INSTALLATION MANUAL
Air Conditioner (Multi Type)
Outdoor unit connection piping kit (For R410A)
Model name: RBM-BT14E, RBM-BT24E
EH78207101-1
Please read and follow the "PRECAUTIONS FOR SAFETY" in the installation manual for the air conditioner.
• Make sure all the parts listed in the table are included in the package.
• Read the installation manual for the air conditioner regarding the selection of the size and material of the refrigerant pipes.
• Ask an authorized dealer or qualified installation professional to install this product.
• Installation work must be carried out by following this installation manual and using exclusive tools and pipes for the refrigerant R410A.
1English
Parts Table
NOTE
1 ( ): indicates outer diameter.
2 For the sockets, the side with a notch is the one to connect a pipe. ( , , : without notch)
Unit: mm
Gas side joint Liquid side joint Balance pipe joint
RBM-
BT14E
Socket
No. Specifications No. Specifications No. Specifications No. Specifications Specifications
Ø34.9 × (Ø31.8) 1 pc (Ø28.6)ר22.2 2 pcs Ø15.9×(Ø19.1) 1 pc (Ø19.1)ר12.7 2 pcs
Ø28.6 × (Ø31.8) 1 pc
Joint Joint 1 pc L-pipe (Ø25.4)ר28.6 1 pc T-joint 3-Ø19.1 1 pc T-joint 3-Ø9.5 1 pc
Heat
insulator Heat insulator for joint 1 pc Heat insulator for L-pipe 1 pc Locally procured Locally procured
RBM-
BT24E
Socket
No. Specifications No. Specifications No. Specifications No. Specifications Specifications
Ø41.3×(Ø38.1) 1 pc (Ø38.1)ר41.3 1 pc Ø19.1×(Ø22.2) 1 pc (Ø22.2)ר19.1 1 pc
Ø34.9×(Ø38.1) 1 pc (Ø38.1)ר34.9 1 pc (Ø22.2)ר15.9 2 pcs
(Ø38.1)ר28.6 1 pc (Ø22.2)ר12.7 1 pc
(Ø38.1)ר22.2 1 pc
(Ø28.6)ר22.2 1 pc
Joint Joint 1 pc L-pipe (Ø31.8)ר28.6 1 pc T-joint 3-Ø22.2 1 pc T-joint 3-Ø9.5 1 pc
Heat
insulator Heat insulator for joint 1 pc Heat insulator for L-pipe 1 pc Locally procured Locally procured
59 61 62
Diameter of the
connecting pipe
External
diameter of
socket
Socket Notch
Ø28.6
Ø22.2
L-pipe
27
(Ø31.8)
59
(Ø28.6)
Ø28.6
(Ø28.6)
Ø22.2
(Ø31.8)
Ø34.9 Ø31.8 Ø28.6
(Brazed locally) (Ø25.4)
43
43
(Ø19.1)
Ø12.7
Ø12.7
Ø15.9
(Ø19.1) 3-Ø19.1
(Ø19.1)
13 10
10
3-Ø9.5
59 43 13 10
27
(Ø38.1)
L-pipe
Ø22.2
(Ø28.6)
Ø38.1
Ø41.3
Ø28.6
73
Ø34.9
(Ø38.1)
Ø38.1
(Brazed locally) (Ø28.6)
(Ø38.1)
Ø41.3 Ø34.9 Ø28.6 Ø22.2
71
6162
43
61 62
(Ø38.1) (Ø38.1) (Ø38.1) Ø19.1
Ø15.9
Ø19.1 3-Ø22.2
(Ø22.2)
18
14
Ø12.7
(Ø22.2)
(Ø22.2) (Ø22.2)(Ø22.2)
18
85
14
Ø15.9
3-Ø9.5
62 62 18 18
61 61 14
71 85
73
43
Installation and connection
Select the model and the number of outdoor unit connection piping kits that you need based on the sales catalog, design engineering, and the
data book and installation manual of outdoor unit.
CAUTION
• When brazing the refrigerant pipes, be sure to put the nitrogen first to prevent from oxidizing the inner pipe. If not, the oxidization scale
brings the refrigerant cycle clogging and result in malfunction.
• Use clean new pipes for the refrigerant pipes, and do not let water, moisture or dust get into the pipes during installation.
1Installation mode
<Gas joint>
Install them horizontally with a maximum gradient of ±15° for even distribution. (Do not install them perpendicularly or upright.)
(Figure 4, Figure 5, Figure 6, Figure 7)
<Liquid/balance pipe joint>
No restrictions on the installation orientation by the direction of refrigerant flow. However, on the liquid joint the installation cannot have the
refrigerant from the main pipe flow directly into the header unit. (Figure 2).
▼Liquid pipes
Figure 1 Figure 2
▼Gas pipes
Figure 3 <Gas joint reverse orientation installation>
Figure 4
<Gas joint upright orientation installation>
Figure 5
<Vertical installation>
Figure 6
<Vertical installation>
Figure 7
A
B
Horizontal line
Within ±15°
A view
Horizontal line
B view
Within ±15°
A
Horizontal line
Horizontal line
A view
A view
Header unit A Follower unit B Follower unit C
Main pipe
To indoor unit Liquid joint Extension valve installation site
(For planned system expansion)
Good
Header unit A Follower unit B Follower unit C
To indoor unit
Main pipe
Not
Good
Header unit A Follower unit B Follower unit C
Main pipe
Gas joint
To indoor unit Extension valve installation site
(For planned system expansion)
Good
Header unit A Follower unit B Follower unit C
Main pipe
Gas joint
To indoor unit
Not
Good
Gas joint
Header unit A Follower unit B
Main pipe
Gas joint
To indoor unit
A view
Gas joint
A
Not
Good
Unit
Vartical line
Header unit A
Gas joint
Not
Good
Header unit A
Gas joint
Not
Good
+EH78207101_01EN.fm Page 1 Wednesday, September 22, 2010 3:42 PM