fore, the F938 and F938/Q-76 must
only be used with the Model A Sprin-
klers shown in Table A.
INSTALLATION
The Models F938 and F938/Q-76 are
to be installed as follows:
1. TheF938ortheF938/Q-76istobe
mounted on the sprinkler after the
sprinkler has been installed in ac-
cordance with its applicable techni-
cal data sheet.
2. With the Clips loose, first spread the
two halves of the Sprinkler Guard
just enough to pass by the sprinkler
deflector from the side. Then, once
again spread the two halves of the
Sprinkler Guard just enough to pass
over the sprinkler wrench flats onto
the thread relief portion of the sprin-
kler.
3. With the Sprinkler Guard positioned
on the thread relief portion of the
sprinkler, engage the Clips and then
slide the Clips until they seat against
the Base to complete the installa-
tion.
NOTE
The F938 and F938/Q-76 may be
located in any position relative to
the sprinkler frame arms.
CARE AND MAINTENANCE
The Models F938 and F938/Q-76 do
not require any regularly scheduled
maintenance; however, proper instal-
lation of the Sprinkler Guards should
be verified during the annual visual
inspection of the sprinklers.
It is recommended that automatic
sprinkler systems be inspected quar-
terly by a qualified Inspection Service.
WARRANTY
Seller warrants for a period of one year
from the date of shipment (warranty
period) that the products furnished
hereunder will be free from defects in
material and workmanship.
For further details on Warranty, see
Price List.
ORDERING PROCEDURE
Contact your local distributor for avail-
ability.
Sprinkler Guard:
Specify: Model F938 Sprinkler Guard
having a (specify) finish,
PSN (specify).
Red Painted. . . . . . . . . . . . . . PSN 56-938-1-001
Zinc Chromate. . . . . . . . . . . . PSN 56-938-9-001
Sprinkler Guard with Shield:
Specify: Model F938/Q-76 Sprinkler
Guard with Shield having a (specify)
finish, PSN (specify).
Red Painted. . . . . . . . . . . . . . PSN 56-938-1-066
Zinc Chromate. . . . . . . . . . . . PSN 56-938-9-066
WEIGHT
The nominal weights of the F936 and
F938/Q-76 are as follows:
F938..................... 2.7oz.(74g)
F938/Q-76................ 4.8oz.(134g)
MODEL SPRINKLER
DESCRIPTION TD
SHEET
F938
F938/Q-76
TABLE A
SPRINKLER COMPATIBILITY AND APPROVAL STATUS
FOR MODEL F938 SPRINKLER GUARD
AND F938/Q-76 SPRINKLER GUARD WITH SHIELD
5.6 K-Factor, Model A Quick Response
Pendent & Upright Sprinklers
5.6 K-Factor, Model A Standard Response
Pendent & Upright Sprinklers
8.0 K-Factor, Model A Quick Response
Pendent & Upright Sprinklers
8.0 K-Factor, Model A Standard Response
Pendent & Upright Sprinklers
5.6 & 8.0 K-Factor, Model A Quick Response
Pendent Intermediate Level Sprinklers
8.0 K-Factor w/ 1/2" NPT, Model A Standard
Response Pendent & Upright Sprinklers
TD515M
TD516M
TD525Q
TD526Q
TD529
5.6 K-Factor, Model A Quick Response
Upright Sprinklers
5.6 K-Factor, Model A Standard Response
Upright Sprinklers
8.0 K-Factor, Model A Quick Response
Upright Sprinklers
8.0 K-Factor, Model A Standard
Response Upright Sprinklers
TD525M
TD516M
TD525Q
TD526Q
5.6 & 8.0 K-Factor, Model A Standard
Response Pendent Intermediate Level
Sprinklers
TD501M
TD500M
GUARD
APPROVALS
1, 2, 3
1, 2, 3
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).