POWER INDICATOR - Constant blue,
signals external power source. Flashing
red, signals loss of power and the using is
running off the backup battery. No light
signals the unit is inactive.
TEST BUTTON - Tests the alarm function.
AUDIO MUTE BUTTON - The mute button,
once activated during the event of an
alarm, will mute the audio alarm only. The
mute button does not affect the alarm
indicator or remote output.
ALARM INDICATOR - Inactive when the
alarm is not triggered. Once the alarm is
triggered the indicator will flash red.
8
1
2
3
4
5
67910 11
12 13 14 15 16
1
2
3
4
5
8
6
7
9
10
11
12
13
14 15
16
AUDIO BUZZER - 105dB audio alarm
FRONT PANEL CABLE CONNECTOR - Connect
the front panel to the alarm unit via the
ribbon cable to enable correct operation.
BACKUP ALARM BATTERY - Allowing the
alarm to operate for at least 50h in the
event of a power outage.
M16 BLANKING PLUG - Replace this with the
supplied optional gland for use with the
remote output wiring.
INCOMING MAINS FUSES - 250mA
fuses are fitted on both the MAINS
to 5Vdc and MAINS to 12Vdc circuits.
17
17 CABLE GLANDS - Two are
fitted as standard with an
optional one supplied.
AUDIO BUZZER CONNECTOR - Ensure the buzzer
connector is fitted correctly for the audio alarm
to operate. BATTERY ISOLATOR CONNECTOR - Fit the battery isolator
connector as shown. The unit may switch on.
NOTE: To test the
battery operation
once the unit is
installed. 1st switch
the unit power on,
the power indicator
will turn blue.
Switch the power
off and the power
indicator will
alternate from red
to off.
ALARM
INPUT
ALARM OPTION & ALARM INPUT - Setup the alarm
to be alarm active on open circuit or closed circuit
ALARM
OUTPUT
ALARM
OPTION
ALARM OPTION: ALARM INPUT:
Fit the jumper to enable alarm active on
open circuit
FITTED
FITTED
NOT FITTED
NOT FITTED INACTIVE
ACTIVE
INACTIVE
ACTIVE
POWER INPUT CONNECTOR -
Connect to incoming mains or
12-24V system.
ISOLATE POWER BEFORE
INSTALLATION
NOTE: The LR30 is available with
mains input voltage or
12-24Vac/dc
ALARM OUTPUT & ALARM 12V JUMPER OPTION - The alarm output can be configured to either a volt free
output or a 12Vdc 500mA output
For volt free operation do not
fit the jumper.
The relay specification is 10A
@250Vac.
0V12V
Jumper
Fit the optional jumper to
enable 12V output.