for
details.
Sensor Min Point 0V 0 9999 450PPM
Sensor Max Point 10V 0 9999 1850PPM
0000 9999
Continous SPEED 2
Proportional Increase
450
Sensor
Min Point
0V
1850
Sensor
Max Point
10V
800
Set Point
Low
1400
Set Point
High
Boost SPEED 3
Switch Input 1 Boost from
Kitchen
Options are;
Boost from Kitchen,
Boost from Wet Room,
Setback,
Summer Mode Engage / SUMMERboost®
Disable.
Switch Input 2 Boost from Wet
Room
Switch Input 3 Summer Mode
Engage /
SUMMERboost®
Disable.
Live Switch 1 (LS1) Boost from
Kitchen
Options are;
Boost from Kitchen,
Boost from Wet Room.
Live Switch 2 (LS2) Boost from Wet
Room
RESET4
Congurable Item Range Default Additional information
Min Max
Passcode 6840
Reset Yes No No Selecting Yes returns ALL conguable
values except commissioned fan speeds
to the preceding default values and
returns to SETUP1 menu.
20
This manual suits for next models
1
Table of contents