Tyco Fire Product AV-1-300 Operating and maintenance instructions

Model AV-1-300 Alarm Check Valve, 300 psi (20,7 bar)
2-1/2, 4, 6 & 8 Inch (DN65, DN100, DN150 & DN200)
Vertical or Horizontal* Installation
Worldwide
Contacts
www.tyco-fire.com
Page 1 of 20 SEPTEMBER 2014 TFP910
General
Description
The TYCO Model AV-1-300 Alarm
Check Valves are divided seat ring,
rubber-faced clapper, waterow alarm
check valves that are intended for
use in wet pipe (automatic sprinkler)
re protection systems. They may be
installed vertically or horizontally*,
and they are designed to automati-
cally actuate electric and/or hydraulic
alarms when there is a steady ow of
water into the system that is equivalent
to the discharge rate of one or more
sprinklers.
A separately ordered Model RC-1
Retard Chamber (Ref. Technical Data
Sheet TFP920) is required for installa-
tions subject to variable pressures. It is
used to help prevent false alarms asso-
ciated with pressure variations in public
water supplies.
The AV-1-300 Alarm Check Valve Trim
includes pressure gauges to monitor
system pressure conditions, a bypass
check valve, a main drain valve, and
an alarm test valve. The bypass check
valve reduces the possibility of false
alarms by permitting slow as well as
small transient increases in water sup-
ply pressure to be passed through to
the system without opening the water-
way clapper.
NOTICE
The TYCO Model AV-1-300 Alarm
Check Valves described herein must
be installed and maintained in com-
pliance with this document, as well as
with the applicable standards of the
National Fire Protection Association
(NFPA), in addition to the standards of
any authorities having jurisdiction. Fail-
ure to do so may impair the integrity of
these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating
condition. Contact the installing con-
tractor or product manufacturer with
any questions.
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Working Water Pressure Range
20 to 300 psi (1,4 to 20,7 bar)
Friction Loss
Refer to Graph A.
End Connections
Groove x Groove
Flange x Groove
Flange x Flange
Refer to Table A for size applicability
Weights
Refer to Table A.
Physical Characteristics
The body is ductile iron, the hand-hole
cover is ductile iron, and the seat ring
is bronze. The clapper for the 2-1/2
inch (DN65) valve size is stainless steel.
The clapper for the larger valve sizes
is ductile iron. All valve sizes utilize an
EPDM clapper facing.
Flanged connections are available
drilled per ANSI, ISO, AS, and JIS
specications as detailed in Table B.
Threaded port connections for the
AV-1-300 Valves are available NPT
threaded or threaded per ISO 7-1 as
detailed in the Ordering Procedure sec-
tion. Valves with NPT threaded ports
will readily accept the trim arrange-
ments detailed in Figures 4 through 6.
* 4, 6, and 8 inch (DN100, DN150, and DN200) valve sizes
For Fire Protection pressure rating, listing
and approval information, contact
your Tyco Representative.

TFP910
Page 2 of 20
Nominal
Valve Size,
Inches
(DN)
Groove x Groove,
Lbs.
(kg)
Flange x Groove,
Lbs.
(kg)
Flange x Flange,
Lbs.
(kg)
2-1/2
(65)
22
(10,0)
28
(12,7) N/A
4
(100)
38
(17, 2 )
47
(21,3)
57
(25,9)
6
(150)
58
(26,3)
70
(31,8)
84
(38,1)
8
(200)
102
(46,3)
120
(54,4)
149
(67,6 )
1
QTY.
1
1
1
1
1
1
1
1
1
2
4
1
4
QTY.
6
6
1
4
. . . . . . .
. . .
. . . . . . . . . .
. . . .
. . . . . . . .
. . .
. . .
. . . . . . .
. .
. . . .
. . .
. . . . . . . . . . .
. . . . . . . . . .
. . . . .
. . . . .
. . . . . . . . .
. . . . . . .
. . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . .
. . . . . .
2
1
NO.
3
7
4
5
6
8
NO.
(a)
(b)
10
11
9
12
NO.
13
Handhole Cover
Valve Body NR
DESCRIPTION REF.
NR
See (a)
Handhole Cover
Gasket
See (a) or (b)Clapper Facing
Clapper Washer
VALVE PARTS
Seat Ring NR
See (b)
Lock Nut,
2-1/2 Inch Valve See (b)
Self-Locking Hex
Cap Screw, 4, 6, & 8
Inch Valves See (b)
REPLACEMENT PARTS
DESCRIPTION P/N
92-200-1-416
92-200-1-620
92-200-1-816
92-200-1-216
92-200-1-218
See (b)Clapper Hinge Pin
Clapper Hinge
See (b)Clapper Spring
Pin Bushing,
2-1/2 Inch Valve NR
Valves
4, 6, & 8 Inch
NR
Clapper See (b)
92-200-1-423
92-200-1-623
92-200-1-823
Hex Bolt,
Handhole Cover
2-1/2 Inch Valve,
x 1-1/4" Long CH
DESCRIPTION REF.
VALVE PARTS
1/2-13 UNC-2A
6 Inch Valve,
x 1-3/4" Long CH
1/2-13 UNC-2A
8 Inch Valve,
x 2" Long CH
3/4-10 UNC-2A
4, 6, & 8 Inch
Plug, 3/8" NPT,
Valves only CH
Square Head Pipe
Clapper Hinge Pin
4 Inch Valve,
x 1-3/4" Long CH
1/2-13 UNC-2A
Repair Parts Kit,
Includes 3 & 6
4 Inch Valve
6 Inch Valve
Clapper Assembly,
Includes 5-9, 11
4 Inch Valve
6 Inch Valve
8 Inch Valve
8 Inch Valve
2-1/2 Inch Valve
2-1/2 Inch Valve
Includes 5-11
F x F valve shown for reference;
components for G x G and F x G
1.
NOTES:
valves are shared.
NR: Not Replaceable
CH: Common Hardware
2.
3.
5
7
6
8
10
11
2
12
9
3
10
4
13
1
5
11
6
7
8
10
CLAPPER
ASSEMBLY
2-1/2 INCH
VALVE
CLAPPER
ASSEMBLY
4, 6, & 8 INCH
VALVES
FIGURE 1
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200)
MODEL AV-1-300 ALARM CHECK VALVE ASSEMBLY
TABLE A
AVAILABLE VALVE END CONNECTIONS AND VALVE WEIGHTS

TFP910
Page 3 of 20
6 INCH (DN150)
4 INCH (DN100)
2-1/2 INCH (DN65)
8 INCH (DN200)
600400 1000
FLOW RATE IN LITRES PER MINUTE (LPM)
(1 GPM = 3,785 LPM)
FLOW RATE IN GALLONS PER MINUTE (GPM)
0.9
300
0.8
0.7
500400
NOMINAL PRESSURE DROP
IN POUNDS PER SQUARE INCH (PSI)
1.0
2.0
3.0
4.0
2000
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0,06895 BAR)
0,06
3000700 1000 2000 4000
0,05
0,08
0,07
0,09
0,10
0,20
1000050003000 7000 15000
200100
2 3
2
3
1
1
Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16).
7.50
(190,5)
9.50
(241,3)
0.75
(19,0)
0.88
(22,2)
7.00
(178,0)
9.25
(235,0)
0.71
(18,0)
0.87
(22,0)
6.89
(175,0)
0.91
(23,0)
0.75
(19,0)
9.45
(240,0)
11.75
(298,5)
0.88
(22,2)
11.50
(292,0)
0.87
(22,0)
11.61
(295,0)
0.91
(23,0)
11.42
(290,0)
5.50
(139,7)
0.75
(19,0)
5.00
(127,0)
5.51
(140,0)
0.87
(22,0)
0.71
(18,0)
0.71
(18,0)
0.87
(22,0)
0.87
(22,0)
0.71
(18,0)
0.75
(19,0)
4 Inch
(DN100)
6 Inch
(DN150)
8 Inch
(DN200)
2-1/2 Inch
(DN65) 4
8
8
8 8
7.09
(180,0)
9.45
(240,0)
11.61
(295,0)
5.71
(145,0) 4
8
8
12
4
8
8
12
4
8
8
8
Dim.
A
Dim.
B
Qty. Dim.
A
Dim.
B
Qty. Dim.
A
Dim.
B
Qty. Dim.
A
Dim.
B
Qty. Dim.
A
Dim.
B
Qty.
Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10).
Dim. A
Bolt Circle
Diameter
Dim. B
Bolt Hole
Diameter
Qty. N
Number of
Bolt Holes
Nominal
Valve
Size
Same drilling as for B16.5 (Class 150) and B16.42 (Class 250).
ANSI B16.1
(Class 125)
AS 2129
(Table E)
ISO 2084
(PN10)
JIS B 2210
(10K)
Flange Drilling Specication
Nominal Dimensions in Inches and (mm)
ISO 2084
(PN16)
USE
ISO 2084
(PN16)
GRAPH A
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW
TABLE B
FLANGE DRILLING SPECIFICATIONS

TFP910
Page 4 of 20
Operation
When the re protection system is ini-
tially pressurized, water ows into the
system until the water supply and sys-
tem pressure become equalized, and
the torsion Spring closes the Water-
way Clapper in the Alarm Check Valve.
Once the pressures stabilize, the Alarm
Check Valve is in service and the cen-
trally located groove in the Seat Ring is
sealed. Consequently, with the Alarm
Check Valve set for service, there is
no ow through the alarm port to the
alarm devices (i.e., water motor alarm
and/or pressure alarm switch).
When there is a steady ow of water
into the sprinkler system due to a sprin-
kler operation, the Waterway Clapper
opens as shown in Figure 2. Water is
then permitted to ow into the centrally
located groove in the Seat Ring and
out through the alarm port towards the
Restriction Assembly (Figure 3). When
the ow through the Inlet Restriction of
the Restriction Assembly exceeds the
ow through the Outlet Restriction, the
Retard Chamber (where provided for
systems with variable pressure), begins
to ll.
Subsequently, the Water Motor Alarm
and/or the pressure alarm switch will
be actuated. The alarms will continue
to be actuated as long as the Water-
way Clapper remains open. Water in
the alarm lines will automatically drain
out through the 1/8 inch (3,2 mm) Drain
Orice in the Restriction Assembly
(Figure 3) when the Waterway Clap-
per closes (due to a stop in the ow of
water into the sprinkler system).
For variable pressure systems, slow
as well as small transient increases in
water supply pressure may continue to
build up in the system (via the Bypass
Check Valve) without opening the
Waterway Clapper.
A transient surge in supply pres-
sure that is sufcient only to open the
Waterway Clapper momentarily will not
cause a false alarm, and a portion of
the increase in pressure will be trapped
within the system, thus reducing the
possibility of another opening. Any
water in the alarm line is automatically
drained, further reducing the possibil-
ity of a false alarm due to a successive
transient surge in supply pressure.
Design
Criteria
In planning installation of the TYCO
Model AV-1-300 Alarm Check Valves,
consideration must be given to the dis-
posal of the large quantities of water
that may be associated with draining
the system or performing a ow test.
Valves installed in the vertical position
must have the ow going up. Valves
installed in the horizontal position must
be positioned so that the drain connec-
tion points down.
The sprinkler system designer must
be aware that the conguration of
the piping network and its tendency
to trap pockets of air (such as in the
case of a peaked-roof gridded sys-
tem) can affect the performance of the
alarm system. Although a slight amount
of trapped air is desirable to prevent
signicant pressure increases due to
thermally induced expansion of the
water, a large quantity of trapped air in
a system may result in the possibility of
an intermittent alarm.
The possibility of an intermittent alarm
condition is a consequence of the fact
that the ow out of the system through
the test valve or a single sprinkler is
very small relative to the ow that can
be passed through the valve. This dif-
ference increases with valve size. If the
system were free of trapped air, ow in
would equal ow out and the Waterway
Clapper would always stabilize at some
open position (as needed to accommo-
date the required ow). With trapped
air in the system, however, the Water-
way Clapper rst opens wider since the
system initially demands greater ow
until the air pockets are compressed
(back to nearly the supply pressure),
and then it will tend to return closer
PRESSURE
WATERFLOW
ALARM SWITCH
MOTOR ALARM
VALVE
RESTRICTION
(3,2 mm)
OUTLET
ORIFICE
RETARD CHAMBER
BEGINS TO FILL
INLET EXCEEDS OUTLET,
RESTRICTION ASSEMBLY
WHEN FLOW THROUGH
ASSEMBLY
1/8"
CHAMBER
RETARD
INLET
ALARM PORT
RING GROOVE AND
THROUGH SEAT
WATERFLOW
MAIN
DRAIN
ALARM ACTUATE
WATERFLOW PRESSURE
CHAMBER OVERFLOWS,
ONCE RETARD
WATER MOTOR
ALARM SWITCH AND
WATERFLOW
TO SYSTEM
WATERFLOW
TO WATER
7/32"
ORIFICE
(5,6 mm)
UPON SPRINKLER
FLOW, WATERWAY
CLAPPER OPENS
GAUGE
GAUGE
SUPPLY
PRESSURE
PRESSURE
SYSTEM
CHECK
VALVE
ALARM
SCREEN
DRAIN RESTRICTION
WITH 0.125" (3,2 mm)
ORIFICE
INLET RESTRICTION
WITH 0.219" (5,6 mm)
ORIFICE
FIGURE 2
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200)
MODEL AV-1-300 ALARM CHECK VALVE
OPERATION
FIGURE 3
RESTRICTION ASSEMBLY
(Provided with Alarm Check Valve Trim)

TFP910
Page 5 of 20
to the Seat Ring. If the volume of the
air pockets is excessive, ow into the
system can be momentarily reduced
to nearly zero (once the air pockets
are compressed) and the Waterway
Clapper may close, causing ow to the
alarms to be shutoff.
After the Waterway Clapper has
closed, sufcient water must ow out
of the system before the Waterway
Clapper will again open. A repetition
of the above described condition is
termed an intermittent alarm.
Using a vent (which can also serve
as an end-of-line Inspector’s Test
Connection) piped from the top of a
cross main or end of a branch line at
the point most remote from the alarm
valve, and lling the system slowly in
accordance with the steps described in
the Setting Procedure section, can pre-
vent an excessive amount of air from
being trapped.
Installation
NOTICE
Proper operation of the TYCO Model
AV-1-300 Alarm Check Valves depends
upon the trim described in this data
sheet installed in accordance with the
following instructions. Failure to fol-
low the appropriate trim installation
instructions may prevent the device
from functioning properly as well as
void listings/approvals and the manu-
facturer’s warranties.
The Alarm Check Valves must be
installed in readily visible and acces-
sible locations.
It is recommended that provision be
made for viewing the alarm line drain
water by locating the main drain outlet
in a readily visible area.
Wet pipe fire protection systems must
be maintained at a minimum tempera-
ture of 40°F (4°C).
Step 1. Trim the Alarm Check Valve in
accordance with Figure 4, 5, or 6, as
applicable. Apply pipe-thread sealant
sparingly to male threads only.
Step 2. The Alarm Vent Trim illustrated
in Figure 8 must be installed if a water
motor alarm is not to be used.
Step 3. Plug unused alarm
connections.
Step 4. Suitable provision must be
made for disposal of alarm line and
system drainage water. Drainage
water must be directed so that it will
not cause damage or result in danger-
ous conditions.
Step 5. The alarm line drain must be
arranged so that there will be no dan-
ger of freezing.
Step 6. The check valve in the exter-
nally mounted bypass around the
Waterway Clapper must be installed
with its arrow pointed up, and the drain
check valve must be installed with its
arrow pointing towards the drain.
Step 7. It is recommended that a vent
connection (which may also be used
as an end-of-line Inspector’s Test
Connection), be piped from a cross
main or branch line at the point most
remote from the alarm valve. The vent
line should be connected to the top of
a cross main or to the end of a branch
line and be located at the highest level
of a multi-level installation.
The vent connection can be used to
bleed-off excessive air from the sys-
tem, and therefore, minimize the
possibility of a false alarm due to a
transient surge in supply pressure. The
contraction/expansion associated with
an excessive amount of trapped air
could also cause the Waterway Clap-
per to cycle open and shut during an
inspector’s test or during a discharge
by a single sprinkler.
Setting
Procedure
Steps 1 through 11 are to be performed
when initially setting the Model AV-1-
300 Alarm Check Valve or after system
operation due to a re.
NOTICE
Filling the system with water will result
in operation of the associated alarms.
Consequently, notification must first be
given to the owner and fire department,
central station, or other signal station to
which the alarms are connected.
Notify the proper authorities and all
personnel who may be affected that
an alarm test is to be performed.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
Step 1. Open the 1/4 inch Gauge Test
Valves for the Supply and System Pres-
sure Gauges.
Step 2. Check to see that the Hand-
hole Cover bolts are tight. If not,
cross-tighten them.
Step 3. Close the Alarm Test Valve.
Step 4. Open the remote cross main or
branch line vent connection. (Refer to
Step 7 in the Installation section.)
Step 5. Slowly open the main control
valve until the sound of owing water
just begins and then open the valve
one more turn.
Step 6. Close the remote branchline
vent connection after the discharge of
aerated water ceases, and the outlet
has owed full for at least 15 seconds.
Step 7. Fully open the main control
valve.
Step 8. Open the end-of-line Inspec-
tor’s Test Connection (or Alarm Test
Valve, if acceptable to the authority
having jurisdiction) and verify that the
system alarms operate.
Step 9. Close the end-of-line Inspec-
tor’s Test Connection (or Alarm Test
Valve).
Step 10. Verify that water ceases to
ow from the alarm line drain. If water
continues to ow, follow the corrective
procedure described in the Care and
Maintenance section.
The Restriction Assembly has a 1/8
inch (3,2 mm) diameter drain orice.
Sufcient time must be allowed for
drainage of the Retard Chamber and
the piping to the water motor alarm.
Step 11. After verication that the ow
of water out of the alarm line drain has
stopped, the alarm valve is set and is
ready for service.

TFP910
Page 6 of 20
1
1
2
2
2
QTY.
2
1
1
1
1
1
2
2
1
1
1
2
1
2
7
1
1
1
1
1
1
2
2
1
QTY.
. . . . . . .
. . . . . . . . .
. .
.
. .
. . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . .
. . . .
. . . . . . . . . . . .
. . . . . . . . . . . .
. .
. . . . . . .
. . . . . .
. . . .
. . . .
. . . . . . . . . . . . . .
. . . . .
. . . . . . . .
. . . .
. . . .
. . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . .
12
14
13
6
1
4
10
5
11
2
3
8
9
7
NO.
15
19
17
18
16
22
27
29
28
24
26
25
23
20
21
NO.
1-1/4" Angle Valve
Alarm Test Tube
Connector
Connector
1/2" Union
1/4" 90° Elbow
1/4" Plug
1/2" NPT x 5/8" Tube
External By-Pass Tube
Restriction Assembly
1/2" NPT x 1/2" Tube
300 psi/ 2000 kPa
1/2" Globe Valve 46-047-1-004
1/2" Y-Strainer 52-353-1-005
Water Pressure Gauge
1/4" Gauge Test Valve
1/2" Swing Check Valve
46-005-1-002
46-049-1-004
92-343-1-005
DESCRIPTION P/N
CH
CH
CH
CH
92-210-2-005
1/2" 90° Elbow
CH1-1/4" x 1-1/4" x 1/2" Tee
CH
CH
92-304-1-017
92-304-1-047
46-048-1-007
CH1/2" x 1/4" x 1/2" Tee
1/2" x 1/2" x 3/4" Tee CH
1/2" Tee CH
P/N
CH1/2" x 1-1/2" Nipple
CH1/2" x 6" Nipple
1-1/4" x 3-1/2" Nipple CH
1-1/4" x 2-1/2" Nipple CH
CH1/2" x 2-1/2" Nipple
1/2" x 4" Nipple
1/2" x 3" Nipple
CH
CH
1/2" x 2" Nipple CH
CH1/4" x 1" Nipple
1/4" x 2-1/2" Nipple CH
DESCRIPTION
1-1/4 INCH NPT
CONNECTION
TO DRAIN
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
MODEL AV-1
ALARM VALVE,
2-1/2 INCH (DN65)
GROOVE x GROOVE
SHOWN
SUPPLY
PRESSURE
GAUGE
EXTERNAL
BY-PASS
TUBE ALARM
TEST TUBE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
All Fittings and Nipples are galvanized
(Standard Order).
CH: Common Hardware.
NOTES:
1.
2.
15 13
22 22
22
6
22
22
5
18
4
21
22
3
19
29
7
28
2427
16
23
26
20
17
14
2
12
2
3
16
10
11
8
11
23
22
25
17
20
10
9
1
12
1
FIGURE 4 (1 OF 3)
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER
FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-950)

TFP910
Page 7 of 20
2
1
1
1
3
2
1
2
2
4
5
1
2
1
1
2
2
QTY. QTY.
1
1
1
1
1
4
1
2
2
1
1
1
. . . . . . . . . .
. . . . .
. . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . .
. . . . .
. . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . .
. . . . . . . . .
.
. .
. .
. . . .
. . . . . . .
. . . .
. . . . .
. .
. .
. . . . . . . .
. . . . .
. . . . .
29
17
6
10
8
9
7
21
22
19
20
18
3
5
4
2
1
NO.
14
16
15
12
13
11
26
28
27
24
25
23
NO.
CH2" x 3" Nipple
CH1/4" x Close Nipple
Restriction Assembly 92-210-2-005
1/2" x 1-1/2" Nipple
1/2" x Close Nipple
Bushing
1/2" Union
2" Angle Valve
1/2" x 1/4" Reducing
1/4" Plug
46-048-1-009
CH
CH
CH
1/2" x 2" Nipple
1/2" x 3" Nipple
1/4" x 4" Nipple
CH
CH
CH
CH
CH
1/2" x 1/4" x 1/2" Tee
1/2" x 1/2" x 3/4" Tee
2" x 2" x 1/2" Tee
1/2" Globe Valve
1/2" Swing Check Valve
Water Pressure Gauge
300 psi/ 2000 kPa
DESCRIPTION
1/2" Y-Strainer
1/4" Gauge Test Valve
46-047-1-004
46-049-1-004
92-343-1-005
52-353-1-005
46-005-1-002
P/N
1/2" 90° Elbow
1/2" 45° Elbow
1/2" Tee
CH
CH
CH
CH
CH
CH
1/2" x 6-1/2" Nipple
1/2" x 5" Nipple
1/2" x 3-1/2" Nipple
Select Nipple per Table
Select Nipple per Table
1/2" x 5-1/2" Nipple
DESCRIPTION
CH
CH
CH
CH
CH
CH
P/N
Select Appropriate Nipple Sizes
per AV-1 Alarm Check Valve Size
4 Inch (DN100)
1/2" x 1-1/2"
1/2" x 3-1/2"
27
28
Nipple
Number 6 Inch (DN150)
1/2" x 2-1/2"
1/2" x 4-1/2"
All Fittings and Nipples are galvanized
(Standard Order).
Install subassemblies in alphabetical order.
NOTES:
3.
1.
2.
CH: Common Hardware.
2 INCH NPT
CONNECTION
TO DRAIN
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
MODEL AV-1
ALARM VALVE,
6 INCH (DN150)
FLANGE xFLANGE
SHOWN
SUPPLY
PRESSURE
GAUGE
1/2" x 1-1/2"
(4 INCH VALVE)
or
1/2" x 2-1/2"
(6 INCH VALVE)
1/2" x 3-1/2"
(4 INCH VALVE)
or
1/2" x 4-1/2"
(6 INCH VALVE)
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
K
H
M
N
C
A
LB
D
E
I
G
J
F
11 1919 203
6
19
10
7
20 22 21
12 20
11
19
14
26
5
15
20
11
16
29
29
10 24
3 20
13
17
4
10
25
27 23
28
21
11
22
28
18
1
2
9
8
1
FIGURE 4 (2 OF 3)
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER — SEMI-PREASSEMBLED
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-951)

TFP910
Page 8 of 20
1
1
1
2
1
2
1
1
3
3
2
1
1
1
1
1
1
1
2
2
QTY. QTY.
1
1
2
2
1
1
1
1
2
2
2
1
1
. . . . . . . . .
. . . . . . .
. . . . .. . . .
. . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . .
. . . . . . .
. . . . . . . . . .
. . . . . . . .
. . . . .
. . . . . . . .
. . . . .
. . . . .
. . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . .
.
.
. .
. .
. . . . . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . .
. . . .
. . . .
17
6 28
10
8
9
7
21
19
20
18
32
30
31
29
3
5
4
2
1
NO.
14
16
15
12
13
11
25
27
26
23
24
NO.
33
22
2" x 2" x 1/2" Tee
1/2" Y-Strainer 52-353-1-005
CH
3/4" x 2-1/2" Nipple CH
1/4" x 1-1/2" Nipple
1/2" x 1-1/2" Nipple
1/2" x Close Nipple
Restriction Assembly
1/2" Union
2" Angle Valve
1/4" Plug
92-210-2-005
46-048-1-009
CH
CH
1/2" x 2" Nipple
CH
CH
CH
CH
2" x 3-1/2" Nipple
2" x 3" Nipple
3/4" x 3" Nipple
3/4" x 4-1/2" Nipple
CH
CH
CH
CH
3/4" x 1/4" x 3/4" Tee
3/4" x 3/4" x 1/2" Tee
1/2" Globe Valve
1/2" Swing Check Valve
Water Pressure Gauge
300 psi/ 2000 kPa
DESCRIPTION
1/4" Gauge Test Valve
3/4" Swing Check Valve
46-047-1-004
46-049-1-004
92-343-1-005
46-005-1-002
46-049-1-005
P/N
1/2" Tee
1/2" 90° Elbow
1/2" 45° Elbow
3/4" Union
CH
CH
CH
CH
CH
CH
1/2" x 3" Nipple
1/2" x 3-1/2" Nipple
3/4" x 1-1/2" Nipple
1/2" x 6-1/2" Nipple
1/2" x 4-1/2" Nipple
3/4" x Close Nipple
DESCRIPTION
CH
CH
CH
CH
CH
CH
P/N
CH1/2" x 1/2" x 3/4" Tee
All Fittings and Nipples are galvanized
(Standard Order).
Install subassemblies in alphabetical order.
NOTES:
3.
1.
2.
CH: Common Hardware.
2 INCH NPT
CONNECTION
TO DRAIN
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
SUPPLY
PRESSURE
GAUGE
MODEL AV-1
ALARM VALVE,
8 INCH (DN200)
FLANGE x GROOVE
SHOWN
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
320
12 20 21
7
10
21
8
21 23
13
6
20
15
26
14
19
18
33
32
28
17
16
2
9
9
2
24
25
10
25
5
24
12
22
27
30
29
11
4
31
27
16
19
1
1
FIGURE 4 (3 OF 3)
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER — SEMI-PREASSEMBLED
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-952)

TFP910
Page 9 of 20
2
1
2
1
1
1
1
1
1
2
1
1
1
2
1
1
1
2
1
1
2
3
2
1
1
2
2
QTY.
2
QTY.
1
1
1
2
. . . . . . . . . . . . . .
. . . . . . .
. .
. . . . . . . . .
. . . .
. . . . . . .
.
. . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . .
. . . .
. . . .
. . . . .
. . . . .
. . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . .
. . . .
. .
. . . . . .
. .
. . . . . . . . .
. . . . . . . . . . . . .
19
9
2
21
22
20
26
29
30
28
27
25
24
23
32
31
6
4
5
3
15
16
13
14
12
11
10
18
17
NO.
1
NO.
8
7
1/2" Tee CH
46-005-1-002
Alarm Test Tube
1/4" Gauge Test Valve
92-304-1-047
Restriction Assembly
1/2" Swing Check Valve
1/2" Globe Valve
1/2" Y-Strainer 52-353-1-005
46-047-1-004
46-049-1-004
92-210-2-005
1/2" NPT x 1/2" Tube
1/2" NPT x 5/8" Tube
Support Bracket
Drip Funnel
Connector
Support Bar
PVC Nipple
Jam Nut
Connector
92-343-1-006
92-343-1-007
CH
92-304-1-014
92-640-1-009
92-640-1-037
CH
1/2" x 2-1/2" Nipple
1/2" x 3" Nipple
1/2" x 4" Nipple
1/2" x 5" Nipple
1-1/4" x 2-1/2" Nipple
1-1/4" x 8-1/2" Nipple
1-1/4" x 1-1/4" x 1/2" Tee
1/4" x 1" Nipple
1/2" x 2" Nipple
1/2" x 1-1/2" Nipple
1/4" x 2-1/2" Nipple
1/2" x 1/2" x 3/4" Tee
1/2" x 1/4" x 1/2" Tee
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
300 psi/ 2000 kPa
Water Pressure Gauge
DESCRIPTION
92-343-1-005
P/N
External By-Pass Tube
1-1/4" Angle Valve
DESCRIPTION
46-048-1-007
92-304-1-017
P/N
1/4" 90° Elbow
1/4" Plug CH
CH
All Fittings and Nipples are galvanized
(Standard Order).
CH: Common Hardware.
NOTES:
1.
2.
SUPPORT
BRACKET
SUPPORT
BAR
EXTERNAL
BY-PASS
TUBE ALARM
TEST TUBE
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
SUPPLY
PRESSURE
GAUGE
DRIP
FUNNEL
MODEL AV-1
ALARM VALVE,
2-1/2 INCH (DN65)
GROOVE x GROOVE
SHOWN
1-1/4 INCH NPT
CONNECTION
TO DRAIN
1-1/4 INCH NPT
CONNECTION
TO DRAIN
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
19
25
32
22
31 12
16
25
6
14 15
13
30
22
31
7
27
5
21
26
4
10 25
19
11
8
10
3
26
11
24
2
20
29
23
23
28
20
18
2
17
9
1
17
1
FIGURE 5 (1 OF 3)
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER
FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-053)

TFP910
Page 10 of 20
2
1
1
1
2
1
1
1
3
4
1
1
2
1
2
1
1
1
2
2
QTY.
3
1
1
1
2
1
1
1
1
1
2
QTY.
. .
. . . .
. . . .
. . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . .
. .
. . . .
. . . . . . . . . . . . . .
. . . . .
. . . . .
. . . . . . . .
. . . . .
. . . . . . . . . .
. .
. . . . . . .
. . . . . . . . .
.
. .
. .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . .
. . . . .
. . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . .
29
6
17
10
11
7
9
8
22
18
20
19
21
31
30
3
4
5
1
2
NO.
13
12
15
16
14
26
28
27
24
25
23
NO.
CHSelect Nipple per Table
92-210-2-005Restriction Assembly
1/2" x 1/2" x 3/4" Tee CH
46-048-1-009
92-211-1-003
92-211-1-005
92-343-1-007
1/4" Plug
2" Angle Valve
Drip Funnel Bracket
Drip Funnel
Drip Funnel Connector
CH
1/2" x 1-1/2" Nipple
1/4" x 4" Nipple
1/2" x Close Nipple
1/4" x Close Nipple
1/2" Tee
CH
CH
CH
CH
CH
Select Nipple per Table
2" x 3" Nipple CH
CH
92-343-1-005
46-005-1-002
52-353-1-005
46-047-1-004
46-049-1-004
DESCRIPTION
1/2" Swing Check Valve
1/2" Y-Strainer
1/2" Globe Valve
Water Pressure Gauge
1/4" Gauge Test Valve
300 psi/ 2000 kPa
P/N
1/2" x 1/4" Reducing
1/2" x 1/4" x 1/2" Tee
1/2" 90° Elbow
1/2" 45° Elbow
Bushing
1/2" Union
CH
CH
CH
CH
CH
1/2" x 6-1/2" Nipple
1/2" x 3-1/2" Nipple
1/2" x 5" Nipple
1/2" x 2" Nipple
1/2" x 3" Nipple
1/2" x 5-1/2" Nipple
DESCRIPTION
CH
CH
CH
CH
CH
CH
P/N
All Fittings and Nipples are galvanized
(Standard Order).
Install subassemblies in alphabetical order.
NOTES:
3.
1.
2.
CH: Common Hardware.
Select Appropriate Nipple Sizes
per AV-1 Alarm Check Valve Size
4 Inch (DN100)
29 1/2" x 1-1/2"
30 1/2" x 3-1/2"
Nipple
Number
1/2" x 2-1/2"
1/2" x 4-1/2"
6 Inch (DN150)
2 INCH NPT
CONNECTION
TO DRAIN
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
MODEL AV-1
ALARM VALVE,
6 INCH (DN150)
FLANGE xFLANGE
SHOWN
SUPPLY
PRESSURE
GAUGE
DRIP
FUNNEL
1-1/4 INCH NPT
CONNECTION
TO DRAIN
1/2" x 1-1/2"
(4 INCH VALVE)
or
1/2" x 2-1/2"
(6 INCH VALVE)
1/2" x 3-1/2"
(4 INCH VALVE)
or
1/2" x 4-1/2"
(6 INCH VALVE)
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
H
B
K
C
A
G
IJ
D
FE
30
22
22
23
8
9
10
18
6
22
21
21
15
14
731
13 26
14
322
18
17
28
5
21
27
29 25
13
14
23
16
19
11
11
4
24
2
1
20
12
2
1
FIGURE 5 (2 OF 3)
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER — SEMI-PREASSEMBLED
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-954)

TFP910
Page 11 of 20
2
1
1
1
1
1
1
3
2
1
1
1
1
1
1
1
1
2
2
QTY.
1
2
1
1
1
2
2
2
1
2
1
QTY.
1
1
. . . .
. . . . .
. . . .
. . . . . . . . . . .
. . . .
. . . . . . . . .
. .
. . . . .
. . . . .
. . . .
. . . . . . . .
. . . . .
. . . . .
. . . . . . . . . .
. . . . . . . . .
. . . . . . .
.
. .
. .
. . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . . . . .
. . . .
. . . . .
28
17
6
10
8
9
7
21
19
20
18
32
30
31
29
3
5
4
2
1
NO.
14
16
15
12
13
11
25
27
26
23
24
NO.
22
CH
3/4" x 1-1/2" Nipple CH
92-210-2-005Restriction Assembly
3/4" x 1/4" x 3/4" Tee
92-211-1-005
92-211-1-003
92-343-1-007
46-048-1-009
Drip Funnel Connector
Drip Funnel
Drip Funnel Bracket
2" Angle Valve
1/4" x 1-1/2" Nipple
1/2" x Close Nipple
3/4" x 3/4" x 1/2" Tee
CH
CH
CH
2" x 3" Nipple
3/4" x 4-1/2" Nipple
3/4" x 3" Nipple
3/4" x 2-1/2" Nipple
CH
CH
CH
CH
92-343-1-005
46-049-1-005
46-005-1-002
52-353-1-005
46-047-1-004
DESCRIPTION
Water Pressure Gauge
300 psi/ 2000 kPa
3/4" Swing Check Valve
1/4" Gauge Test Valve
1/2" Y-Strainer
1/2" Globe Valve
P/N
1/2" 90° Elbow
1/2" 45° Elbow
1/2" Tee
3/4" Union
1/2" Union
1/4" Plug
CH
CH
CH
CH
CH
CH
1/2" x 6-1/2" Nipple
3/4" x Close Nipple
1/2" x 3-1/2" Nipple
1/2" x 4-1/2" Nipple
1/2" x 2" Nipple
DESCRIPTION
CH
CH
CH
CH
CH
P/N
CH1/2" x 1/2" x 3/4" Tee
1/2" x 1-1/2" Nipple CH
All Fittings and Nipples are galvanized
(Standard Order).
Install subassemblies in alphabetical order.
NOTES:
3.
1.
2.
CH: Common Hardware.
DRIP
FUNNEL 2 INCH NPT
CONNECTION
TO DRAIN
1-1/4 INCH NPT
CONNECTION
TO DRAIN
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE ALARM
SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
3/4 INCH NPT
CONNECTION FOR
WATER MOTOR
ALARM
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
SUPPLY
PRESSURE
GAUGE
MODEL AV-1
ALARM VALVE,
8 INCH (DN200)
FLANGE x GROOVE
SHOWN
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE G
E
H
A
F
D
C
B
8
9
10 7
15
21
16
6
22 21
32
21
17
26
5
16 24
25
12 4
24
25
14
23
20
28
19
18
27
29
30
13
3
31
27
18
20
1
11
2
1
2
11
FIGURE 5 (3 OF 3)
VERTICAL OPEN DRAIN TRIM — SPECIAL ORDER — SEMI-PREASSEMBLED
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-955)

TFP910
Page 12 of 20
3
1
2
1
1
1
8
1
1
1
1
2
3
5
1
1
QTY.
2
2
1
2
2
2
1
2
2
1
QTY.
. . . . . . . .
. . . . . . . .
. . . . .
. . . . . . . . .
. . . . . . .
. . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . .
. . . .
. . . . .
. . . . .
. . . .
. . . .
. . . . . . .
. .
.
. .
. .
. . . . . . .
. . . . . . . .
. .
. .
. . . . .
19
20
5
12
16
17
13
14
15
18
10
11
8
9
7
6
NO.
3
4
2
1
25
26
21
23
24
22
NO.
92-210-2-005
CH
46-047-1-009
CH
CH
CH
46-005-1-002
52-353-1-005
92-343-1-005
46-049-1-004
46-047-1-004
P/N
CH
CH
CH
CH
CH
CH
CH
CH
CH
1/2" x 2" Nipple
1/2" x 3-1/2" Nipple
1/2" x 3" Nipple
Restriction Assembly
2" x 2" x 1/2" Tee
1/4" Plug
2" Globe Valve
1/4" x Close Nipple
1/4" x 4" Nipple
1/2" x 1/2" x 3/4" Tee
1/2" x 1/4" x 1/2" Tee
1/4" Gauge Test Valve
1/2" Y-Strainer
DESCRIPTION
300 psi/ 2000 kPa
Water Pressure Gauge
1/2" Swing Check Valve
1/2" Globe Valve
1/2" Tee
1/2" 90° Elbow
1/2" Union
1/2" x 1-1/2" Nipple
CHSelect Nipple per Table
2" x 2-1/2" Nipple CH
1/2" x 5" Nipple
Select Nipple per Table
Select Nipple per Table
1/2" x 5-1/2" Nipple
CH
CH
CH
CH
DESCRIPTION P/N
Select Appropriate Nipple Sizes
per AV-1 Alarm Check Valve Size
1/2" x 8"
1/2" x 2-1/2"
6 Inch (DN150)
1/2" x 4-1/2"
23
25
24
Nipple
Number
1/2" x 1-1/2"
1/2" x 7"
1/2" x 3-1/2"
4 Inch (DN100)
2 INCH NPT
CONNECTION
TO DRAIN
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE
ALARM SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION
FOR WATER
MOTOR
ALARM
3/4 INCH NPT
CONNECTION
FOR WATER
MOTOR
ALARM
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE
ALARM
SWITCH
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
MODEL AV-1
ALARM VALVE,
6 INCH (DN150)
FLANGE x FLANGE
SHOWN
HANDHOLE
COVER MUST
BE AT LEAST
30 INCHES
AWAY FROM
A WALL
SUPPLY
PRESSURE
GAUGE
1/2" x 3-1/2"
(4 INCH
VALVE)
or
1/2" x 4-1/2"
(6 INCH
VALVE)
1/2" x 1-1/2"
(4 INCH
VALVE)
or
1/2" x 2-1/2"
(6 INCH
VALVE)
1/2" x 7"
(4 INCH
VALVE)
or
1/2" x 8"
(6 INCH
VALVE)
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
All Fittings and Nipples are galvanized
(Standard Order).
CH: Common Hardware.
NOTES:
1.
2.
9
17
17
6
17
18
26
9
18
3
5
17
10
19 25
13
17
17
10
9
22
17
3
10
21
17
14
26
7
11
19
82
8
16 15
2
1
10
12
1
20
18
10
4
24
23
FIGURE 6 (1 OF 2)
HORIZONTAL CLOSED DRAIN TRIM — SPECIAL ORDER
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-057)

TFP910
Page 13 of 20
2
1
3
1
2
5
1
1
2
1
2
2
1
1
1
1
QTY.
2
1
1
2
QTY.
1
1
1
1
1
2
2
1
1
1
2
. . . . . . . .
. . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . .
. . . . .
. . . . .
. . . .
. . . .
. . . .
. .
.
.
. .
. . . . . . . . . .
. . . . .
. . . . .
. . . . . . .
. . . . . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . . . . .
20
5
12
13
15
16
14
18
19
17
11
10
9
7
8
6
NO.
3
4
2
1
27
30
31
29
28
23
24
26
25
21
22
NO.
CH
CH
CH
CH
CH
CH
P/N
46-049-1-005
46-005-1-002
92-343-1-005
46-049-1-004
46-047-1-004
CH
CH
CH
CH
CH
92-210-2-005
CH
52-353-1-005
46-047-1-009
1/2" x 2" Nipple
1/2" x 1/2" x 3/4" Tee
3/4" Union
1/2" 90° Elbow
1/2" Tee
3/4" Swing Check Valve
1/4" Gauge Test Valve
DESCRIPTION
300 psi/ 2000 kPa
Water Pressure Gauge
1/2" Swing Check Valve
1/2" Globe Valve
3/4" x 3/4" x 1/2" Tee
3/4" x 1/4" x 3/4" Tee
1/4" Plug
1/2" Union
Restriction Assembly
1/2" x 1-1/2" Nipple
1/4" x 1-1/2" Nipple
1/2" Y-Strainer
2" x 2" x 1/2" Tee
2" Globe Valve 2" x 2-1/2" Nipple
2" x 3" Nipple
3/4" x Close Nipple
1/2" x 4-1/2" Nipple
1/2" x 9-1/2" Nipple
3/4" x 1-1/2" Nipple
1/2" x 3-1/2" Nipple
1/2" x 3" Nipple
3/4" x 4-1/2" Nipple
3/4" x 3" Nipple
3/4" x 2-1/2" Nipple
DESCRIPTION
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
CH
P/N
2 INCH NPT
CONNECTION
TO DRAIN
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE
ALARM SWITCH
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
3/4 INCH NPT
CONNECTION
FOR WATER
MOTOR
ALARM
3/4 INCH NPT
CONNECTION
FOR WATER
MOTOR
ALARM
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
PRESSURE
ALARM
SWITCH
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
ALARM
TEST VALVE
(NORMALLY
CLOSED)
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
SYSTEM
PRESSURE
GAUGE
MODEL AV-1
ALARM VALVE,
8 INCH (DN200)
FLANGE x
GROOVE
SHOWN
HANDHOLE
COVER MUST
BE AT LEAST
30 INCHES
AWAY FROM
A WALL
SUPPLY
PRESSURE
GAUGE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
All Fittings and Nipples are galvanized
(Standard Order).
CH: Common Hardware.
NOTES:
1.
2.
15
18
30
17
20
10
19
12
19
19
7
14
6
19
12
21
24
13 23
19
3
31
8
12
10
22
20
5
22
11
27
15
25
18
9
23 28
4
25
2
26
16
29
9
1
1
2
FIGURE 6 (2 OF 2)
HORIZONTAL CLOSED DRAIN TRIM — SPECIAL ORDER
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-058)

TFP910
Page 14 of 20
ELEVATION VIEW
PLAN VIEW
ELEVATION VIEW
PLAN VIEW
Vertical Closed Drain Trim
Vertical Open Drain Trim
13-1/2 (343)15-1/2 (394)
10-1/2 (267)10-1/2 (267)
10 (254)10-1/2 (267)
12-1/4 (311)12-1/4 (311)
3 (75)3 (75)
16-1/2 (419) N/A
8-7/8 (225) 8-7/8 (225)
G
F
E
D
G x G &
F x G
C
A B
F x G
G x G &
BA
D
E
C
F
G
With RC-1
D
E
F
G
B
C
Dimension
A
Without RC-1
Dimensions in Inches and (mm)
16-1/2 (419)
8-7/8 (225)
10-1/2 (267)
12-1/4 (311)
16-1/2 (419)
10-1/2 (267)
3 (75)
N/A
3 (75)
13-1/2 (343)
10 (254)
12-1/4 (311)
8-7/8 (225)
10-1/2 (267)
RC-1
RC-1
Dimensions in Inches and (mm)
With RC-1
G
C
E
D
F
A
B
Dimension Without RC-1
FIGURE 7 (1 OF 3)
INSTALLATION DIMENSIONS
FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES

TFP910
Page 15 of 20
PLAN VIEW
ELEVATION VIEW
PLAN VIEW
ELEVATION VIEW
ELEVATION VIEW PLAN VIEW
Horizontal Closed Drain Trim
Vertical Closed Drain Trim
Vertical Open Drain Trim
G
F
A B
DE
C
G
F
A B
DE
C
E
D
C A
B
RC-1
RC-1
4 Inch (DN100)
10 (254)
15 (381)
3-1/4 (83)
10 (254)
14 (356)
13-3/4 (349)
10-1/4 (260)
Dimension
D
E
A (G x G)
A (F x F)
A (F x G)
C
B
Without RC-1
6 Inch (DN150)
14-3/4 (375)
11-1/2 (292)
12-1/4 (311)
6 Inch (DN150)
12 (305)
12 (305)
12-1/4 (311)
15 (381)
15 (381)
3-1/4 (83)
14-3/4 (375)
14 (356)
13-3/4 (349)
4 Inch (DN100)
10 (254)
10 (254)
10-1/4 (260)
10-1/2 (267)
3-1/4 (83)
With RC-1
15 (381)
12 (305)
3-1/4 (83)
12 (305)
Dimensions in Inches and (mm)
4 Inch (DN100)
Dimension
6 Inch (DN150)
Without RC-1With RC-1
6 Inch (DN150) 4 Inch (DN100)
Dimensions in Inches and (mm)
15-1/2 (394)
12-1/2 (318)
10-1/4 (260)
10-1/2 (267)
10-1/2 (267)
10 (254)
10 (254)
19 (483)
D (F x G)
F
G
E
D (F x F)
D (G x G)
C
A
B
11-1/2 (292)
11-1/4 (286)
11-1/2 (292)
12-1/4 (311)
2-3/4 (70)
15-1/2 (394)
12 (305)
12 (305)
12-1/4 (311)
11-1/2 (292)
11-1/4 (286)
19 (483)
15 (381)
3 (75)
10 (254)
3 (75)
11-1/2 (292)
12-1/2 (318)
19 (483)
10 (254)
10-1/2 (267)
10-1/2 (267)
10-1/4 (260)
12 (305)
2-3/4 (70)
15 (381)
12 (305)
19 (483)
4 Inch (DN100)
19 (483)
10-1/2 (267)
10-1/2 (267)
10-1/4 (260)
10 (254)
10 (254)
12-1/2 (318)
15-1/2 (394)
E
G
F
Dimension
D (G x G)
D (F x F)
D (F x G)
C
A
B
Dimensions in Inches and (mm)
Without RC-1
6 Inch (DN150)
11-1/4 (286)
11-1/2 (292)
12-1/4 (311)
11-1/2 (292)
6 Inch (DN150)
19 (483)
11-1/4 (286)
11-1/2 (292)
12-1/4 (311)
12 (305)
12 (305)
15 (381)
15-1/2 (394)
2-3/4 (70)3 (75)
With RC-1
12-1/2 (318)
11-1/2 (292)
3 (75)
4 Inch (DN100)
19 (483)
10-1/2 (267)
10-1/2 (267)
10-1/4 (260)
10 (254)
10 (254)
15 (381)
2-3/4 (70)
12 (305)
12 (305)
19 (483)
RC-1
FIGURE 7 (2 OF 3)
INSTALLATION DIMENSIONS
FOR 4 & 6 INCH (DN100 & DN150) MODEL AV-1-300 ALARM CHECK VALVES

TFP910
Page 16 of 20
ELEVATION VIEW
PLAN VIEW
ELEVATION VIEW
ELEVATION VIEW PLAN VIEW
PLAN VIEW
Vertical Closed Drain Trim
Vertical Open Drain Trim
Horizontal Closed Drain Trim
14 (356)14 (356)
N/A
15-1/2 (394)
2-1/2 (64) 2-1/2 (64)
16-1/2 (419) 16-1/2 (419)
12 (305) 12 (305)
16-1/8 (410) 16-1/8 (410)
18-1/2 (470) 15-3/4 (400)
14 (356)
12 (305)
N/A
19-1/2 (495)
16-1/2 (419)16-1/2 (419)
15 (381)
1-1/2 (38)
19-1/2 (495)
14 (356)
C
BA
E
G
F
G
F
C
A B
B
C
D
E
G x G
F x F
F x G &
E
3-1/2 (89)
15-1/2 (394)
16-1/2 (419)
16-1/8 (410)
18-1/2 (470)
3-1/2 (89)
N/A
16-1/2 (419)
16-1/8 (410)
15-3/4 (400)
14 (356)
12 (305)
14 (356)
12 (305)
D
F x G &
G x G
F x F
D
A
F x F
G x G
F x G &
B
E
G
F
C
D
With RC-1
Dimensions in Inches and (mm)
Dimensions in Inches and (mm)
With RC-1
Dimension
A
G
C
F
D
E
B
A
Dimension
Without RC-1
Without RC-1
Dimensions in Inches and (mm)
Without RC-1
B
E
C
D
Dimension
A
With RC-1
RC-1
RC-1
RC-1
FIGURE 7 (3 OF 3)
INSTALLATION DIMENSIONS
FOR 8 INCH (DN200) MODEL AV-1-300 ALARM CHECK VALVES

TFP910
Page 17 of 20
Trim kit is ordered separately when a
Water Motor Alarm is not installed.
Care and
Maintenance
The following procedures and
inspections should be performed in
accordance with this section, in addi-
tion to any specic requirements of the
NFPA. Any impairment must be imme-
diately corrected.
NOTICE
Performing the care and maintenance
procedures will result in operation of
the associated alarms. Consequently,
notification must first be given to the
owner and fire department, central sta-
tion, or other signal station to which the
alarms are connected.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
The TYCO Model AV-1-300 Alarm
Check Valves do not require any reg-
ularly scheduled maintenance. It is
recommended, however, that proper
operation of the alarms be periodically
veried in accordance with a proce-
dure that is acceptable to the authority
having jurisdiction. Any impairment
must be immediately corrected.
Inspection Procedure
It is recommended that the following
inspection procedure be performed at
least quarterly by a qualied Inspection
Service.
Step 1. Notify the proper authorities
and all personnel who may be affected
that an alarm test is to be performed.
Step 2. Open the end-of-line Inspec-
tor’s Test Connection (or Alarm Test
Valve, if acceptable to the authority
having jurisdiction) and verify that the
system alarms operate in accordance
with the requirements of the authority
having jurisdiction. Verify that the water
motor alarm and/or the pressure alarm
switch properly actuate and within the
elapsed time required by the authority
having jurisdiction.
Step 3. Verify that water is owing
out of the alarm line drain at a rate
consistent with the 1/8 inch (3,2 mm)
diameter drain orice in the Restriction
Assembly.
Step 4. Close the end-of-line Inspec-
tor’s Test Connection (or Alarm Test
Valve).
Step 5. Verify that water ceases to ow
from the alarm line drain.
Step 6. Clean the 1/2 inch Strainer
(located in the valve trim) as well as
the 3/4 inch Strainer (located at the
connection to the water motor alarm,
as applicable). Be sure to replace the
strainer baskets and tighten the caps
securely.
NOTICE
Cleaning of the Strainers after each
operation of the alarms is especially
important in the case of water sup-
plies (such as lakes and rivers) having
a large quantity of suspended matter. A
clogged alarm line can prevent opera-
tion of the alarms.
Step 7. Notify all authorities responsi-
ble for monitoring the installation that
the re protection system has been
returned to service.
Sprinkler System Drain-Down
Draining the sprinkler system must be
done in accordance with the following
procedure:
Step 1. Close the main control valve, if
this has not already been done.
Step 2. Open the remote cross main or
branch line vent connection. (Refer to
Step 7 in the Installation section.)
Step 3. Open the Main Drain Valve.
Check rst to see that the drainage
water discharge will not cause dam-
age or result in dangerous conditions.
Step 4. Wait until the Supply Pressure
Gauge reads zero pressure and the
sound of draining water has stopped
before performing any maintenance
work on the re protection system.
Leakage from Alarm Line Drain
Follow the steps indicated below until
water ceases to ow from the alarm
line drain. After each step check if leak-
age has stopped.
Step 1. Open the Main Drain Valve. Let
the water ow for about 5 seconds and
then close the Main Drain Valve. This
should ush any loose debris that may
have become trapped between the
Clapper Facing and the Seat Ring or
in the seating area of the Drain Valve.
Step 2. Repeat Step 1 if the rate of
continued ow out of the drain was
noticeably reduced.
Step 3. Open the Alarm Test Valve and
allow water to ow for about 5 seconds
before re-closing the valve. This should
ush any loose debris that may have
become trapped in the seating area of
the Alarm Test Valve.
Step 4. Repeat Step 3 if the rate of
continued ow out of the drain was
noticeably reduced.
Step 5. Determine whether the water is
owing from the Alarm Port (Ref. Figure
1) or past the Alarm Test Valve. If the
leakage is past the Alarm Test Valve,
close the main control valve, and then
repair or replace the Alarm Test Valve
as necessary.
Step 6. If it appears that the leakage
noted in Step 5 is from the Alarm Port,
drain the system in accordance with
the prescribed procedure. After the
system has been drained, remove the
Handhole Cover.
Step 7. While holding the Spring down
by the coils, remove the Hinge Pin.
Remove the Spring and Waterway
Clapper Assembly.
1
1
QTY.
1
. . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . .
1
2
NO.
3
3/32" Vent
3/4" x 1/4" Hex
Fitting
Bushing
92-032-1-002
CH
DESCRIPTION P/N
1/4" x 5'-0"
Tubing CH
2
(GREEN
TINT)
MODEL RC-1
RETARD
CHAMBER
PRESSURE
SWITCH
3
(ROUTE TO
DRAIN)
1
FIGURE 8
ALARM VENT TRIM KIT
(P/N 52-201-2-012)

TFP910
Page 18 of 20
Step 8. Using a light, check for and
remove any debris that may have
become lodged within the Seat Ring
groove. Inspect the Seat Ring seat
for any damage. If the Seat Ring has
become dented across the seat then
the Alarm Check Valve will have to be
replaced. It is impractical to re-face a
Seat Ring in the eld.
Step 9. Check for and remove any
debris that may have become lodged
in the Clapper Facing. If a minor imper-
fection remains in the Clapper Facing,
then turn it over after thoroughly clean-
ing both surfaces with a clean cloth.
Replace the Clapper Facing if neces-
sary. Be sure to securely re-tighten
the retaining fastener for the Clapper
Washer.
Step 10. Replace the Spring and
Waterway Clapper Assembly as shown
in Figure 1. While holding the coils of
the Spring down, re-insert the Hinge
Pin. Be sure that the Hinge Pin is
pushed all the way to the rear of the
valve.
Step 11. Replace the Handhole Cover.
Return the Alarm Valve to operation in
accordance with the steps described in
the Setting Procedure section.
Clogged Alarm Line Drain
If water either does not ow or only
dribbles out of the alarm line drain dur-
ing an alarm test, then it is likely that
the screen protecting the Restriction
Assembly drain orice (Ref. Figure 3)
has become clogged.
NOTICE
For variable pressure systems, a
clogged alarm line drain will increase
the likelihood of a false alarm.
First break the union downstream of
the Drain Restriction and remove the
Drain Restriction for cleaning by back-
ushing the screen. Re-install the Drain
Restriction and re-assemble the drain
line.
Loss of Excess System Pressure
For variable pressure systems, the
System Pressure Gauge normally indi-
cates a pressure greater than that
shown by the Supply Pressure Gauge.
Also, the value should be close to that
of the peak supply pressure that has
occurred after the system was placed
in service.
NOTICE
For variable pressure systems, loss of
excess system pressure will increase
the likelihood of a false alarm.
Follow the procedure indicated below
to correct a loss of excess system
pressure condition.
Step 1. Check for signs of continued
leakage from the alarm line drain. If rust
stains and/or water deposits indicate
that continued leakage has been taking
place, take corrective action according
to the procedure described in the sub-
section entitled “Leakage from Alarm
Line Drain.”
Step 2. If there are no signs of contin-
ued leakage from the alarm line drain,
close the main control valve, slowly
remove the plug from the supply pres-
sure gauge test valve to relieve the
supply pressure, and then slowly open
the union in the externally mounted
bypass.
Step 3. Check for leakage past the
Bypass Check Valve. If there is leak-
age, debris may have become lodged
between its clapper and seat. Drain
the system in accordance with the
prescribed procedure and then clean
or replace the Bypass Check Valve as
required.
Step 4. Re-assemble the externally
mounted bypass, replace the plug into
the Gauge Test Valve, and return the
re protection system to operation in
accordance with the steps described
in the Operation section.
Step 5. If there are no signs of leak-
age past either the Alarm Check Valve
Clapper per Step 1 or the Bypass
Check Valve per Step 2, inspect the
sprinkler system for leakage.
Excess Pressure Due to
Thermal Expansion
Wet pipe sprinkler systems subject
to ambient temperatures in excess of
100°F (38°C) can experience signicant
increases in system pressure due to
the thermal expansion of the water. In
particular, a gridded wet-pipe system
with a relatively small air pocket and
no relief valve can be subjected to an
increase of more than 100 psi (6,9 bar),
due to an increase in ambient tempera-
ture of approximately 50°F (28°C).
As necessary, install a pressure
relief valve, in accordance with the
requirements of the authority having
jurisdiction, to automatically relieve
the excess pressure that could other-
wise be created in wet-pipe systems
exposed to signicant increases in
ambient temperature.
False Alarms
Follow the step below when repeated
false alarms occur in a variable pres-
sure system.
Step 1. Check for and correct the
cause of continued leakage out the
alarm line drain.
Step 2. Check for and clean a clogged
alarm line drain.
Step 3. Check for and correct the
cause of a loss in excess system
pressure.
Step 4. Drain the sprinkler system and
re-ll it using the steps described in the
Setting Procedure section.
Intermittent Alarms
If the pressure alarm switch gives a
steady signal, but the water motor gen-
erates an intermittent alarm, check for
binding in the water motor alarm drive
shaft.
If the water motor alarm and/or the
pressure alarm switch provide an
intermittent alarm, it is likely the conse
-
quence of an excessive amount of air
being trapped within the sprinkler sys-
tem. Drain down the sprinkler system
and rell it using the steps described in
the Setting Procedure section.
A discontinuance of an alarm may also
be caused by the Clapper closing due
to a sudden drop in supply pressure
or the shut-off of a pump in the supply
line. These types of problems can only
be corrected by maintaining a steady
supply pressure.

TFP910
Page 19 of 20
Limited
Warranty
For warranty terms and conditions,
visit www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name. Refer to Table
A (Page 3) for Flange Drilling Speci-
cations. The Price Book provides
Part Numbers (P/Ns) for factory pre-
trimmed Model AV-1-300 Valves.
Standard AV-1-300
Alarm Check Valve
(Assumes American Standard Flange
Drilling, American Threaded Ports, and
American Groove Outside Diameter, as
applicable.)
Specify: (size in inches) Model AV-1-
300 Alarm Check Valve with (end
connections), P/N (specify):
2-1/2 Inch Valves
2.88 inch (73,0 mm) Groove O.D. x
2.88 inch (73,0 mm) Groove O.D.
2-1/2 Inch G x G . . . . . . . P/N 52-203-1-110
ANSI Flange x
2.88 inch (73,0 mm) Groove O.D.
2-1/2 Inch F x G. . . . . . . . P/N 52-203-1-210
4 Inch Valves
4.50 inch (114,3 mm) Groove O.D. x
4.50 inch (114,3 mm) Groove O.D.
4 Inch G x G ..........P/N 52-203-1-113
ANSI Flange x
4.50 inch (114,3 mm) Groove O.D.
4 Inch F x G...........P/N 52-203-1-413
ANSI Flange x ANSI Flange
4 Inch F x F ...........P/N 52-203-1-013
6 Inch Valves
6.62 inch (168,3 mm) Groove O.D. x
6.62 inch (168,3 mm) Groove O.D.
6 Inch G x G ..........P/N 52-203-1-115
ANSI Flange x
6.62 inch (168,3 mm) Groove O.D.
6 Inch F x G...........P/N 52-203-1-615
ANSI Flange x ANSI Flange
6 Inch F x F ...........P/N 52-203-1-015
8 Inch Valves
8.62 inch (219,1 mm) Groove O.D. x
8.62 inch (219,1 mm) Groove O.D.
8 Inch G x G ..........P/N 52-203-1-916
ANSI Flange x
8.62 inch (219,1 mm) Groove O.D.
8 Inch F x G...........P/N 52-203-1-816
ANSI Flange x ANSI Flange
8 inch F x F ...........P/N 52-203-1-016
AV-1-300 Valve Trim
Standard Order
Specify: Vertical, Closed Drain Galva-
nized Trim for (size) Model AV-1-300
Alarm Check Valve, P/N (specify):
Vertical Closed Drain, Galvanized
(See Figure 4)
2-1/2 Inch ................ P/N 52-204-4-950
4 or 6 Inch* ............... P/N 52-204-4-951
8 Inch* .................. P/N 52-204-4-952
*Provided semi-preassembled
Special Order
Specify: (Vertical or Horizontal),
(Closed or Open) Drain Galvanized Trim
for (size) Model AV-1-300 Alarm Check
Valve, P/N (specify):
Vertical Open Drain, Galvanized
(See Figure 5)
2-1/2 Inch ................ P/N 52-204-4-053
4 or 6 Inch* ............... P/N 52-204-4-954
8 Inch* .................. P/N 52-204-4-955
*Provided semi-preassembled
Horizontal Closed Drain, Galvanized
(See Figure 6)
4 or 6 Inch................ P/N 52-204-4-057
8 Inch ................... P/N 52-204-4-058
Accessories
Order the following accessories, as
applicable:
Model RC-1
Retard Chamber .......P/N 52-211-1-002
(Required for variable pressure water sup-
ply conditions.)
Alarm Vent Trim....... P/N 52-201-2-012
(Required when a water motor alarm is not
installed.)
Model PS10-2 Potter Electric Waterow
Pressure Alarm Switch ....... P/N 25710
(Required for electric signal indicating
waterow.)
Model WMA-1 Water Motor Alarm
Red Finish Gong..........P/N 52-630-1-001P
Aluminum Finish Gong .....P/N 52-630-2-001P
(Required for a mechanical waterow
alarm.)
Optional 600 PSI Water
Pressure Gauge . . . . . . P/N 92-343-1- 004
Replacement Parts
Valve
Specify: (description) for use with (size)
Model AV-1-300 Alarm Check Valve,
P/N (specify, see Figure 1)
Trim
Specify: (description) for use with
Model AV-1-300 Alarm Check Valve,
P/N (specify, see Figure 4, 5, or 6)
Other Model AV-1-300
Configurations
Other AV-1-300 Alarm Check Valves
are valves ordered with any combina-
tion of ange, threaded port, or groove
outside diameter not offered under
Standard AV-1-300 Alarm Check Valve
offerings.
Valves with NPT threaded ports are
intended for use with the AV-1-300
Valve Trim described in this data sheet.
Valves with ISO threaded ports are
intended for use with special order trim
that is provided by local distributors
to meet the specic needs of certain
localities. Contact your local distribu
-
tor regarding valves and valve trim for
specic localities.
Specify: (size) Model AV-1-300 Alarm
Check Valve with (connections)
with (NPT or ISO) threaded ports,
P/N (specify):
2-1/2 Inch Valves with NPT Ports
ISO (PN16) Flange x
2.88 inch (73,0 mm)
Groove O.D. ..........P/N 52-203-1-251
ANSI Flange x
3.00 inch (76,1 mm)
Groove O.D. ..........P/N 52-203-1-220
ISO (PN16) Flange x
3.00 inch (76,1 mm)
Groove O.D. ..........P/N 52-203-1-331
AS Flange x
2.88 inch (73,0 mm)
Groove O.D ...........P/N 52-203-1-611
AS Flange x
3.00 inch (76,1 mm)
Groove O.D. ......... P/N 52-203-4-410
JIS Flange x
2.88 inch (73,0 mm)
Groove O.D. ..........P/N 52-203-1-710
JIS Flange x
3.00 inch (76,1 mm)
Groove O.D. ..........P/N 52-203-1-810
3.00 inch (76,1 mm) Groove O.D x
3.00 inch (76,1 mm)
Groove O.D. ..........P/N 52-203-1-120
2-1/2 Inch Valves with ISO Ports
ISO (PN16) Flange x
2.88 inch (73,0 mm)
Groove O.D. ..........P/N 52-203-1-211
ISO (PN16) Flange x
3.00 inch (76,1 mm)
Groove O.D. ..........P/N 52-203-1-311
3.00 inch (76,1 mm) Groove O.D. x
3.00 inch (76,1 mm)
Groove O.D. ..........P/N 52-203-4-120
2.88 inch (73,0 mm) Groove O.D. x
2.88 inch (73,0 mm)
Groove O.D. ..........P/N 52-203-1-921

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP910
Page 20 of 20
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
4 Inch Valves with NPT Ports
ISO (PN16) Flange x
4.50 inch (114,3 mm)
Groove O.D. ......... P/N 52-203-1-493
ISO (PN16) Flange x
ISO (PN16) Flange..... P/N 52-203-4-013
AS Flange x
AS Flange ........... P/N 52-203-4-313
AS Flange x
4.50 inch (114,3 mm)
Groove O.D. ......... P/N 52-203-4-413
JIS Flange x
JIS Flange ............P/N 52-203-4-713
JIS Flange x
4.50 inch (114,3 mm)
Groove O.D. ......... P/N 52-203-4-813
4 Inch Valves with ISO Ports
ISO (PN16) Flange x
ISO Flange ...........P/N 52-203-4-113
ISO (PN16) Flange x
4.50 inch (114,3 mm)
Groove O.D. ......... P/N 52-203-4-213
4.50 inch (114,3 mm) Groove O.D. x
4.50 inch (114,3 mm)
Groove O.D. ..........P/N 52-203-1-923
6 Inch Valves with NPT Ports
ANSI Flange x
6.50 inch (165,1 mm)
Groove O.D. ..........P/N 52-203-1-625
ISO (PN16) Flange x
6.62 inch (168,3 mm)
Groove O.D. ......... P/N 52-203-1-695
ISO (PN16) Flange x
6.50 inch (165,1 mm)
Groove O.D. ......... P/N 52-203-5-215
ISO (PN16) Flange x
ISO (PN16) Flange..... P/N 52-203-4-015
AS Flange x
AS Flange ........... P/N 52-203-4-315
AS Flange x
6.62 inch (168,3 mm)
Groove O.D. ......... P/N 52-203-4-415
AS Flange x
6.50 inch (165,1 mm)
Groove O.D. ......... P/N 52-203-4-425
JIS Flange x
JIS Flange ............P/N 52-203-4-715
JIS Flange x
6.62 inch (168,3 mm)
Groove O.D. ......... P/N 52-203-4-815
JIS Flange x
6.50 inch (165,1 mm)
Groove O.D. ......... P/N 52-203-5-815
6.50 inch (165,1 mm) Groove O.D. x
6.50 inch (165,1 mm)
Groove O.D. ..........P/N 52-203-1-124
6 Inch Valves with ISO Ports
ISO (PN16) Flange x
ISO (PN16) Flange..... P/N 52-203-4-115
ISO (PN16) Flange x
6.62 inch (168,3 mm)
Groove O.D. ......... P/N 52-203-4-215
ISO (PN16) Flange x
6.50 inch (165,1 mm)
Groove O.D. ......... P/N 52-203-4-225
6.62 inch (168,3 mm) Groove O.D. x
6.62 inch (168,3 mm)
Groove O.D. ..........P/N 52-203-1-925
6.50 inch (165,1 mm) Groove O.D. x
6.50 inch (165,1 mm)
Groove O.D. ..........P/N 52-203-1-125
8 Inch Valves with NPT Ports
ISO (PN10) Flange x
8.62 inch (219,1 mm)
Groove O.D. ......... P/N 52-203-1-896
ISO (PN16) Flange x
8.62 inch (219,1 mm)
Groove O.D. ......... P/N 52-203-4-266
ISO (PN10) Flange x
ISO (PN10) Flange..... P/N 52-203-4-016
ISO (PN16) Flange x
ISO (PN16) Flange......P/N 52-203-4-118
AS Flange x
AS Flange ........... P/N 52-203-4-316
AS Flange x
8.62 inch (219,1 mm)
Groove O.D. ......... P/N 52-203-4-416
JIS Flange x
JIS Flange ............P/N 52-203-1-716
JIS Flange x 8.62 inch (219,1 mm)
Groove O.D. ......... P/N 52-203-4-816
8 Inch Valves with ISO Ports
ISO (PN10) Flange x
ISO (PN10) Flange......P/N 52-203-4-116
ISO (PN16) Flange x
ISO (PN16) Flange......P/N 52-203-4-117
ISO (PN10) Flange x
8.62 inch (219,1 mm)
Groove O.D. ......... P/N 52-203-4-216
ISO (PN16) Flange x
8.62 inch (219,1 mm)
Groove O.D. ......... P/N 52-203-4-226
8.62 inch (219,1 mm) Groove O.D. x
8.62 inch (219,1 mm)
Groove O.D. ..........P/N 52-203-1-926
Table of contents
Other Tyco Fire Product Control Unit manuals
Popular Control Unit manuals by other brands

Siemens
Siemens SITRANS F M MAGFLO series operating manual

Speck
Speck P41 Removal/Assembly

Cepex
Cepex PVC-U Installation and maintenance manual

Acorn
Acorn SV16 Installation, operation and maintenance guide

DSC
DSC Downlook DLM-7 installation instructions

SmartOne
SmartOne 70-600000-001 installation instructions