Picco R32Heat pumps inverter air/water with axial fans
18
Switching from ulity water to domesc hot water, the working probe changes from “water outlet probe” to “DHW tank probe”. Switching from
winter mode to sanitary mode, the compressor does not switch o and is brought to the maximum frequency established by the controller,
whereas switching from summer mode to domesc hot water, the compressor is switched o and waits a safety me.
Defrosng is always carried out in winter mode on the ulity side, and never on the domesc hot water tank.
NOTE:
-If H10 = 1/3/5. Switching o the unit by remote control (remote on-o, see paragraph 10.4.1) does not aect domesc hot water operaon. The
unit goes to priority sanitary mode just powered on. The display on the machine shows the temperature detected by the probe inside the DHW
tank. When the sanitary cycle has nished, the display goes back to showing the water outlet probe temperature.
If the remote ON-OFF digital input (terminals 15.1 / 15.2) is open, with sanitary funcon enabled (H10=1 and H20=6), the wording “SAN” will
appear on the machine display. When the sanitary cycle has nished, the display goes back to showing “E00” indicang that the remote ON-OFF
contact is open.
-If H10 = 2/4/6, the remote on-o funcon disables domesc hot water producon and operaon of the heat pump in hean and cooling mode,
system side.
MEMORISING THE PROBE IN HEATING MODE
Switching from ulity water to domesc hot water, the working probe changes from “water outlet probe” to “DHW tank probe”. For this reason,
in heang mode, before entering sanitary mode, the last value read by the heat pump delivery probe is stored.
When sanitary temperature control is fullled, the system side temperature of reference goes back to that previously stored. The memory
funcon interrupts:
• when the temperature read by the probe becomes lower than the stored value;
• or when a me equal to b06 seconds (default b06 = 45) has elasped.
HEATING MODE ON DHW STORAGE TANK
If the parameter H130=1, the machine exploits the DHW storage tank even for central heang. In these condions, the outlet of the DHW valve
is also enabled during operaon in heang mode and not only in sanitary mode. The valve is deacvated during defrosng and in cooling mode.
When H130=1, the DHW integraon heater can be enabled also to act as system integraon heater: to do this, set r10=1 e r15=2 (for other r15
sengs see Paragraph 10.6.3); furthermore no digital output must be set as system integraon heater.
INSUFFICIENT HEAT EXCHANGE IN A DHW SYSTEM
During DHW producon, if the heat pump ow probe detects a temperature higher than 60°C, the DHW valve output is de-energised (DO6), and
the value of the DHW probe at this me is recorded (Tsan,set).
-if the operaon is San or Cool+San the compressor is stopped.
-If the operaon is Heat+San, the system evaluates for b06 seconds whether there is a demand for heang from the system. If the system re-
quires it, the compressor connues to work on the system, otherwise it is switched o.
-If the DHW resistor is present (e.g. DO3, H81=26), r15 = 0 or 1 and r24=2 or 3 it is acvated unl the DHW setpoint detected by the DHW probe
is met (and any oset).
The compressor restarts when the ow temperature of the heat pump falls below 60°C again and the temperature measured by the DHW probe
is lower than Tsan,set - 4°C.
Not all of the conguraons can be acvated and/or modied at the same me
The terminal block has digital inputs to control the unit via an external consent.
ON/OFF
The funcon is enabled by default on digital input ID 3 (terminals X15.1/X15.2).
Remove the terminal block jumper to place the unit in standby (the text “E00” appears on the controller display). When the contact closes, the
machine comes out of standby and the circulator switches on for 2 minutes.
Funcon enabled by default (Parameter H47=2).
I/O Resource- Parameter
ID3 can be acvated via H47 Enables remote On /O funcon
If the unit is switched o by remote control during defrosng, the heat pump nishes defrosng and then places itself in o mode via remote
control.
SUMMER/WINTER MODE CHANGE
The funcon can be set on digital input ID 2 (terminals X16.1/X16.2).
Heang or cooling mode of the heat pump can be managed by remote control.
I/O resource - Parameter Value
ID2 can be acvated via H46 3Open contact -> heat pump in cooling mode.
Closed contact -> heat pump in heang mode.
The poles of the digital input can be swapped by seng H75 = 2
DHW ENABLE FROM DIGITAL INPUT
Funcon which can be acvated instead of managing the double setpoint.
If DHW mode is enabled, instead of using the temperature probe, the domesc hot water funcon can be acvated by the opening/closing of
a digital input on the unit. This funcon is recommended when using two or more heat pumps in cascade hydronically connected to the same
domesc hot water storage tank; this way acvaon of the domesc hot water funcon is controlled by the tank probe connected to the rst
unit, while the other units are enabled automacally by digital consent.
The system goes to sanitary mode when the digital input closes and exits DHW producon when it opens.