turck FMX-IM-3UP63X User manual

Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com 1|5
FMX-IM-3UP63X | 24-02-2023 18-33 | Technical modifications reserved
FMX-IM-3UP63X
Flow Monitoring – For the Connection of FCS/FCI Product
Series Ex Flow Sensors (NAEX)
IO-Link Device with Transistor Outputs
Technical data
Type FMX-IM-3UP63X
ID 7525101
Electrical data
Operating voltage 20…30VDC
Power consumption <12.6W
No-load current I0≤63mA
Teach modes QuickTeach; min/max adjustment. Teach
modes incl. DeltaFlow monitoring (teach
modes are automatically released with
the change of flow speed).
Flow speed [%] after min/max adjustment (perma-
nent)
Flow speed % after Quick-Teach (permanent)
Medium temperature [°C] with the SET button temporarily
pressed
Repeatability flow rate typical ±1% (of full scale)
Repeatability media temperature typical ±1K
Measuring accuracy media temperature typical ±7K
Switchpoint hysteresis media tempera-
ture
2K
Input function Connection of flow sensors (Ex sensors
of the FCS/FCI product series only!)
Sensor voltage ≤7VDC
Sensor current ≤70mA
Sensor current limitation approx.110mA
Measuring frequency 5 Hz (every 200 ms with software filter)
Features
■For Ex ia resp. Ex ib sensors
■Transistor outputs for flow, temperature and
faults
■Adjustment of switchpoint, no teaching of
flow boundaries (QuickTeach)
■LED band for indication of flow speed and
media temperature
■Monitoring of operating and display range
■Detection of wire-break and short-circuit on
the sensor side
■Standard IO or IO-Link operating mode
■Parametrized via pushbutton or soft-
ware-supported via IO-Link
■Associated equipment [Ex ia Ga / Da]
■Connection of flow probes Zone 0 / 20
Functional principle
All Ex flow sensors from the FCS series
(immersion sensors) and FCI series (inline
sensors) can be operated with the FMX-IM
external processing unit.
The flow module features four status LEDs
as well as a 10-segment LED band for local
monitoring. Software-based diagnostic options
are also available to the user, such as wire-
break and short-circuit on the sensor side.
Furthermore, monitoring of flow rates and
media temperatures within a predefined
operating and display range.
The upper and lower limits of the flow range
are taught in using the max./min. teach
mode implemented. The flow switchpoint is
easily adjusted by means of the Quick-Teach
function, without having to program a lower
and upper limit of the flow range. Working
on the calorimetric principle, the connectible
sensors not only detect the flow rate but also
the media temperature.

Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com 2|5
FMX-IM-3UP63X | 24-02-2023 18-33 | Technical modifications reserved
Technical data
Output functions
Flow monitoring transistor output
Temperature monitoring transistor output
Error monitoring transistor output
Switching characteristic PNP
Switching state active high / active low parametrizable
(transistor output error monitoring only
active low)
Switching voltage 20…30VDC
Switching current 100mA
Electrical connections 5-pole removable reverse polarity protect-
ed terminal blocks
Connection mode screw connection
Terminal cross-section ≥1.5…≤2.5mm²
IO-Link
IO-Link specification V 1.0
Transmission rate 38.4 kBit/s (COM 2)
Transmission physics Transmission physics 3-wire physics
(PHY 2)
Communication channel Clamp 12 and via front panel jack COM
(PC)
Communication modes Tool based engineering via FDT / DTM,
IODD. Acyclic communication via On-Re-
quest Data Objects
Included in the SIDI GSDML Yes
Tests/approvals
Device marking Ex II (1) G [Ex ia Ga] IIC resp. II (1) D [Ex
ia Da] IIIC
EX type-examination certificate TÜV 11 ATEX 078981
IECEx certificate of conformity IECEx TUN 11.0005
Declaration of conformity EN ISO/IEC 5108M
Approvals CE, C-UL U.S. submitted
Electromagnetic compatibility (EMC) Acc. to NE21
Relative humidity EN 60068-2-38
Mechanical data
Design Signal processor
Dimensions 89x110x27mm
Housing material Polycarbonate/ABS
Ambient temperature -25…+70°C
Mounting type DIN rail mounting and mounting panel
Protection class IP20
MTBF 101Years
The flow module can be operated either in
IO-Link (IOL) or in standard IO (SIO) mode
via the integrated IO-Link interface. In SIO
mode, the switching outputs are operated in
the standard way. In IOL mode the current
process signal is transmitted cyclically as a 10
bit-serial value.
Parametrization is initiated either via
pushbutton or software-supported via IO-
Link interface. The actual parametrization is
then implemented via the tool-based DTM or
IODD within the FDT frame PACTware™ or
acyclically near the control via On-Request
Data Objects (ORDO).

Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com 3|5
FMX-IM-3UP63X | 24-02-2023 18-33 | Technical modifications reserved
LED display
LED Color Status Description
Pwr green on Operating voltage applied
Device ready for operation
flashing Operating voltage applied
IO-Link communication active
(inverted flash with T on 900 ms and T off 100 ms)
Flow yellow off Switching output flow [low]
on Switching output flow [high]
flashing Teach mode / display of diagnostic data
for specification see manual
Temp yellow off Switching output media temperature [low]
on Switching output media temperature [high]
flashing Teach mode / display of diagnostic data
for specification see manual
Fault Red Off Switching output fault [high]
On Switching output flow [low]
(for error pattern in combination with LEDs see manual)
For detailed description of the display patterns and flashing codes see instruction manual FM-
IM/FMX-IM
IO-Link (Process Data Objects)
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Flow Value 10 Bit (Bit 15 = MSB, Bit 6 = LSB) not assigned Out 3
(Fault)
Out 2
(Temp)
Out1
(Flow)
Accessories
Dimension drawing Type ID
IOL-COM/3M 7525110 IO-Link communication line for
connecting IO-Link devices to an IO-link
master via a 3.5-mm jack plug
USB-2-IOL-0002 6825482 IO-Link Master with integrated USB port
Accessories
Dimension drawing Type ID
FCS-N1/2A4-NAEX0 6870471 Sensor according to category II 1 G for
liquid media

Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com 4|5
FMX-IM-3UP63X | 24-02-2023 18-33 | Technical modifications reserved
Dimension drawing Type ID
FCS-G1/4A4-NAEX0 6870465 Sensor according to category II 1 G for
liquid media
FCS-G1/4A4-NAEX-H1141 6870341 Sensor according to category II 2 G for
liquid media
FCS-GL1/2A4-NAEX-H1141 6870432 Sensor according to category II 2 G for
liquid media
FCS-DN25A4-NAEX0/L100 6872035 Sensor according to category II 1 G for
liquid media

Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com 5|5
FMX-IM-3UP63X | 24-02-2023 18-33 | Technical modifications reserved
Instructions for use
Intended use
This device fulfills the directive 2014/34/EC and can be applied in explosion hazardous areas according to EN60079-0,
EN60079-11 and EN61241-11 as associated equipment for connection to intrinsically safe flow sensors.In order to ensure cor-
rect operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II (1) G and II (1) D (Group II, Category (1) G, electrical equipment for gas-atmospheres and category (1) D, electrical equip-
ment for dust atmospheres)
Marking (see device or technical data sheet)
É II (1) G [Ex ia Ga] IIC T4 acc. to EN60079-11 and EN60079-0/61241-11 and É II (1) D [Ex ia Da] IIIC
É II 1 G and EEx ia IIC T4 acc.to EN50020 and EN50284 and É II 1 D IP67 T 115°C acc.to EN50281-1-1
Local admissible ambient temperature
-25…+70 °C
Installation/Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowl-
edge of protection classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous
areas.Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is accessory equipment which features intrinsically safe circuits as well as non-intrinsically safe circuits. It may only
be installed outside the explosion hazardous area in dry, clean and well monitored areas. If a declaration of conformity or dec-
laration of the manufacturer as a category 3 device exists, the device may be installed in zone 2. Special conditions for safe
operation must be observed. Intrinsically-safe electrical equipment can be connected to the intrinsically-safe connections. All
equipment must comply with the demands for operation in the existing zone of the explosion hazardous area. If the intrinsi-
cally safe circuits lead to the dust explosion hazardous zones 20 or 21, it is important to ensure that the devices connected to
this circuit fulfil the demands for category 1D or 2D and are certified accordingly. If the equipment is interconnected, it is nec-
essary to perform the "Proof of intrinsic safety" (EN 60079-14). Equipment which has been used once to connect intrinsical-
ly safe circuits to non-intrinsically safe circuits is no longer suitable for subsequent use with intrinsically safe circuits. Relevant
regulations exist for the establishment of intrinsically-safe circuits, mounting of external connection parts as well as the char-
acteristics and laying of cables. Cables and terminals with intrinsically-safe circuits must be marked. They should be sepa-
rated from non-intrinsically safe circuits or must feature appropriate insulation (EN 60079-14). Observe the prescribed clear-
ances to earthed components and connections of other devices to the intrinsically-safe connections of this device. Unless ex-
pressed specifically in the device-specific operating instructions, the approval becomes void if the device is opened, repaired
or actions are performed on the device by someone other than approved experts or the manufacturer. Visible changes to the
device housing, such as brown-black discolourations caused by heat, as well as holes or bulges also indicate a serious dan-
ger. Switch off the device immediately. With the associated electrical equipment the interconnected intrinsically-safe equipment
must also be checked. Inspection of a device with regard to the explosion protection can only be performed by an expert or the
manufacturer. The operation of the devices is only permitted in conjunction with the permitted data printed on the side of the
housing. Before any commissioning or modification of the device interconnections, ensure that the respective regulations, di-
rectives and conditions have been complied with and also ensure that use is only for the intended purpose and the safety re-
quirements have been fulfilled.After connection to other circuits the sensor may no longer be used in Exi installations. When in-
terconnected to (associated) electrical equipment, it is required to perform the "Proof of intrinsic safety" (EN60079-14).
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in
a dust flow and avoid build-up of dust deposits on the device.If the devices and the cable could be subject to mechanical dam-
age, they must be protected accordingly. They must also be shielded against strong electro-magnetic fields.The pin configura-
tion and the electrical specifications can be taken from the device marking or the technical data sheet.In order to avoid contam-
ination of the device, please remove possible blanking plugs of the cable glands or connectors only shortly before inserting the
cable or opening the cable socket.
Special conditions for safe operation
The device must be protected against any kind of mechanical damage.
Service/Maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer.
The most important data from the approval are listed.
This manual suits for next models
1
Table of contents
Other turck Switch manuals

turck
turck IM1-451EX Series User manual

turck
turck TBIL-M1-16DIP User manual

turck
turck TBEN-L SE-M2 Series User manual

turck
turck TBIP-L 16DXP-AUX Series User manual

turck
turck TBIL-S Series User manual

turck
turck TBIL-S Series User manual

turck
turck TBEN-L-SE-U1 Series User manual

turck
turck TBIL-M1-16DXP User manual