EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product S1810 User manual

Tyco Fire Product

Tyco Fire Product S1810 User manual

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product CENTRAL H17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H17/32 User manual

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product

Tyco Fire Product Star DS-1 Series User manual

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product STAR S160E User manual

Tyco Fire Product

Tyco Fire Product STAR S160E User manual

Tyco Fire Product Star I-LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star I-LD-2 User manual

Tyco Fire Product CENTRAL TY-B Series User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B Series User manual

Tyco Fire Product Gem F978 User manual

Tyco Fire Product

Tyco Fire Product Gem F978 User manual

Tyco Fire Product Gem F685 User manual

Tyco Fire Product

Tyco Fire Product Gem F685 User manual

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product CENTRAL DS-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL DS-2 User manual

Tyco Fire Product CENTRAL BV-QR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-QR User manual

Tyco Fire Product CENTRAL EC-25 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL EC-25 User manual

Tyco Fire Product Gem G102 User manual

Tyco Fire Product

Tyco Fire Product Gem G102 User manual

Tyco Fire Product Star SuperNova S120 User manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S120 User manual

Tyco Fire Product Gem F938 User manual

Tyco Fire Product

Tyco Fire Product Gem F938 User manual

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-EC User manual

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Tyco Fire Product

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Popular Irrigation System manuals by other brands

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Reliable F1FR-300 quick start guide

Reliable

Reliable F1FR-300 quick start guide

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Tyco TY-L Series quick start guide

Tyco

Tyco TY-L Series quick start guide

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Victaulic

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

General
Description
The Model ESFR-17 Sprinklers (Ref.
Figure 1) are “Early Suppression Fast
Response Sprinklers” having a nomi-
nal K-factor of 16.8. They are suppres-
sion mode sprinklers, and they are es-
pecially advantageous as a means of
eliminating in-rack sprinklers, when
protecting rack storage.
TheModelESFR-17isprimarilyde-
signed for use in ceiling only sprinkler
systems (i.e. no in-rack sprinklers) for
the protection of storage heights of
most encapsulated or non-encapsu-
lated common materials including car-
toned unexpanded plastics of up to 35
ft. (10,7 m) with ceiling heights to 40 ft.
(12,2 m), as well as cartoned ex-
panded plastics up to 25 ft. (7,6 m) with
ceiling heights to 30 ft.(9,1 m). In addi-
tion, the protection of some storage
arrangements of roll paper and rubber
tires can be considered.
In some cases, the Model ESFR-17
can be used to protect storage heights
up to 40 ft. (12,2 m) with ceiling heights
to 45 ft. (13,7 m) in combination with
one level of in-rack sprinklers.
The ESFR-17 provides the system de-
signer with hydraulic options not pres-
ently available to traditional ESFR
sprinklers having a nominal K-Factor
of 14.0. In particular, the Model ESFR-
17 has been designed to operate at
substantially lower end head pres-
sures, as compared to ESFR sprin-
klers having a nominal K-Factor of
14.0. This feature offers flexibility when
sizing the system piping, as well as
possibly reducing or eliminating the
need for a system fire pump.
WARNINGS
The Model ESFR-17 Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction (e.g., FM Global). Fail-
ure to do so may impair the integrity of
these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Sprinkler
Identification
Numbers
SIN TY7226 - (Pendent K=16.8)
Technical
Data
Approvals
FM Approved. UL and C-UL Listed.
(Refer to the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT or ISO 7-R3/4
Discharge Coefficient
K = 16.8 GPM/psi1/2
(241,9 LPM/bar1/2)
Temperature Ratings
165°F/74°C or 214°F/101°C
Finish
Natural Brass
Physical Characteristics
Frame ............. Brass
Deflector............Bronze
Compression Screw . . . . . . . . .
............ StainlessSteel
Hook.............. Monel
Strut.............. Monel
Link Assembly . . . . Solder, Nickel
Button............. Brass
SealingAssembly ..........
. . . . . . Beryllium Nickel w/Teflon*
Ejection Spring . . . . . . . Inconel
Patents
U.S.A. Patent Numbers 4,580,729
5,829,532, and 6,059,044 may be ap-
plicable to the Model ESFR-17. Other
patents are pending.
Operation
The fusible link assembly is comprised
of two link halves that are joined to-
gether by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate activating the sprinkler and
allowing water to flow.
Page 1 of 4 TFP315
FEBRUARY, 2002
Model ESFR-17
Early Suppression Fast Response Pendent Sprinklers
16.8 K-factor
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Customer Service/Sales:
Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385
TFP315 (3-1.6)
OBSOLETE
Design
Criteria
FM APPROVAL CRITERIA
The Model ESFR-17 Sprinklers (SIN
TY7226) may be used to protect the
same types of storage and building
heights (up to 40 ft. (12,2 m) without
in-rack sprinklers, or 45 ft. (13,7 m)
with one level of in-rack sprinklers) as
14.0 K-Factor ESFR sprinklers, ex-
cluding storage of roll tissue, flam-
mable liquids, aerosols, and ex-
posed expanded plastics. Refer to
the appropriate FM Global Data Sheet
and Engineering Bulletin entitled “Tyco
Fire Products Model TY7226, K16.8
Suppression-Model Sprinklers” for de-
tails of appropriate applications and
design specifications.
A. Hydraulic Design: Design should
be 12 sprinklers, supplying four
sprinklers on three branch lines, at
the following pressures based on
equivalence to 14.0 K-Factor ESFR
sprinkler flows:
K=14.0 K=16.8
ESFR ESFR
Design Design
Pressure, Pressure,
psi (bar) psi (bar)
50 (3,4) 35 (2,4)
60 (4,1) 42 (2,9)
75 (5,2) 52 (3,6)
90 (6,2) 63 (4,3)
B. System Type: wet-pipe only (no
preaction or dry-pipe).
C. Sprinkler Spacing: The maximum
area of coverage is 100 ft2
(9,3m2) and the minimum area of
coverage is 80 ft2(7,4 m2).
The maximum distance between
sprinklers on branch lines or be-
tween branch lines is 12 ft. (3,7 m)
for buildings up to 30 ft. (9,1 m) high,
and 10 ft. (3,1 m) for buildings higher
than 30 ft. (9,1 m) to 45 ft. (13,7 m).
The minimum distance between
sprinklers on branch lines or be-
tween branch lines is 8 ft. (2,4 m).
C. Sprinkler Position: Position sprin-
klers so that the deflectors are lo-
cated at a maximum distance of 14
inches (360 mm) and a minimum
distance of 4 inches (100 mm) below
the ceiling.
D. Hose Stream Demand and Water
Supply Duration:
250 GPM (950 LPM) and 60 minutes
respectively.
F. Other Details: All other details are
the same as for pendent 14.0
K-Factor ESFR sprinklers as recom-
mended in the following FM Global
Data Sheets:
2-2, “Installation Guidelines for Early
Suppression Fast Response Sprin-
klers”
8-3, “Rubber Tire Storage”
8-9, “Storage of Commodities”
8-21, “Roll Paper Storage”
8-24, “Idle Pallet Storage”
G. Mixed Occupancies:
16.8 K-Factor ESFR sprinklers may
be used in adjacent non-storage oc-
cupancies which qualify for use with
quick response sprinklers as indi-
cated in FM Global Data Sheet 3-26,
Table 2, using design guidelines as
described above.
UL AND C-UL
SPECIFIC APPLICATION
LISTING CRITERIA
The Model ESFR-17 Sprinklers (SIN
TY7226) are UL and C-UL Listed as
“Specific Application Early Suppres-
sion Fast Response Sprinklers”. They
are intended for installation and to pro-
tect the same types of storage and
building heights as described in NFPA
13 for UL and C-UL Listed K=14.0
ESFR Sprinklers using the following
K=16.8 ESFR Design Pressures in lieu
of the given K=14.0 ESFR Design
Pressures stated in NFPA 13.
K=14.0 K=16.8
ESFR ESFR
Design Design
Pressure, Pressure,
psi (bar) psi (bar)
50 (3,4) 35 (2,4)
75 (5,2) 52 (3,6)
NOTE
Since UL and C-UL currently limit the
listing of K=14.0 ESFR Sprinklers to a
maximum ceiling height of 40 feet
(12,2 m), the specific application of the
Model ESFR-17 is for a maximum ceil-
ing height of 40 feet (12.2 m), even
though NFPA 13 may reference pro-
tection schemes using K=14.0 ESFR
Sprinklers for ceiling heights greater
than 40 feet (12,2 m).
Page2of4 TFP315
1-Frame
2-Deflector
3-Compression Screw
4-Hook
5-Strut
6-Link Assembly
7-Button
8-Sealing Assembly
9-Ejection Spring
FIGURE 1, MODEL ESFR-17 EARLY SUPPRESSION FAST RESPONSE PENDENT SPRINKLER
* Registered Trademark of DuPont
OBSOLETE
Installation
The Model ESFR-17 Pendent Sprin-
klers are to be installed in accordance
with the following instructions:
NOTE
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler
wrench. Damaged sprinklers must be
replaced.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Step 1. The ESFR-17 Sprinkler must
be installed in the pendent position.
Step 2. With pipe thread sealant ap-
plied, hand tighten the sprinkler into
the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle
the ESFR-17 Sprinkler only by the
Frame arms.
Step 3. Wrench tighten the ESFR-17
Sprinkler using only the W-Type 21
Sprinkler Wrench (Ref. Figure 2) and
by fully engaging (seating) the wrench
on the sprinkler wrench flats.
Step 4. After installation, inspect the
Link Assembly of each ESFR-17
Sprinkler for damage. In particular,
verify that the Link Assembly and Hook
are positioned as illustrated in Figure
1, and that the Link Assembly has not
been bent, creased, or forced out of its
normal position in any way.
Damaged sprinklers must be replaced.
Care and
Maintenance
The Model ESFR-17 must be main-
tained and serviced in accordance
with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified or over-heated sprin-
klers must be replaced.
Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage,
or the like, must be replaced.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES,ANDINNOEVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
TFP315 Page 3 of 4
FIGURE 2
W-TYPE 21
SPRINKLER WRENCH
OBSOLETE
Ordering
Procedure
When placing an order, indicate the full
product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Refer
to the Price List for complete listing of
Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (specify temperature rating),
natural brass, TY7226 Pendent Sprin-
kler, PSN (specify).
165°F/74°C . . . . . . . . . . . . . . . P/N 58-445-1-165
214°F/101°C . . . . . . . . . . . . . . P/N 58-445-1-214
Sprinkler Wrench
Specify: W-Type 21 Sprinkler Wrench,
P/N 56-001-0-686.
Page4of4 TFP315