turck TBIL-S Series User manual

Your Global Automation Partner
Instructions for Use
TBIL-S…
Compact I/O Hubs with
IO-Link

2Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

V 01.02 | 2021/04 3
Table of Contents
1 About These Instructions.................................................................................................................. 5
1.1 Target groups................................................................................................................... 5
1.2 Explanation of symbols used ........................................................................................ 5
1.3 Additional documents.................................................................................................... 5
1.4 Feedback about these instructions.............................................................................. 5
2 Notes on the Product......................................................................................................................... 6
2.1 Product identification..................................................................................................... 6
2.2 Scope of delivery ............................................................................................................. 6
2.3 Legal requirements.........................................................................................................6
2.4 Turck service..................................................................................................................... 6
3 For Your Safety.................................................................................................................................... 7
3.1 Intended use..................................................................................................................... 7
3.2 General safety notes ....................................................................................................... 7
4 Product Description ........................................................................................................................... 8
4.1 Device overview .............................................................................................................. 8
4.2 Properties and features.................................................................................................. 9
4.3 Operating principle......................................................................................................... 9
4.4 Functions and operating modes ..................................................................................9
5 Mounting............................................................................................................................................10
5.1 Grounding the device...................................................................................................10
6 Connecting ........................................................................................................................................11
6.1 Connecting the supply voltage and IO-Link ............................................................11
6.2 Connecting digital sensors and actuators................................................................12
7 Parameterizing and Configuring...................................................................................................13
7.1 Parameters......................................................................................................................13
8 Operating ...........................................................................................................................................21
8.1 Process input data.........................................................................................................21
8.2 Process output data......................................................................................................23
8.3 LED displays....................................................................................................................24
8.3.1 IO-Link................................................................................................................................................24
8.3.2 Channel LEDs...................................................................................................................................24
8.4 Evaluating diagnostic data..........................................................................................25
8.5 IO-Link Events ................................................................................................................27
8.6 IO-Link error codes........................................................................................................27
9 Troubleshooting ...............................................................................................................................28
10 Maintenance......................................................................................................................................29
11 Repair..................................................................................................................................................29
11.1 Returning devices..........................................................................................................29
12 Disposal ..............................................................................................................................................29

Table of Contents
4Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
13 Technical Data ..................................................................................................................................30
13.1 General technical data..................................................................................................30
13.2 Technical data – TBIL-S…-8DIP...................................................................................31
13.3 Technical data – TBIL-S…-8DXP .................................................................................32
14 Appendix: EU Declaration of Conformity ....................................................................................33
15 Turck Subsidiaries - Contact Information ....................................................................................34

V 01.02 | 2021/04 5
1 About These Instructions
These operating instructions describe the structure, functions and the use of the product and
will help you to operate the product as intended. Read these instructions carefully before using
the product. This is to avoid possible damage to persons, property or the device. Retain the in-
structions for future use during the service life of the product. If the product is passed on, pass
on these instructions as well.
1.1 Target groups
These instructions are aimed at qualified personal and must be carefully read by anyone
mounting, commissioning, operating, maintaining, dismantling or disposing of the device.
1.2 Explanation of symbols used
The following symbols are used in these instructions:
DANGER
DANGER indicates a dangerous situation with high risk of death or severe injury if
not avoided.
WARNING
WARNING indicates a dangerous situation with medium risk of death or severe in-
jury if not avoided.
CAUTION
CAUTION indicates a dangerous situation of medium risk which may result in minor
or moderate injury if not avoided.
NOTICE
NOTICE indicates a situation which may lead to property damage if not avoided.
NOTE
NOTE indicates tips, recommendations and useful information on specific actions
and facts. The notes simplify your work and help you to avoid additional work.
uCALL TO ACTION
This symbol denotes actions that the user must carry out.
aRESULTS OF ACTION
This symbol denotes relevant results of actions.
1.3 Additional documents
The following additional documents are available online at www.turck.com:
nData sheet
nCommissioning manual IO-Link devices
nIO-Link parameter manuals for IO-Link devices
nEU Declaration of Conformity
1.4 Feedback about these instructions
We make every effort to ensure that these instructions are as informative and as clear as pos-
sible. If you have any suggestions for improving the design or if some information is missing in
the document, please send your suggestions to [email protected].

Notes on the Product
Turck service
6Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
2 Notes on the Product
2.1 Product identification
This instruction is valid for following devices:
nTBIL-S3-8DIP
nTBIL-S3-8DXP
nTBIL-S4-8DIP
nTBIL-S4-8DXP
2.2 Scope of delivery
The scope of delivery includes:
nI/O hub
nDummy plugs for M8 or M12 connectors
nLabel clips
2.3 Legal requirements
The device falls under the following EU directives:
n2014/30/EU (electromagnetic compatibility)
n2011/65/EU (RoHS Directive)
2.4 Turck service
Turck supports you with your projects, from initial analysis to the commissioning of your applic-
ation. The Turck product database under www.turck.com contains software tools for program-
ming, configuration or commissioning, data sheets and CAD files in numerous export formats.
The contact details of Turck subsidiaries worldwide can be found on p. [}34].

V 01.02 | 2021/04 7
3 For Your Safety
The product is designed according to state-of-the-art technology. However, residual risks still
exist. Observe the following warnings and safety notices to prevent damage to persons and
property. Turck accepts no liability for damage caused by failure to observe these warning and
safety notices.
3.1 Intended use
These devices are designed solely for use in industrial areas.
The block modules of the TBIL-S… series are IO-Link devices and serve as I/O hub between field
devices (sensors/actuators) and the IO-Link master. The hub has eight digital I/O channels. De-
pending on the module type, eight digital inputs (TBIL-S…8DIP) for connecting digital sensors
or eight digital DXP channels (TBIL-S…-8DXP) for connecting digital sensors or actuators are
provided. On devices with DXP channels, each I/O channel can be used as either a digital input
or output without additional configuration.
The device is designed in IP65/IP67/IP69K and can be mounted directly in the field.
The devices may only be used as described in these instructions. Any other use is not in accord-
ance with the intended use. Turck accepts no liability for any resulting damage.
3.2 General safety notes
nThe device may only be assembled, installed, operated, parameterized and maintained by
professionally-trained personnel.
nThe device may only be used in accordance with applicable national and international regu-
lations, standards and laws.
nThe device only meets the EMC requirements for industrial areas and is not suitable for use
in residential areas.

Product Description
Device overview
8Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
4 Product Description
The I/O hubs of the TBIL-S… series connect up to eight digital sensors or up to eight sensors or
actuators with one IO-Link master port.
The following device types are available:
nTBIL-S3-8DIP: 8 digital input channels, 8 M8 connectors
nTBIL-S3-8DXP: 8 digital I/O channels, 8 M8 connectors, each channel can be used as digital
input or output without additional configuration
nTBIL-S4-8DIP: 8 digital input channels, 4 M12 channels
nTBIL-S4-8DXP: 8 digital I/O channels, 4 M12 connectors, each channel can be used as digital
input or output without additional configuration
The devices are designed in a fully encapsulated housing with degree of protection
IP65/IP67/IP69K.
4.1 Device overview
16 [0.63] 22.2 [0.87]
26.8 [1.06]
31.6 [1.24]
132 [5.20]6.1 [0.24]
144 [5.67]
M12 x 1
Ø 4.3 [0.17]
Ø 4.3 [0.17]
P1 C2
C7 C6
C1
C5
C0
C4
Fig.1: Dimensions TBIL-S3-…
16 [0.63] 24.9 [0.98]
26.8 [1.06]
31.6 [1.24]
132 [5.20]6.1 [0.24]
144 [5.67]
M12 x 1
Ø 4.3 [0.17]
Ø 4.3 [0.17]
C3P1 C2 C1 C0
Fig.2: Dimensions TBIL-S4-…

V 01.02 | 2021/04 9
4.2 Properties and features
nFibre-glass reinforced housing
nShock and vibration tested
nFully potted module electronics
nProtection class IP65/IP67/IP69K
nIO-Link diagnostics for short-circuit and supply over- and undervoltage
nTBIL-S3-…: 1 digital input channel or 1 universal digital channels per connector
nTBIL-S4-…: 2 digital input channels or 2 universal digital channels per connector
nMetal connectors
4.3 Operating principle
I/O hubs receive binary sensor signals from the process level at the digital inputs and transmit
them via an IO-Link master to a higher-level controller. Output commands sent by a controller
via an IO-Link master are forwarded to connected binary actuators via the I/O hub output chan-
nels.
4.4 Functions and operating modes
The I/O hubs with IO-Link of the TBIL-S series connect up to eight digital sensors or eight digital
sensors and actuators with one IO-Link master port.
The device provides diagnostics for power supply and short circuit of the sensors and actuators
on the IO-Link master.

Mounting
Grounding the device
10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
5 Mounting
The device is mounted via four M4 screws on a flat and pre-drilled mounting surface.
Attach the module to the mounting surface with two M4 screws. The maximum tighten-
ing torque for the screws is 1.3 Nm
31.8
132
M4 (2 x)
max. 1.3 Nm
Fig.3: Mounting the device to a mounting surface (example: TBIL-S3-…)
5.1 Grounding the device
When mounting on a mounting plate, fasten the device with an M4 metal screw.
aThe FE connection of the device is connected to the reference potential of the installation
via the M4 metal screw.

V 01.02 | 2021/04 11
6 Connecting
NOTICE
Intrusion of liquids or foreign bodies through leaking connections
Loss of protection class IP65/IP67/IP69K, device damage possible
Tighten connectors with a tightening torque of 0.6Nm.
Only use accessories that guarantee the protection class.
Always seal unused connectors with suitable screw caps or blind caps.
6.1 Connecting the supply voltage and IO-Link
WARNING
Incorrect or defective power supply unit
Danger to life due to dangerous voltages on touchable parts
Only use SELV or PELV power supplies in accordance with EN ISO 13849-2, which
allow a maximum of 60 VDC or 25 VAC in the event of a fault.
For the connection to IO-Link and the supply voltage, a 5-pin M12 connector is available.
Fig.4: M12 connector for the connection to IO-Link
Connect the device to the supply voltage and IO-Link according to the pin assignment.
4
13
2
5
1 = 24 VDC
2 = n.c.
3 = GND
4 = C/Q (IO-Link)
5 = n.c.
Fig.5: Pin assignment IO-Link

Connecting
Connecting digital sensors and actuators
12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
6.2 Connecting digital sensors and actuators
Connecting digital sensors and actuators– TBIL-S3-…
For connecting digital sensors and actuators, the TBIL-S3 variants provide eight 3-pin M8
connectors.
Fig.6: TBIL-S3-…: M8 connector for connecting digital sensors and actuators
Connect the sensors and actuators to the device according to the pin assignment.
3 1
4
v
1 = VAUX
3 = GND
4 = Signal In/Out
C0…C7
Fig.7: Pin assignment TBIL-S3-8DXP
Connecting Digital Sensors and Actuators – TBIL-S4-…
For connecting digital sensors and actuators, the TBIL-S4 variants provide four 5-pin M12
connectors.
Fig.8: TBIL-S4-…: M12 connector for connecting digital sensors and actuators
Connect the sensors and actuators to the device according to the pin assignment.
4
13
2
5
v1 = VAUX
2 = Signal In/Out
3 = GND
4 = Signal In/Out
5 = FE
C0...C3
Fig.9: Pin assignment TBIL-S4-8DXP

V 01.02 | 2021/04 13
7 Parameterizing and Configuring
This chapter contains the description of selected device parameters that are common for oper-
ating the device.
The device-specific parameter manuals at www.turck.com contain a detailed description of all
IO-Link indices of the devices according to IODD.
7.1 Parameters
IO-Link object directory – ISDU device parameters: Direct Parameter Page
ISDU
Index
Hex.
(dec.)
Sub index Object name Access Length
in bytes
Meaning/default value
0x00
(0)
Direct Parameter Page 1 read
only
16
0x03 Minimum cycle time read
only
1
0x05 IO-Link version ID read
only
1 17
0x08 Vendor ID read
only
2 ID for Turck:
0x013D
0x09
0x0A Device ID read
only
3 E.g: TBIL-S3-8DXP:
0x1E2213
0x0B
0x0C
IO-Link object directory – ISDU device parameters: Identification
ISDU
Index
Hex.
(dec.)
Object name Access Length
[Byte]
Meaning/
default value
Comment
0x10
(16)
Vendor
Name
read
only
16 Turck
0x11
(17)
Vendor Text read
only
32 www.turck.com
0x12
(18)
Product
Name
read
only
32 E. g. TBIL-S3-8DXP
0x13
(19)
Product ID read
only
16 Ident no. of the device.
E. g. 100002595 for
TBIL-S3-8DXP
0x14
(20)
Product Text read
only
32 I/O hub
0x15
(21)
Serial
Number
read
only
16 Sequential
serial number
0x16
(22)
Hardware ID read/
write
8 Hardware version of
the device, e. g. V1.0

Parameterizing and Configuring
Parameters
14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
ISDU
Index
Hex.
(dec.)
Object name Access Length
[Byte]
Meaning/
default value
Comment
0x17
(23)
Firmware
Revision
read
only
16 Firmware version of
the device, e. g.
V1.0.7.0
0x18
(24)
Application
Specific Tag
read/
write
32 Default "***" Customer-specific or
application-specific
data can be stored in
this field.
0x19
(25)
Function Tag read/
write
32 Default "***" The application-spe-
cific device function
can be stored in this
field.
0x1A
(26)
Location Tag read/
write
32 Default "***" The application-spe-
cific installation loca-
tion of the device can
be stored in this field.
IO-Link object directory – ISDU device parameters: Preferred Index (parameters and
diagnostics of the digital in- and outputs)
ISDU
Index
Hex.
(dec.)
Object name Access Length
[Byte]
Meaning
0x40
(64)
Parameter ID read/
write
4 Customer-specific ID, for free use
0x41
(65)
Inverting
Input
read/
write
1 Invert digital input
0x42
(66)
Activate
Output
read/
write
1 Activate output
(only valid for TBIL-S…- 8DXP)
0x43
(67)
Impulse
Stretching
Input
read/
write
8 Pulse stretching input
0x44
(68)
Short Circuit
Recovery
read/
write
1 Manual output reset after overcurrent
(only valid for TBIL-S…- 8DXP)
0x45
(69)
Failsafe read/
write
2 Output After Error
(only valid for TBIL-S…- 8DXP)
0x46
(70)
Under
Voltage
Diagnostics
read/
write
2 Undervoltage Diagnosis (defining the
threshold value for the undervoltag dia-
gnostics)
Diagnostics
0x50
(80)
Supply Error read
only
2nOver- and undervoltage supply
nOvercurrent VAUX connector C0…C7 or
C0…C3
0x51
(81)
Output Short
Circuit
read
only
1 Overcurrent output 0…7
(only valid for TBIL-S…- 8DXP)

V 01.02 | 2021/04 15
Invert Digital Input – 0x41 (65), sub index 0
This parameter inverts the state of the digital input in the process image.
Format Length
Byte 1 byte 1 bit per channel
Default values are shown in bold.
Value Meaning
0 No
1 yes Input signal inverted
nTBIL-S3-8DIP
nTBIL-S3-8DXP
Byte 0
Bit offset
76543210
C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4
nTBIL-S4-8DIP
nTBIL-S4-8DXP
Byte 0
Bit offset
76543210
C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.

Parameterizing and Configuring
Parameters
16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Activate Output – 0x42 (66), sub index 0
This parameter activates or deactivates the output function of the digital channel.
Format Length
Byte 1 byte 1 bit per channel
Default values are shown in bold.
Value Meaning
0 No Output function deactivated, channel can only be used as input
1 Yes Output function activated, channel can be used as in- or output
nTBIL-S3-8DXP
Byte 0
Bit offset
76543210
C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4
nTBIL-S4-8DXP
Byte 0
Bit offset
76543210
C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.

V 01.02 | 2021/04 17
Impulse Stretching Input – 0x43 (67)
This parameter defines the duration of the pulse stretching for digital input edges in multiples
of 10 ms. This allows that even short signals with longer PLC cycle times can be detected.
Format Length
Array of byte 8 byte 1 byte per channel
Default values are shown in bold.
Value Meaning
0 Disabled Pulse stretching deactivated
1 1…255 Pulse stretching input [*10 ms]
nTBIL-S3-8DIP
nTBIL-S3-8DXP
Byte offset
01234567
Sub index
87654321
C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4
nTBIL-S4-8DIP
nTBIL-S4-8DXP
Byte offset
01234567
Sub index
87654321
C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.

Parameterizing and Configuring
Parameters
18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Short Circuit Recovery – 0x44 (68), Subindex 0
This parameter defines if a manual reset is necessary after an overcurrent occurred at the digital
channel.
Format Length
Byte 1 byte 1 bit per channel
Default values are shown in bold.
Value Meaning
0 No Automatic recovery mode
1 Yes Controlled recovery mode (output has to be reset manually)
nTBIL-S3-8DXP
Byte 0
Bit offset
76543210
C7P2 C6P4 C5P4 C4P4 C5P2 C2P4 C1P4 C0P4
nTBIL-S4-8DXP
Byte 0
Bit offset
76543210
C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.

V 01.02 | 2021/04 19
Failsafe – 0x45 (69), sub index 0
This parameter defines the behavior of the output in case of an interruption of the IO-Link com-
munication.
Format Length
Array of byte 2 byte 2 bit per channel
Default values are shown in bold.
Value Meaning
00 0 Set output to 0
01 1 Set output to 1
10 Current value Hold current value
11 reserved
nTBIL-S3-8DXP
Byte 1 Byte 0
Bit offset Bit offset
64206420
C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4
nTBIL-S4-8DXP
Byte 1 Byte 0
Bit offset Bit offset
64206420
C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.

Parameterizing and Configuring
Parameters
20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Under Voltage Diagnostics – 0x46 (70), Subindex 0
This parameter defines threshold value for the undervoltage diagnostics.
Format Length
Array of byte 2 byte 1 bit per module
Default values are shown in bold.
Value Meaning
0 Standard
(IEC 61131-2)
lower threshold: 19.2 V
upper threshold: 20.4 V
1 Extended lower threshold: 17.5 V
upper threshold: 18.5 V
Byte 0
Bit offset
7654321 0
- - - - - - - Threshold
Byte 1
Bit offset
76543210
--------
Meaning of parameter bits
Name Meaning
Cx Port no.
Py Pin no.
Other manuals for TBIL-S Series
1
This manual suits for next models
4
Table of contents
Other turck Switch manuals

turck
turck FMX-IM-3UP63X User manual

turck
turck TBEN-L-SE-U1 Series User manual

turck
turck TBIL-M1-16DIP User manual

turck
turck IM1-451EX Series User manual

turck
turck TBIL-S Series User manual

turck
turck TBIP-L 16DXP-AUX Series User manual

turck
turck TBEN-L SE-M2 Series User manual

turck
turck TBIL-M1-16DXP User manual
Popular Switch manuals by other brands

Asante
Asante IC35516 IC35516G Specifications

Cisco
Cisco Catalyst Express 520-24LC Features & benefits

Berker
Berker 75316102 Operation instructions

Allied Telesis
Allied Telesis AT-x230-10GP installation guide

Altinex
Altinex MT304-203 user guide

NETGEAR
NETGEAR M4250-10G2XF-PoE++ Hardware installation guide